Mitsubishi Electronics FR-F700 Pr Remote setting function, Pr , 58, 162 to 165, 299, Description

Page 32

Pr. 57, 58, 162 to 165, 299, 611

Restart operation after instantaneous power failure / Flying start

Pr.57 Restart coasting time

Pr.58 Restart cushion time

Pr.162 Automatic restart after instantaneous power failure selection

Pr.163 First cushion time for restart

 

Pr.164 First cushion voltage for restart

Pr.165 Stall prevention operation level for restart

Pr.299 Rotation direction detection selection at restarting

Pr.611 Acceleration time at a restart

You can restart the inverter without stopping the motor in the following cases.

when commercial power supply operation is switched to inverter operation

when power comes back on after an instantaneous power failure

when motor is coasting at start

Pr.

Setting Range

Description

Number

 

 

 

 

1.5K or less..........0.5s,

 

0

2.2K to 7.5K.........1s,

 

11K or more ........3.0s

57

 

75K or more ........5.0s

 

The above times are coasting time.

 

 

 

0.1 to 5s/

Set the waiting time for inverter-triggered

 

restart after an instantaneous power

 

0.1 to 30s *

 

failure.

 

 

 

9999 (initial value)

No restart

58

0 to 60s

Set a voltage starting time at restart.

 

0 (initial value)

With frequency search

 

1

Without frequency search (reduced

162

voltage system)

 

 

10

Frequency search at every start

 

11

Reduced voltage system at every start

163

0 to 20s

Set a voltage starting time at restart.

 

 

Consider using these parameters

164

0 to 100%

according to the load (inertia moment,

 

 

torque) magnitude.

165

0 to 150%

Consider the rated inverter current as

100% and set the stall prevention

 

 

operation level during restart operation.

 

0

Without rotation direction detection

 

1

With rotation direction detection

299

 

When Pr. 78 =0, the rotation direction is

9999

detected.

 

 

When Pr. 78 =1,2, the rotation direction is

 

 

 

 

not detected.

 

0 to 3600s

Set the acceleration time to reach the set

611

frequency at restart.

 

9999

Acceleration time for restart is the normal

 

 

acceleration time (e.g. Pr. 7).

 

 

*The setting range varies according to the inverter capacity. (55K or less/ 75K or more)

<Connection diagram>

 

 

 

MC2

MCCB

MC1

 

MC3

 

R/L1

U

 

 

 

S/L2

V

IM

 

T/L3

W

 

 

R1/L11

 

 

 

S1/L21

 

 

STF

 

CS

MC

SD

switchover

 

sequence

For use for only

CS automatic restart

SD after instantaneous power failure or flying start, short CS-SD in advance.

￿When “0 (initial value) or 10” is set in Pr. 162, the inverter smoothly starts after detecting the motor speed upon power restoration.

￿Even when the motor is rotating in the opposite direction, the inverter can be restarted smoothly as the direction of rotation is detected. (You can select whether to make rotation direction detection or not with Pr. 299 Rotation direction detection selection at restarting. )

When Pr. 162 = 0, 10 (with frequency search)

Instantaneous (power failure) time

Power supply (R/L1,S/L2,T/L3)

Motor

speed N (r/min) Inverter

output frequency

 

*

 

 

 

 

f (Hz)

 

 

 

Inverter

 

 

 

output voltage

 

 

 

E (V)

 

 

Restart cushion

 

 

 

Coasting

+

Speed

time (Pr. 58 setting)

time (Pr.57)

detection time

 

Acceleration time at a restart

(Pr. 611 setting)

*The output shut off timing differs according to the load condition.

￿When Pr. 162 = "1" or "11", automatic restart operation is performed in a reduced voltage system, where the voltage is gradually risen with the output frequency unchanged from prior to an instantaneous power failure independently of the coasting speed of the motor.

When Pr. 162 = 1, 11 (without frequency search)

Instantaneous (power failure) time

Power supply (R/L1,S/L2,T/L3)

Motor speed N

 

 

 

 

 

(r/min)

 

 

 

 

 

 

 

 

 

 

 

 

Inverter

 

*

 

 

 

output frequency

 

 

 

 

 

 

 

 

 

f (Hz)

 

 

 

 

 

 

Inverter

 

 

 

 

 

 

 

 

 

 

output voltage

 

 

 

 

 

 

E (V)

 

 

 

 

 

Coasting time

 

 

 

 

 

Pr. 57 setting

Restart cushion

 

 

time

Pr. 58 setting

*The output shut off timing differs according to the load condition.

Pr. 59 Remote setting function

Pr.59 Remote function selection

￿Even if the operation panel is located away from the enclosure, you can use contact signals to perform continuous variable-speed operation, without using analog signals.

￿By merely setting this parameter, you can use the acceleration, deceleration and setting clear functions of the motorized speed setter (FR-FK).

Pr.59 Setting

Description

RH, RM, RL signal

Frequency setting

 

function

storage function

0 (initial value)

Multi-speed setting

1

Remote setting

Yes

2

Remote setting

No

 

 

No

3

Remote setting

(Turning STF/STR off

clears remotely-set

 

 

 

 

frequency.)

frequency

 

When Pr. 59 = 1, 2

When Pr. 59 = 1

 

When Pr. 59 = 3

 

 

 

When Pr. 59 = 2, 3

*

 

 

 

Output (Hz)

 

 

 

 

 

0Hz

 

 

Time

Acceleration

ON

 

ON

 

(RH)

ON

 

 

 

Deceleration

ON

 

 

 

(RM)

 

 

 

 

ON

 

 

Clear (RL)

 

 

 

 

 

 

 

Forward

ON

ON

ON

ON

rotation (STF)

 

 

 

 

Power supply

ON

 

 

ON

*External runnning frequency (other than multi-speed operation) or PU running frequency

33

Pr. indicates simple mode parameters and Pr. indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.

Image 32
Contents FR-F700 Energy savings for buildings and factories as a whole Outline Dimension Drawings Warranty InquiryConnection with Peripheral Devices Inverter FR-F700Why Can the Inverter Save Energy? Damper control discharge sideAmount Inverter controlStandard Specifications RatingType FR-F720-K Type FR-F740-KCommon specifications Can be selectedOperating status Open collectorOutline Dimension Drawings Inverter TypeFR-F720-0.75K 110 FR-F720-1.5K 125 FR-F740-0.75K to 2K are not provided With a cooling fanWiring cover FR-F740-15K, 18.5KFR-F720-30K is Not provided with aInverter Type Mass FR-F740-75K 140 120295 185 FR-HEL-H75K FR-F740-90K 150 130 310 190 FR-HEL-H90KDC reactor supplied FR-F740-110KFR-HEL-H110KMass kg MassRemove the eye nut after installation of the product MassRemove the eye nut after installation of the product FR-F740-400KFR-HEL-H400KFR-F740-450KFR-HEL-H450K Parameter ListPanel cutting dimension drawing Outline drawingPanel FR-DU07 M3 screw CableTerminal Connection Diagram Option connectorMain circuit Control circuitTerminal Name Description Terminal Specification ExplanationType Relay output 1 alarm Preset detected frequency. *1Relay OutputExplanation of the Operation Panel FR-DU07 Basic operation Operation mode switchoverSetting Name Setting Range Increments Initial Value Parameter ListRemarks Function24 to Jump100 101102 103135 139143 144178 179180 181261 262263 264867 872882 883Frequency Explanations of ParametersMaximum/minimum Jog operation Starting frequencySpeed and remote setting Stall prevention operationInput compensation of multi Pr , 23, 48, 49, 66, 148, 149, 154, 156Speed display and speed SettingPr , 70 Selection of regeneration unit Pr , 54, 158, 170, 171, 268, 563, 564, 867 Pr Remote setting function Connection diagramPr.59 Setting Description Pr , 58, 162 to 165, 299Retry function at alarm Pr Energy saving control selectionOccurrence Use the constant torque motorCarrier frequency and SoftPWM selection Analog input selectionPr , 240 Pr , 242, 243, 252, 253Pr. Reset selection, disconnected PU 75 detection Pr Output function of alarm codePr. Noise elimination at the analog 74 input Pr Prevention of parameter rewritePr Pr Operation mode selection Pr. Simple magnetic flux vector 80, 90 controlOff LED IndicationAdjustable 5 points V/F Communication initial settingPr to Pr to 124, 331 to 337, 341 to 343Pr Pr Pr , C2902 to C7905 Pr to 134, 575 to 577 PID controlAnalog input bias/gain calibration Analog input display unit changing PrSecond function signal RT Pr. Parameter unit display language 145 selectionSelection of action conditions Pr Pr toPr. Operation selection of the 161 operation panel Terminal assignmentPr to 196 output terminal Function assignmentPr. Selection of motor stopping 250 method and start signal Input/output phase failurePr Increase cooling fan life Pr to 247 Slip compensation261 to 266 power failure Power failure stop mode Pr.261 =Pr Parameter for manufacturer setting. Do not set Operation at instantaneousTo determine Maintenance time of parts Pr to 497 REM signalPr to 557 monitor signal Remote output functionPr. Regeneration avoidance Free parameterPr to 899 Energy saving monitor 882 to 886 functionPr PU contrast adjustment Pr. C0900, C1901 Adjustment of terminal FM AM calibrationParameter clear, parameter copy Pr , CL, ALLC, Er.CL, PcpyError message *2 Minor fault *4 Major failures *5 Protective FunctionsFunction Name Description Indication Regenerative overvoltage shutSupply short circuit RS-485 terminals power Was shorted Options Instructions MotorOption and Peripheral Devices OptionsController/Speed SeriesOthers ManualName type Specifications, Structure, etcStand-alone option Name type Specifications, Structure, etc Connection example FR-BU-HKFR-BR-HK Outline dimension drawings External connection diagramCable Resistor unit Resistance Mass Type ValueHigh power factor Converter Outline dimension Unit mm FR-HC- HKCircuit configuration and connection Application of the sine wave filterApplication condition Capacitor for sine wave filterPeripheral devices list On mA Standard BreakerEMC Filter Precautions for Operation/Selection Precautions for Peripheral Device Selection Noise reduction examples NoiseLeakage currents Input Target Measures Power Three 7kW Reference materials PhaseInput Target Measures Power Capacity Connect the AC reactor or DC reactorApplication to Motor 60Hz torque reference50Hz torque reference Suppressing the surge voltage on the inverter sideFR-F500 L FR-F700 Warranty FA Center in North America FA Center in TaiwanFA Center in Asean FA Center in Korea