Mitsubishi Electronics FR-F700 instruction manual Terminal Specification Explanation, Type

Page 16

Terminal Specification Explanation

Type

Terminal Symbol

Terminal Name

Description

 

 

 

R/L1, S/L2, T/L3

AC power input

Connect to the commercial power supply.

 

 

 

U, V, W

Inverter output

Connect a three-phase squirrel-cage motor.

 

 

 

R1/L11, S1/L21

Power supply for control

Connected to the AC power supply terminals R/L1 and S/L2. To retain the alarm display and

circuit

circuit

alarm output, apply external power to this terminal.

 

 

 

 

 

 

 

P/+, N/-

Brake unit connection

Connect the brake unit (FR-BU, BU, MT-BU5), power regeneration common converter (FR-

CV), power regeneration converter (MT-RC) or high power factor converter (FR-HC, MT-HC).

 

 

 

 

 

 

Main

 

 

 

 

 

 

P/+, P1

DC reactor connection

For the 55K or less, remove the jumper across terminals P/+ - P1 and connect the DC reactor.

(For the 75K or more, a DC reactor is supplied as standard.)

 

 

 

 

 

 

 

 

 

 

 

 

PR, PX

Please do not remove or use terminals PR and PX or the jumper connected.

 

 

 

 

 

 

 

 

Earth (Ground)

For earthing (grounding) the inverter chassis. Must be earthed (grounded).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STF

Forward rotation start

Turn on the STF signal to start forward rotation and turn it off to

When the STF and STR

 

 

stop.

signals are turned on

 

 

 

 

 

 

 

 

 

 

STR

Reverse rotation start

Turn on the STR signal to start reverse rotation and turn it off to

simultaneously, the stop

 

 

stop.

command is given.

 

 

 

 

 

 

 

 

 

 

STOP

Start self-holding

Turn on the STOP signal to self-hold the start signal.

 

 

 

selection

 

 

 

 

 

 

 

 

 

 

 

 

RH, RM, RL

Multi-speed selection

Multi-speed can be selected according to the combination of RH, RM and RL signals.

 

 

JOG

Jog mode selection

Turn on the JOG signal to select Jog operation (initial setting) and turn on the start signal (STF

 

 

or STR) to start Jog operation.

 

 

 

 

 

 

 

 

 

 

 

 

RT

Second acceleration/

Turn on the RT signal to select second acceleration/deceleration time.

 

 

deceleration time

When the second function such as "second torque boost" and "second V/F (base frequency)"

 

 

 

 

 

 

 

selection

are set, turning on the RT signal selects these functions.

 

 

 

MRS

Output stop

Turn on the MRS signal (20ms or more) to stop the inverter output.

 

 

 

Use to shut off the inverter output when stopping the motor by electromagnetic brake.

 

input

 

 

 

 

 

 

 

 

 

 

 

 

 

Used to reset alarm output provided when protective function is activated. Turn on the RES

 

RES

Reset

signal for more than 0.1s, then turn it off.

 

 

Contact

 

 

 

 

 

 

Recover about 1s after reset is cancelled.

 

 

 

 

 

 

 

Terminal 4 input selection

Terminal 4 is made valid only when the AU signal is turned on. (The frequency setting signal

 

 

 

 

 

 

can be set between 4 and 20mADC.)

 

 

 

AU

 

Turning the AU signal on makes terminal 2 (voltage input) invalid.

 

 

 

 

 

 

 

 

PTC input

AU terminal is used as PTC input terminal (thermal protection of the motor). When using it as

 

 

 

 

 

 

 

PTC input terminal, set the AU/PTC switch to PTC.

 

signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Selection of automatic

When the CS signal is left on, the inverter restarts automatically at power restoration. Note that

 

CS

restart after

input

 

instantaneous power

restart setting is necessary for this operation. In the initial setting, a restart is disabled.

 

 

 

 

 

 

 

 

 

 

 

 

failure

 

 

circuit

 

SD

Contact input common

Common terminal for contact input terminal (sink logic) and terminal FM. Common output

 

(sink)

terminal for 24VDC 0.1A power supply (PC terminal). Isolated from terminals 5 and SE.

 

 

 

 

 

 

Control

 

 

 

 

 

 

External transistor

When connecting the transistor output (open collector output), such as a programmable

 

 

 

 

 

 

common,

controller (PLC), when sink logic is selected, connect the external power supply common for

 

PC

24VDC power supply,

transistor output to this terminal to prevent a malfunction caused by undesirable currents. Can

 

 

 

 

 

 

 

contact input common

be used as 24VDC 0.1A power supply. When source logic has been selected, this terminal

 

 

 

 

 

 

 

(source)

serves as a contact input common.

 

 

 

10E

 

When connecting the frequency setting potentiometer at an initial

10VDC, permissible load

 

 

Frequency setting power

current 10mA.

 

 

 

 

 

 

 

status, connect it to terminal 10.

 

 

 

 

 

 

 

supply

5VDC, Permissible load

 

 

10

 

Change the input specifications when connecting it to terminal 10E.

 

 

 

 

 

 

 

 

 

current 10mA.

 

 

 

 

 

 

 

 

Inputting 0 to 5VDC (or 0 to 10V, 4 to 20mA) provides the maximum

output frequency at 5V

 

 

2

 

 

Frequency setting

(10V, 20mA) and makes input and output proportional. Use Pr.73 to switch from among input 0

 

 

 

 

to 5VDC (initial setting), 0 to 10VDC, and 4 to 20mA.

 

 

setting

 

 

(voltage)

 

 

 

 

 

 

 

Voltage input: Input resistance 10kΩ ± 1kΩ Maximum permissible voltage 20VDC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current input: Input resistance 250Ω ± 2% Maximum permissible current 30mA

 

Frequency

 

 

 

 

 

 

Inputting 4 to 20mADC (or 0 to 5V, 0 to 10V) provides the maximum output frequency at 20mA

 

 

 

 

 

 

 

(5V, 10V) makes input and output proportional. This input signal is valid only when the AU

 

4

 

 

Frequency setting

signal is on (terminal 2 input is invalid). Use Pr.267 to switch between the input 4 to 20mA and 0

 

 

 

(current)

to 5VDC, 0 to 10VDC (initial setting).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage input: Input resistance 10kΩ ± 1kΩ Maximum permissible voltage 20VDC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current input: Input resistance 250Ω ± 2% Maximum permissible current 30mA

 

 

 

 

 

 

 

Frequency setting

Inputting 0 to ±5 VDC or 0 to ±10VDC adds this signal to terminal 2 or 4 frequency setting

 

 

1

 

 

signal. Use Pr.73 to switch between the input 0 to ±5VDC and 0 to ±10VDC (initial setting).

 

 

 

 

auxiliary

 

 

 

 

 

 

 

Input resistance 10kΩ ± 1kΩ, Maximum permissible voltage ± 20VDC

 

 

 

 

 

 

 

 

 

 

5

 

 

Frequency setting

Common terminal for frequency setting signal (terminal 2, 1 or 4) and analog output terminal

 

 

 

 

common

AM. Do not earth (ground).

 

 

 

 

 

 

 

 

 

17

Image 16
Contents FR-F700 Energy savings for buildings and factories as a whole Outline Dimension Drawings Warranty InquiryConnection with Peripheral Devices Inverter FR-F700Why Can the Inverter Save Energy? Damper control discharge sideAmount Inverter controlStandard Specifications RatingType FR-F720-K Type FR-F740-KCommon specifications Can be selectedOperating status Open collectorOutline Dimension Drawings Inverter TypeFR-F720-0.75K 110 FR-F720-1.5K 125 FR-F740-0.75K to 2K are not provided With a cooling fanWiring cover FR-F740-15K, 18.5KFR-F720-30K is Not provided with aInverter Type Mass FR-F740-75K 140 120295 185 FR-HEL-H75K FR-F740-90K 150 130 310 190 FR-HEL-H90KDC reactor supplied FR-F740-110KFR-HEL-H110KMass kg MassRemove the eye nut after installation of the product MassRemove the eye nut after installation of the product FR-F740-400KFR-HEL-H400KFR-F740-450KFR-HEL-H450K Parameter ListPanel cutting dimension drawing Outline drawingPanel FR-DU07 M3 screw CableTerminal Connection Diagram Option connectorMain circuit Control circuitType Terminal Specification ExplanationTerminal Name Description Relay output 1 alarm Preset detected frequency. *1Relay OutputExplanation of the Operation Panel FR-DU07 Setting Operation mode switchoverBasic operation Name Setting Range Increments Initial Value Parameter ListRemarks Function24 to Jump100 101102 103135 139143 144178 179180 181261 262263 264867 872882 883Maximum/minimum Explanations of ParametersFrequency Jog operation Starting frequencySpeed and remote setting Stall prevention operationInput compensation of multi Pr , 23, 48, 49, 66, 148, 149, 154, 156Pr , 70 Selection of regeneration unit SettingSpeed display and speed Pr , 54, 158, 170, 171, 268, 563, 564, 867 Pr Remote setting function Connection diagramPr.59 Setting Description Pr , 58, 162 to 165, 299Retry function at alarm Pr Energy saving control selectionOccurrence Use the constant torque motorCarrier frequency and SoftPWM selection Analog input selectionPr , 240 Pr , 242, 243, 252, 253Pr. Reset selection, disconnected PU 75 detection Pr Output function of alarm codePr. Noise elimination at the analog 74 input Pr Prevention of parameter rewritePr Pr Operation mode selection Pr. Simple magnetic flux vector 80, 90 controlOff LED IndicationAdjustable 5 points V/F Communication initial settingPr to Pr to 124, 331 to 337, 341 to 343Pr Pr Pr , C2902 to C7905 Pr to 134, 575 to 577 PID controlAnalog input bias/gain calibration Analog input display unit changing PrSecond function signal RT Pr. Parameter unit display language 145 selectionSelection of action conditions Pr Pr toPr. Operation selection of the 161 operation panel Terminal assignmentPr to 196 output terminal Function assignmentPr. Selection of motor stopping 250 method and start signal Input/output phase failurePr Increase cooling fan life Pr to 247 Slip compensation261 to 266 power failure Power failure stop mode Pr.261 =Pr Parameter for manufacturer setting. Do not set Operation at instantaneousTo determine Maintenance time of parts Pr to 497 REM signalPr to 557 monitor signal Remote output functionPr. Regeneration avoidance Free parameterPr to 899 Energy saving monitor 882 to 886 functionPr PU contrast adjustment Pr. C0900, C1901 Adjustment of terminal FM AM calibrationParameter clear, parameter copy Pr , CL, ALLC, Er.CL, PcpyError message *2 Minor fault *4 Major failures *5 Protective FunctionsFunction Name Description Indication Regenerative overvoltage shutSupply short circuit RS-485 terminals power Was shorted Options Instructions MotorOption and Peripheral Devices OptionsController/Speed SeriesOthers ManualStand-alone option Specifications, Structure, etcName type Name type Specifications, Structure, etc FR-BR-HK FR-BU-HKConnection example Outline dimension drawings External connection diagramCable Resistor unit Resistance Mass Type ValueHigh power factor Converter Outline dimension Unit mm FR-HC- HKCircuit configuration and connection Application of the sine wave filterApplication condition Capacitor for sine wave filterPeripheral devices list EMC Filter Standard BreakerOn mA Precautions for Operation/Selection Precautions for Peripheral Device Selection Leakage currents NoiseNoise reduction examples Input Target Measures Power Three 7kW Reference materials PhaseInput Target Measures Power Capacity Connect the AC reactor or DC reactorApplication to Motor 60Hz torque reference50Hz torque reference Suppressing the surge voltage on the inverter sideFR-F500 L FR-F700 Warranty FA Center in North America FA Center in TaiwanFA Center in Asean FA Center in Korea