Function

Parameters

Name

 

Setting Range

Increments

Initial Value

Refer to

 

page

 

 

 

 

 

 

 

 

66

Stall prevention operation reduction

0 to 400Hz

0.01Hz

60Hz

30

starting frequency

 

 

 

 

 

 

 

Retry

67

Number of retries at alarm occurrence

0 to 10, 101 to 110

1

0

34

68

Retry waiting time

0 to 10s

0.1s

1s

34

 

 

69

Retry count display erase

0

 

1

0

34

70

Special regenerative brake duty *2

0 to 10%

0.1%

0%

31

71

Applied motor

0, 1, 2, 20

1

0

34

72

PWM frequency selection

0 to 15/0 to 6, 25*1

1

2

35

73

Analog input selection

0 to 7, 10 to 17

1

1

35

74

Input filter time constant

0 to

8

1

1

36

 

75

Reset selection/disconnected PU

0 to 3, 14 to 17

1

14

36

detection/PU stop selection

 

 

 

 

 

 

 

76

Alarm code output selection

0, 1,

2

1

0

36

77

Parameter write selection

0, 1,

2

1

0

36

78

Reverse rotation prevention selection

0, 1,

2

1

0

36

￿ 79

Operation mode selection

0, 1, 2, 3, 4, 6, 7

1

0

37

Simple fluxmagnetic controlvector

80

Motor capacity (simple magnetic flux

0.4 to 55kW, 9999

0.01/0.1kW*1

9999

37

vector control)

/0 to 3600kW, 9999*1

 

 

 

 

 

 

 

90

Motor constant (R1)

0 to 50Ω, 9999

0.001Ω/

9999

37

 

/0 to 400mΩ, 9999*1

0.01mΩ*1

 

 

 

 

 

 

 

 

 

 

 

 

 

100

V/F1 (first frequency)

0 to 400Hz, 9999

0.01Hz

9999

38

V/F

101

V/F1 (first frequency voltage)

0 to 1000V

0.1V

0V

38

102

V/F2 (second frequency)

0 to 400Hz, 9999

0.01Hz

9999

38

points

103

V/F2 (second frequency voltage)

0 to 1000V

0.1V

0V

38

 

5

104

V/F3 (third frequency)

0 to 400Hz, 9999

0.01Hz

9999

38

Adjustable

105

V/F3 (third frequency voltage)

0 to 1000V

0.1V

0V

38

106

V/F4 (fourth frequency)

0 to 400Hz, 9999

0.01Hz

9999

38

 

 

107

V/F4 (fourth frequency voltage)

0 to 1000V

0.1V

0V

38

 

108

V/F5 (fifth frequency)

0 to 400Hz, 9999

0.01Hz

9999

38

 

109

V/F5 (fifth frequency voltage)

0 to 1000V

0.1V

0V

38

 

117

PU communication station

0 to 31

1

0

38

connectorPU communication

118

PU communication speed

48, 96, 192, 384

1

192

38

123

PU communication waiting time setting

0 to 150ms, 9999

1

9999

38

 

119

PU communication stop bit length.

0, 1, 10, 11

1

1

38

 

120

PU communication parity check

0, 1, 2

1

2

38

 

121

Number of PU communication retries

0 to 10, 9999

1

1

38

 

122

PU communication check time interval

0, 0.1 to 999.8s, 9999

0.1s

9999

38

 

 

 

 

 

 

 

 

 

124

PU communication CR/LF presence/

0, 1, 2

1

1

38

 

absence selection

 

 

 

 

 

 

 

 

￿ 125

Terminal 2 frequency setting gain

0 to 400Hz

0.01Hz

60Hz

39

frequency

 

 

 

 

 

 

 

 

￿ 126

Terminal 4 frequency setting gain

0 to 400Hz

0.01Hz

60Hz

39

frequency

 

 

 

 

 

 

 

 

127

PID control automatic switchover

0 to 400Hz, 9999

0.01Hz

9999

39

 

freqeuncy

 

 

 

 

 

 

 

operation

128

PID action selection

10, 11, 20, 21, 50, 51, 60,

1

10

39

61

 

 

 

 

 

 

 

129

PID proportional band

0.1 to 1000%, 9999

0.1%

100%

39

 

 

130

PID integral time

0.1 to 3600s, 9999

0.1s

1s

39

PID

131

PID upper limit

0 to 100%, 9999

0.1%

9999

39

132

PID lower limit

0 to 100%, , 9999

0.1%

9999

39

 

 

133

PID action set point

0 to 100%, 9999

0.01%

9999

39

 

134

PID differential time

0.01 to 10.00s, 9999

0.01s

9999

39

*1 Differ according to capacities. (55K or less/75K or more) *2 Setting can be made for the 75K or more.

23

Image 22
Contents FR-F700 Energy savings for buildings and factories as a whole Outline Dimension Drawings Warranty InquiryConnection with Peripheral Devices Inverter FR-F700Amount Why Can the Inverter Save Energy?Damper control discharge side Inverter controlType FR-F720-K Standard SpecificationsRating Type FR-F740-KOperating status Common specificationsCan be selected Open collectorFR-F720-0.75K 110 FR-F720-1.5K 125 Outline Dimension DrawingsInverter Type FR-F740-0.75K to 2K are not provided With a cooling fanFR-F720-30K is Wiring coverFR-F740-15K, 18.5K Not provided with a295 185 FR-HEL-H75K FR-F740-90K 150 130 Inverter Type MassFR-F740-75K 140 120 310 190 FR-HEL-H90KMass kg DC reactor suppliedFR-F740-110KFR-HEL-H110K MassRemove the eye nut after installation of the product MassFR-F740-450KFR-HEL-H450K Remove the eye nut after installation of the productFR-F740-400KFR-HEL-H400K Parameter ListPanel FR-DU07 Panel cutting dimension drawingOutline drawing M3 screw CableMain circuit Terminal Connection DiagramOption connector Control circuitType Terminal Specification ExplanationTerminal Name Description Relay Relay output 1 alarmPreset detected frequency. *1 OutputExplanation of the Operation Panel FR-DU07 Setting Operation mode switchoverBasic operation Remarks Name Setting Range Increments Initial ValueParameter List Function24 to Jump102 100101 103143 135139 144180 178179 181263 261262 264882 867872 883Maximum/minimum Explanations of ParametersFrequency Jog operation Starting frequencyInput compensation of multi Speed and remote settingStall prevention operation Pr , 23, 48, 49, 66, 148, 149, 154, 156Pr , 70 Selection of regeneration unit SettingSpeed display and speed Pr , 54, 158, 170, 171, 268, 563, 564, 867 Pr.59 Setting Description Pr Remote setting functionConnection diagram Pr , 58, 162 to 165, 299Occurrence Retry function at alarmPr Energy saving control selection Use the constant torque motorPr , 240 Carrier frequency and SoftPWM selectionAnalog input selection Pr , 242, 243, 252, 253Pr. Noise elimination at the analog 74 input Pr. Reset selection, disconnected PU 75 detectionPr Output function of alarm code Pr Prevention of parameter rewriteOff Pr Pr Operation mode selectionPr. Simple magnetic flux vector 80, 90 control LED IndicationPr to Adjustable 5 points V/FCommunication initial setting Pr to 124, 331 to 337, 341 to 343Analog input bias/gain calibration Pr Pr Pr , C2902 to C7905Pr to 134, 575 to 577 PID control Analog input display unit changing PrSelection of action conditions Second function signal RTPr. Parameter unit display language 145 selection Pr Pr toPr to 196 output terminal Pr. Operation selection of the 161 operation panelTerminal assignment Function assignmentPr Increase cooling fan life Pr. Selection of motor stopping 250 method and start signalInput/output phase failure Pr to 247 Slip compensationPr Parameter for manufacturer setting. Do not set 261 to 266 power failurePower failure stop mode Pr.261 = Operation at instantaneousPr to 557 monitor signal To determine Maintenance time of partsPr to 497 REM signal Remote output functionPr to 899 Energy saving monitor Pr. Regeneration avoidanceFree parameter 882 to 886 functionParameter clear, parameter copy Pr PU contrast adjustmentPr. C0900, C1901 Adjustment of terminal FM AM calibration Pr , CL, ALLC, Er.CL, PcpyFunction Name Description Indication Error message *2 Minor fault *4 Major failures *5Protective Functions Regenerative overvoltage shutSupply short circuit RS-485 terminals power Was shorted Options Instructions MotorOption and Peripheral Devices OptionsOthers Controller/SpeedSeries ManualStand-alone option Specifications, Structure, etcName type Name type Specifications, Structure, etc FR-BR-HK FR-BU-HKConnection example Cable Outline dimension drawingsExternal connection diagram Resistor unit Resistance Mass Type ValueHigh power factor Converter Outline dimension Unit mm FR-HC- HKApplication condition Circuit configuration and connectionApplication of the sine wave filter Capacitor for sine wave filterPeripheral devices list EMC Filter Standard BreakerOn mA Precautions for Operation/Selection Precautions for Peripheral Device Selection Leakage currents NoiseNoise reduction examples Input Target Measures Power Capacity Input Target Measures PowerThree 7kW Reference materials Phase Connect the AC reactor or DC reactor50Hz torque reference Application to Motor60Hz torque reference Suppressing the surge voltage on the inverter sideFR-F500 L FR-F700 Warranty FA Center in Asean FA Center in North AmericaFA Center in Taiwan FA Center in Korea