Application to Motor
Application to standard motor
When the Mitsubishi standard
Output characteristics
60Hz torque reference
resonance points to be avoided during operation. (During acceleration/deceleration, the frequency within the setting range is passed through.) An effect is also produced if the PWM carrier frequency in Pr. 72 is changed. When a
Inverter-driven 400V class motor
Continuous output torque (%)
| torque (%) |
100 | maximum |
90 |
|
80 | Short time |
| |
50 |
|
45 |
|
30 |
|
*5 *4 *3 *2
120
110
100
80
70
63
20
10
0 | 1 | 3 | 6 | 20 | 30 |
Short time maximum torque*1
220V
200V
Continuous operation torque (*6 to 8)
60120 Output frequency (Hz)
When driving a 400V class motor by the inverter, surge voltages attributable to the wiring constants may occur at the motor terminals, deteriorating the insulation of the motor. In such a case, consider taking the following measures.
(1) Rectifying the motor insulation |
1. Use a "400V class inverter driven insulation- |
enhanced motor". |
Note: The four poles of the Mitsubishi standard |
50Hz torque reference
torqueoutputContinuous(%) |
| torquemaximumtimeShort(%) | *5 *4 *3 | *2 | Short time maximum torque*1 |
| 104 |
|
| ||
|
|
| 95 |
|
|
| 85 |
|
|
|
|
|
|
| 80 |
|
|
| 75 |
|
|
|
|
| 65 |
| 67 |
|
|
|
|
|
|
| |
|
|
| 53 |
|
|
| 45 |
|
|
| Continuous operation torque |
| 38 |
|
|
| |
|
|
|
| (*6 to 8) | |
|
|
|
|
|
2525
9
0 | 1 | 3 | 6 | 20 | 30 | 50 | 120 | Output |
|
|
|
|
|
|
|
| frequency (Hz) |
*1 The 60Hz torque reference indicates that the rated torque of the motor running at 60Hz is 100%, and the 50Hz torque reference indicates that the rated torque of the motor running at 50Hz is 100%
*2 Torque boost minimum (0%)
*3 Torque boost standard (initial value)
*4 Torque boost large (0.75K... 10%, 1.5K to 3.7K... 7%, 5.5K, 7.5K... 6%, 11K or more... 4%) *5 Enabled for torque boost adjustment (3.7kW or less) or simple magnetic flux vector
control (slip compensation setting)
*6 A
*7 200/220V 60Hz or 200V 50Hz in the chart indicates a motor torque standard (base frequency set in Pr. 3 of the inverter) and is not the frequency of the power supply. You can also set 60Hz in a 50Hz power supply area.
*8 As shown in the chart, the 60Hz torque reference setting allows you to use the motor more efficiently as it can bring out the 100% torque of the motor continuously.
*9 This chart shows the characteristic available when a
Motor loss and temperature rise
The motor operated by the inverter has a limit on the continuous operating torque since it is slightly higher in temperature rise than the one operated by a commercial power supply. At a low speed, reduce the output torque of the motor since the cooling effect decreases. When 100% torque is needed continuously at low speed, consider using a
Torque characteristic
The motor operated by the inverter may be less in motor torque (especially starting torque) than the one driven by the commercial power supply. It is necessary to fully check the load torque characteristic of the machine.
Vibration
The
1.Vibration due to imbalance of the rotator itself including the machine
2.Resonance due to the natural oscillation of the mechanical system. Caution is required especially when the machine used at constant speed is operated at variable speed. The frequency jump function allows
motor |
inverter driving |
2. For the dedicated motor such as the |
motor and |
driven, dedicated motor". |
(2) Suppressing the surge voltage on the inverter side |
Connect a filter on the secondary side of the inverter to |
suppress a surge voltage so that the terminal voltage of the |
motor is 850V or less. When driving by the Mitsubishi |
inverter, connect an optional surge voltage suppression filter |
filter |
output side. |
Application to constant-torque motor
Since a
5.5to 7.5kW...3%, 11 to 37kW...2%,
45 to 55kW...1.5%, 75k or more...1%
When two or more motors are operated synchronously, torque imbalance is likely to occur as motor slip is smaller than that of the standard motor.
Application to special motors
Pole changing motor
As this motor differs in rated current from the standard motor, confirm the maximum current of the motor and select the inverter. Be sure to change the number of poles after the motor has stopped. If the number of poles is changed during rotation, the regenerative overvoltage protecion circuit may be activated to cause an inverter alarm, coasting the motor to a stop.
Geared motor
The continuous operating rotation range of this motor changes depending on the lubrication system and maker. Especially in the case of oil lubrication, continuous operation in the low speed range only can cause gear seizure. For fast operation at higher than 60Hz, please consult the maker.
Synchronous motor
This motor is not suitable for applications of large load variation or impact, where
63