Mitsubishi Electronics FR-F700 Operation at instantaneous, 261 to 266 power failure

Page 42

Pr.

Operation at instantaneous

261 to 266 power failure

Pr.261 Power failure stop selection

Pr.262 Subtracted frequency at deceleration start

Pr.263 Subtraction starting frequency Pr.264 Power-failure deceleration time 1 Pr.265 Power-failure deceleration time 2

Pr.266 Power failure deceleration time switchover frequency

When a power failure or undervoltage occurs, the inverter can be decelerated to a stop or can be decelerated and re- accelerated to the set frequency.

Pr.

Setting Range

 

Description

Number

 

 

 

 

 

 

 

Coasting to stop

 

0 (initial value)

 

When undervoltage or power failure

 

 

 

occurs, the inverter output is shut off.

 

1

 

When undervoltage or a power failure

261

 

occurs, the inverter can be decelerated

 

 

to a stop.

 

 

 

When undervoltage or a power failure

 

 

 

occurs, the inverter can be decelerated

 

2

 

to a stop.

 

 

 

If power is restored during a power

 

 

 

failure, the inverter accelerates again.

 

 

 

Normally operation can be performed

 

 

 

with the initial value unchanged. But

262

0 to 20Hz

 

adjust the frequency according to the

 

 

 

magnitude of the load specifications

 

 

 

(moment of inertia, torque).

 

 

 

When output frequency ≥ Pr. 263

 

 

 

Decelerate from the speed obtained

 

0 to 120Hz

 

from output frequency minus Pr. 262.

263

 

 

When output frequency < Pr. 263

 

 

 

Decelerate from output frequency

 

9999

 

Decelerate from the speed obtained

 

 

from output frequency minus Pr. 262.

 

 

 

264

0 to 3600/ 360s

*

Set a deceleration slope down to the

frequency set in Pr. 266.

 

 

 

 

0 to 3600/ 360s

*

Set a deceleration slope below the

265

frequency set in Pr. 266.

 

 

 

9999

 

Same slope as in Pr. 264

266

0 to 400Hz

 

Set the frequency at which the

 

deceleration slope is switched from the

 

 

 

Pr. 264 setting to the Pr. 265 setting.

*When the setting of Pr. 21 Acceleration/deceleration time increments is "0" (initial value), the setting range is "0 to 3600s" and the setting increments are "0.1s", and when the setting is "1", the setting range is "0 to 360s" and the setting increments are "0.01s"

Power supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

 

 

 

 

 

Pr.264

Subtracted

 

 

 

Power-failure

frequency

frequency at

 

 

 

 

deceleration time 1

Power-failure

 

 

 

 

deceleration start

 

 

 

 

 

 

Pr.265

deceleration

Pr.262

 

 

 

 

 

 

Power-failure

time switchover

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

deceleration

frequency

 

 

 

 

 

 

 

 

 

 

 

time 2

 

Pr.266

 

 

 

 

 

Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1)Power failure stop mode (Pr.261 = “1”)

If power is restored during power failure deceleration, deceleration to a stop is continued and the inverter remains stopped.To restart, turn off the start signal once, then turn it on again.

Power

supply

Pr.261 = 1

 

 

frequency

During deceleration at

 

occurrence of power failure

 

During stop at

 

occurrence of

 

power failure

 

Output

 

 

 

 

Time

STF

 

Y46

 

Turn off STF once to make acceleration again

(2)Instantaneous power failure-time operation continuation function (Pr.261 = “2”)

When power is restored during deceleration after an instantaneous power failure, acceleration is made again up to the set frequency.

When this function is used in combination with the automatic restart after instantaneous power failure operation, deceleration can be made at a power failure and acceleration can be made again after power restoration.

When power is restored after a stop by deceleration at an instantaneous power failure, automatic restart operation is performed if automatic restart after instantaneous power failure has been selected (Pr. 57 ≠ "9999")

Pr.261 = 2

When power is restored during

deceleration

 

Power

 

IPF

 

 

supply

 

 

Output

 

 

frequency

During deceleration

 

 

at occurrence of

Reacceleration

 

power failure

 

Time

 

 

Y46

 

 

Pr.261 = 2, Pr.57 9999

When used with automatic restart

after instantaneous power failure

 

During power failure

Power

 

supply

 

Output

 

frequency

Automatic restart

During deceleration

 

at occurrence of

after instantaneous

power failure

power failure

 

Time

Reset time + Pr.57

Y46

Pr. 267 Refer to the section about Pr. 73 and other relevant parameters.

Pr. 268 Refer to the section about Pr. 52 and other relevant parameters.

Pr. 269 Parameter for manufacturer setting. Do not set.

Pr.

299

 

Refer to the section about Pr. 57 and other

 

 

relevant parameters.

 

 

 

Pr.

331 to 337

Refer to the section about Pr. 117 and

other relevant parameters.

 

 

 

 

43

Pr. indicates simple mode parameters and Pr. indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.

Image 42
Contents FR-F700 Energy savings for buildings and factories as a whole Outline Dimension Drawings Warranty InquiryConnection with Peripheral Devices Inverter FR-F700Amount Why Can the Inverter Save Energy?Damper control discharge side Inverter controlType FR-F720-K Standard SpecificationsRating Type FR-F740-KOperating status Common specificationsCan be selected Open collectorFR-F720-0.75K 110 FR-F720-1.5K 125 Outline Dimension DrawingsInverter Type FR-F740-0.75K to 2K are not provided With a cooling fanFR-F720-30K is Wiring coverFR-F740-15K, 18.5K Not provided with a295 185 FR-HEL-H75K FR-F740-90K 150 130 Inverter Type MassFR-F740-75K 140 120 310 190 FR-HEL-H90KMass kg DC reactor suppliedFR-F740-110KFR-HEL-H110K MassRemove the eye nut after installation of the product MassFR-F740-450KFR-HEL-H450K Remove the eye nut after installation of the productFR-F740-400KFR-HEL-H400K Parameter ListPanel FR-DU07 Panel cutting dimension drawingOutline drawing M3 screw CableMain circuit Terminal Connection DiagramOption connector Control circuitTerminal Specification Explanation TypeTerminal Name Description Relay Relay output 1 alarmPreset detected frequency. *1 OutputExplanation of the Operation Panel FR-DU07 Operation mode switchover SettingBasic operation Remarks Name Setting Range Increments Initial ValueParameter List Function24 to Jump102 100101 103143 135139 144180 178179 181263 261262 264882 867872 883Explanations of Parameters Maximum/minimumFrequency Jog operation Starting frequencyInput compensation of multi Speed and remote settingStall prevention operation Pr , 23, 48, 49, 66, 148, 149, 154, 156Setting Pr , 70 Selection of regeneration unitSpeed display and speed Pr , 54, 158, 170, 171, 268, 563, 564, 867 Pr.59 Setting Description Pr Remote setting functionConnection diagram Pr , 58, 162 to 165, 299Occurrence Retry function at alarmPr Energy saving control selection Use the constant torque motorPr , 240 Carrier frequency and SoftPWM selectionAnalog input selection Pr , 242, 243, 252, 253Pr. Noise elimination at the analog 74 input Pr. Reset selection, disconnected PU 75 detectionPr Output function of alarm code Pr Prevention of parameter rewriteOff Pr Pr Operation mode selectionPr. Simple magnetic flux vector 80, 90 control LED IndicationPr to Adjustable 5 points V/FCommunication initial setting Pr to 124, 331 to 337, 341 to 343Analog input bias/gain calibration Pr Pr Pr , C2902 to C7905Pr to 134, 575 to 577 PID control Analog input display unit changing PrSelection of action conditions Second function signal RTPr. Parameter unit display language 145 selection Pr Pr toPr to 196 output terminal Pr. Operation selection of the 161 operation panelTerminal assignment Function assignmentPr Increase cooling fan life Pr. Selection of motor stopping 250 method and start signalInput/output phase failure Pr to 247 Slip compensationPr Parameter for manufacturer setting. Do not set 261 to 266 power failurePower failure stop mode Pr.261 = Operation at instantaneousPr to 557 monitor signal To determine Maintenance time of partsPr to 497 REM signal Remote output functionPr to 899 Energy saving monitor Pr. Regeneration avoidanceFree parameter 882 to 886 functionParameter clear, parameter copy Pr PU contrast adjustmentPr. C0900, C1901 Adjustment of terminal FM AM calibration Pr , CL, ALLC, Er.CL, PcpyFunction Name Description Indication Error message *2 Minor fault *4 Major failures *5Protective Functions Regenerative overvoltage shutSupply short circuit RS-485 terminals power Was shorted Options Instructions MotorOption and Peripheral Devices OptionsOthers Controller/SpeedSeries ManualSpecifications, Structure, etc Stand-alone optionName type Name type Specifications, Structure, etc FR-BU-HK FR-BR-HKConnection example Cable Outline dimension drawingsExternal connection diagram Resistor unit Resistance Mass Type ValueHigh power factor Converter Outline dimension Unit mm FR-HC- HKApplication condition Circuit configuration and connectionApplication of the sine wave filter Capacitor for sine wave filterPeripheral devices list Standard Breaker EMC FilterOn mA Precautions for Operation/Selection Precautions for Peripheral Device Selection Noise Leakage currentsNoise reduction examples Input Target Measures Power Capacity Input Target Measures PowerThree 7kW Reference materials Phase Connect the AC reactor or DC reactor50Hz torque reference Application to Motor60Hz torque reference Suppressing the surge voltage on the inverter sideFR-F500 L FR-F700 Warranty FA Center in Asean FA Center in North AmericaFA Center in Taiwan FA Center in Korea