Peripheral devices list
| Motor |
|
| Moulded Case Circuit Breaker (MCCB) *2 or |
| Input Side Magnetic | Recommended Cable | ||||||
|
|
|
| Earth Leakage Circuit Breaker (ELB) |
| Contactor*3 | Size (mm2)*4 | ||||||
Voltage | Output | Applicable Inverter Type |
| Reactor connection |
| Reactor connection |
|
| |||||
| (kW) |
|
|
|
|
| |||||||
| *1 |
| without |
| with | supply operation | without | with | R, S, T | U, V, W | |||
|
|
|
| available |
|
| |||||||
| 0.75 | 30AF | 10A |
| 30AF 10A | 30AF | 10A | 2 | 2 | ||||
| 1.5 | 30AF | 15A |
| 30AF 15A | 30AF | 15A | 2 | 2 | ||||
| 2.2 | 30AF | 20A |
| 30AF 15A | 30AF | 20A | 2 | 2 | ||||
| 3.7 | 30AF | 30A |
| 30AF 30A | 30AF | 30A | 3.5 | 3.5 | ||||
| 5.5 | 50AF | 50A |
| 50AF 40A | 50AF | 50A | 5.5 | 5.5 | ||||
| 7.5 | 100AF 60A |
| 50AF 50A | 100AF 60A | 14 | 8 | ||||||
| 11 | 100AF 75A |
| 100AF 75A | 100AF 75A | 14 | 14 | ||||||
| 15 | 225AF | 125A |
| 100AF | 100A | 225AF | 125A | 22 | 22 | |||
200V class | 18.5 | 225AF | 150A |
| 225AF | 125A | 225AF | 150A | 38 | 38 | |||
| 22 | 225AF | 175A |
| 225AF | 150A | 225AF | 175A | 38 | 38 | |||
| 30 | 225AF | 225A |
| 225AF | 175A | 225AF | 225A | 60 | 60 | |||
| 37 | 400AF | 250A |
| 225AF | 225A | 400AF | 250A | 80 | 80 | |||
| 45 | 400AF | 300A |
| 400AF | 300A | 400AF | 350A | 100 | 100 | |||
| 55 | 400AF | 400A |
| 400AF | 350A | 600AF | 500A | 100 | 100 | |||
| 75 | — |
| 400AF | 400A | 400AF | 400A | — | 125 | 125 | |||
| 90 | — |
| 400AF | 400A | 600AF | 500A | — | 150 | 150 | |||
| 110 | — |
| 600AF | 500A | 600AF | 600A | — | 2 × 100 | 2 × 100 | |||
| 0.75 | 30AF 5A |
| 30AF 5A | 30AF 5A | 2 | 2 | ||||||
| 1.5 | 30AF | 10A |
| 30AF 10A | 30AF | 10A | 2 | 2 | ||||
| 2.2 | 30AF | 10A |
| 30AF 10A | 30AF | 15A | 2 | 2 | ||||
| 3.7 | 30AF | 20A |
| 30AF 15A | 30AF | 20A | 2 | 2 | ||||
| 5.5 | 30AF | 30A |
| 30AF 20A | 30AF | 30A | 2 | 2 | ||||
| 7.5 | 30AF | 30A |
| 30AF 30A | 30AF | 30A | 3.5 | 3.5 | ||||
| 11 | 50AF | 50A |
| 50AF 40A | 50AF | 50A | 5.5 | 5.5 | ||||
| 15 | 100AF 60A |
| 50AF 50A | 100AF 60A | 8 | 8 | ||||||
| 18.5 | 100AF 75A |
| 100AF 60A | 100AF 75A | 14 | 8 | ||||||
| 22 | 100AF | 100A |
| 100AF 75A | 100AF | 100A | 14 | 14 | ||||
| 30 | 225AF | 125A |
| 225AF | 100A | 225AF | 125A | 22 | 22 | |||
| 37 | 225AF | 150A |
| 225AF | 125A | 225AF | 150A | 22 | 22 | |||
| 45 | 225AF | 175A |
| 225AF | 150A | 225AF | 175A | 38 | 38 | |||
| 55 | 225AF | 200A |
| 225AF | 175A | 225AF | 200A | 60 | 60 | |||
| 75 | — |
| 225AF | 225A | 225AF | 225A | — | 60 | 60 | |||
400V class | 90 | — |
| 225AF | 225A | 400AF | 300A | — | 60 | 60 | |||
| 110 | — |
| 225AF | 225A | 400AF | 350A | — | 80 | 80 | |||
| 132 | — |
| 400AF | 400A | 400AF | 400A | — | 100 | 125 | |||
| 160 | — |
| 400AF | 400A | 600AF | 500A | — | 125 | 125 | |||
| 185 | — |
| 400AF | 400A | 600AF | 500A | — | 150 | 150 | |||
| 220 | — |
| 600AF | 500A | 600AF | 600A | — | 2 × 100 | 2 × 100 | |||
| 250 | — |
| 600AF | 600A | 600AF | 600A | — | 2 × 100 | 2 × 100 | |||
| 280 | — |
| 600AF | 600A | 800AF | 800A | — | 2 × 125 | 2 × 125 | |||
| 315 | — |
| 800AF | 700A | 800AF | 800A | — | 2 × 150 | 2 × 150 | |||
| 355 | — |
| 800AF | 800A | 800AF | 800A | — | 2 × 200 | 2 × 200 | |||
| 400 | — |
| 1000AF 900A | 1000AF | 1000A | — | 2 × 200 | 2 × 200 | ||||
| 450 | — |
| 1000AF | 1000A | 1000AF | 1000A | — | 1000A rated | 2 × 250 | 2 × 250 | ||
|
| product | |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 500 | — |
| 1200AF | 1200A | 1200AF | 1200A | — | 1000A rated | 2 × 250 | 2 × 250 | ||
|
| product | |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 560 | — |
| 1600AF | 1500A | 1600AF | 1600A | — | 1200A rated | 3 × 200 | 3 × 200 | ||
|
| product | |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
*1 Selections for use of the Mitsubishi
*2 Install one MCCB per inverter.
For installations in the United States or Canada, use the fuse certified by the UL and cUL.
(Refer to the Instruction Manual (basics).)
MCCB INV IM
MCCB INV IM
*3 The electrical durability of magnetic contactor is 500,000 times. When the magnetic contactor is used for emergency stop during motor driving, the electrical durability is 25 times.
When using the MC for emergency stop during motor driving or using on the motor side during
*4 Cable
For the 55K or less, the recommended cable size is that of the cable (HIV cable (600V class 2
For the 75K or more, the recommended cable size is that of the cable (LMFC (heat resistant flexible
57