Mitsubishi Electronics FR-F700 instruction manual Jog operation, Starting frequency

Page 28

Pr. 9 Pr.

Motor protection from overheat

51 (electronic thermal relay function)

Pr.9 Electronic thermal O/L relay Pr.51 Second electronic thermal O/L relay

Set the current of the electronic overcurrent protection to protect the motor from overheat.This feature provides the optimum protective characteristics, including reduced motor cooling capability, at low speed.

￿This function detects the overload (overheat) of the motor, stops the operation of the inverter's output transistor, and stops the output.

￿Set the rated current [A] of the motor in Pr.9.

￿When using a motor with an external thermal relay, etc., set “0” in Pr. 9 to make the electronic thermal relay function invalid. (Note that the output transistor protection of the inverter (E.THT) functions.)

￿When using the Mitsubishi constant-torque motor

1)Set “1” in Pr.71 .

(This provides a 100% continuous torque characteristic in the low-speed range.)

2)Set the rated motor current in Pr. 9.

￿When the RT signal is on, thermal protection is provided based on the Pr. 51 setting.

Use this function when rotating two motors of different rated currents individually by a single inverter. (When rotating two motors together, use external thermal relays.)

Pr. 10 to 12 DC injection brake

Pr.10 DC injection brake operation frequency

Pr.11 DC injection brake operation time

Pr.12 DC injection brake operation voltage

 

The DC injection brake can be operated at a motor stop to adjust the stop timing and braking torque.

Pr. 14 V/F pattern matching applications

Pr. 14 Load pattern selection

You can select the optimum output characteristic (V/F characteristic) for the application and load characteristics.

Setting “0”

Setting “1” (initial value)

For constant-torque load

For variable-torque load

100%

100%

Output voltage

Output voltage

Pr.3 Base frequency

Pr.3 Base frequency

Output frequency (Hz)

Output frequency (Hz)

Pr. 15, 16

Jog operation

Pr.15 Jog frequency

Pr.16 Jog acceleration/deceleration time

You can set the frequency and acceleration/decelertion time for jog operation. Jog operation can be performed from either the outside or PU.

Can be used for conveyor positioning, test operation, etc.

Output frequency (Hz) Pr.20

Pr.15

Forward

 

Jog frequency

rotation

Time

setting range

 

 

Reverse

 

 

rotation

Pr.16

JOG signal

ON

Forward

rotation STF

ON

(Hz)

Operation

Outputfrequency

Pr.10

Timefrequency

DC injection

Pr.12

brake

Operation

voltage

voltage

Time

 

 

Pr.11 Operation time

 

 

When

When

Pr.12 Initial

Using the

Using

Mitsubish

the

Value

 

Constant

Energy

 

 

Torque

Saving

 

 

Motor

Motor

3.7K or less

4%

5.5K to 7.5K

4%

2% *

3%

11K or more

2%

75K or more

1%

Reverse

 

 

 

rotation STR

ON

 

 

 

 

 

 

 

 

 

 

 

Logic selection of output stop

Pr. 17 signal (MRS)

 

 

 

Pr.17 MRS input selection

The inverter output can be shut off by the MRS signal. The logic of the MRS signal can also be selected.

Motor coasts

Setting value "0"

(Initial

Setting value "2"

*If the Pr. 71 initial value is changed to the setting for use with a constant-torque motor, the Pr. 12

setting changes to the corresponding value in the above table.

Pr. 13, 571

Starting frequency

Pr.13 Starting frequency

Pr.571 Holding time at a start

MRS signal

STF (STR) signal

to stop

 

value)

 

 

 

 

 

 

 

Output

Inverter

Output

Inverter

 

 

 

 

stop

 

stop

 

 

 

MRS

 

MRS

 

 

SD (PC)

 

SD (PC)

Time

ON

ON

You can set the starting frequency and hold the set starting frequency for a certain period of time.

Set these functions when you need the starting torque or want smooth motor drive at a start.

Output

frequency

(Hz)

 

range

60

 

Setting

Pr.13

0

 

 

 

 

 

Time

Forward

 

Pr.571 setting time

 

rotation

ON

Pr. 18 Refer to the section about Pr.1, Pr.2

Pr. 19 Refer to the section about Pr. 3.

Pr. 20, 21 Refer to the section about Pr.7, Pr.8

29

Pr. indicates simple mode parameters and Pr. indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.

Image 28
Contents FR-F700 Energy savings for buildings and factories as a whole Outline Dimension Drawings Warranty InquiryConnection with Peripheral Devices Inverter FR-F700Why Can the Inverter Save Energy? Damper control discharge sideAmount Inverter controlStandard Specifications RatingType FR-F720-K Type FR-F740-KCommon specifications Can be selectedOperating status Open collectorOutline Dimension Drawings Inverter TypeFR-F720-0.75K 110 FR-F720-1.5K 125 FR-F740-0.75K to 2K are not provided With a cooling fanWiring cover FR-F740-15K, 18.5KFR-F720-30K is Not provided with aInverter Type Mass FR-F740-75K 140 120295 185 FR-HEL-H75K FR-F740-90K 150 130 310 190 FR-HEL-H90KDC reactor supplied FR-F740-110KFR-HEL-H110KMass kg MassRemove the eye nut after installation of the product MassRemove the eye nut after installation of the product FR-F740-400KFR-HEL-H400KFR-F740-450KFR-HEL-H450K Parameter ListPanel cutting dimension drawing Outline drawingPanel FR-DU07 M3 screw CableTerminal Connection Diagram Option connectorMain circuit Control circuitType Terminal Specification ExplanationTerminal Name Description Relay output 1 alarm Preset detected frequency. *1Relay OutputExplanation of the Operation Panel FR-DU07 Setting Operation mode switchoverBasic operation Name Setting Range Increments Initial Value Parameter ListRemarks Function24 to Jump100 101102 103135 139143 144178 179180 181261 262263 264867 872882 883Maximum/minimum Explanations of ParametersFrequency Jog operation Starting frequencySpeed and remote setting Stall prevention operationInput compensation of multi Pr , 23, 48, 49, 66, 148, 149, 154, 156Pr , 70 Selection of regeneration unit SettingSpeed display and speed Pr , 54, 158, 170, 171, 268, 563, 564, 867 Pr Remote setting function Connection diagramPr.59 Setting Description Pr , 58, 162 to 165, 299Retry function at alarm Pr Energy saving control selectionOccurrence Use the constant torque motorCarrier frequency and SoftPWM selection Analog input selectionPr , 240 Pr , 242, 243, 252, 253Pr. Reset selection, disconnected PU 75 detection Pr Output function of alarm codePr. Noise elimination at the analog 74 input Pr Prevention of parameter rewritePr Pr Operation mode selection Pr. Simple magnetic flux vector 80, 90 controlOff LED IndicationAdjustable 5 points V/F Communication initial settingPr to Pr to 124, 331 to 337, 341 to 343Pr Pr Pr , C2902 to C7905 Pr to 134, 575 to 577 PID controlAnalog input bias/gain calibration Analog input display unit changing PrSecond function signal RT Pr. Parameter unit display language 145 selectionSelection of action conditions Pr Pr toPr. Operation selection of the 161 operation panel Terminal assignmentPr to 196 output terminal Function assignmentPr. Selection of motor stopping 250 method and start signal Input/output phase failurePr Increase cooling fan life Pr to 247 Slip compensation261 to 266 power failure Power failure stop mode Pr.261 =Pr Parameter for manufacturer setting. Do not set Operation at instantaneousTo determine Maintenance time of parts Pr to 497 REM signalPr to 557 monitor signal Remote output functionPr. Regeneration avoidance Free parameterPr to 899 Energy saving monitor 882 to 886 functionPr PU contrast adjustment Pr. C0900, C1901 Adjustment of terminal FM AM calibrationParameter clear, parameter copy Pr , CL, ALLC, Er.CL, PcpyError message *2 Minor fault *4 Major failures *5 Protective FunctionsFunction Name Description Indication Regenerative overvoltage shutSupply short circuit RS-485 terminals power Was shorted Options Instructions MotorOption and Peripheral Devices OptionsController/Speed SeriesOthers ManualStand-alone option Specifications, Structure, etcName type Name type Specifications, Structure, etc FR-BR-HK FR-BU-HKConnection example Outline dimension drawings External connection diagramCable Resistor unit Resistance Mass Type ValueHigh power factor Converter Outline dimension Unit mm FR-HC- HKCircuit configuration and connection Application of the sine wave filterApplication condition Capacitor for sine wave filterPeripheral devices list EMC Filter Standard BreakerOn mA Precautions for Operation/Selection Precautions for Peripheral Device Selection Leakage currents NoiseNoise reduction examples Input Target Measures Power Three 7kW Reference materials PhaseInput Target Measures Power Capacity Connect the AC reactor or DC reactorApplication to Motor 60Hz torque reference50Hz torque reference Suppressing the surge voltage on the inverter sideFR-F500 L FR-F700 Warranty FA Center in North America FA Center in TaiwanFA Center in Asean FA Center in Korea