Mitsubishi Electronics FR-F700 instruction manual Fr-Bu-Hk, Fr-Br-Hk, Connection example

Page 52

Name (type)

Specifications, Structure, etc.

￿The brake unit and resistor unit are options that will fully exhibit the regenerative braking capability of the inverter and are always used as a set.

￿There are six different brake units as in the following table, from which make selection according to the necessary braking torque and deceleration time.

￿The brake unit is equipped with a seven-segment LED that displays the duty (%ED) and alarm.

￿Brake unit selection table

￿%ED at short-time rating when braking torque is 100%

 

 

Motor Capacity

5.5kW

7.5kW

11kW

15kW

18.5kW

22kW

30kW

37kW

45kW

55kW

 

 

Inverter

200V

5.5K

7.5K

11K

15K

18.5K

22K

30K

37K

45KK

55K

 

 

400V

5.5K

7.5K

11K

15K

18.5K

22K

30K

37K

45KK

55K

 

 

 

 

2

FR-BU-15K

 

80

40

15

10

------

------

------

------

------

------

unit

0

FR-BU-30K

%ED

------

------

65

30

25

15

10

------

------

------

 

0

 

 

 

 

 

 

 

 

 

 

 

 

Brake

V

FR-BU-55K

 

------

------

------

------

90

60

30

20

15

10

0

FR-BU-H30K

%ED

80------

------

65

30

25

15

10

------------

------

------

 

4

FR-BU-H15K

 

40

15

10

------

------

------

------

------

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

V

FR-BU-H55K

 

------

------

------

------

90

60

30

20

15

10

￿Braking torque (%) at short-time rating when 10%ED is 15s

 

 

Motor Capacity

5.5kW

7.5kW

11kW

15kW

18.5kW

22kW

30kW

37kW

45kW

55kW

 

 

 

Inverter

200V

5.5K

7.5K

11K

15K

18.5K

22K

30K

37K

45KK

55K

 

 

 

400V

5.5K

7.5K

11K

15K

18.5K

22K

30K

37K

45KK

55K

 

 

 

 

 

 

2

FR-BU-15K

Braking

280

200

120

100

80

70

------

------

------

------

 

unit

0

FR-BU-30K

Torque

------

------

260

180

160

130

100

80

70

------

Brake unit

V

FR-BU-55K

(%)

------

------

------

------

300

250

180

150

120

100

Brake

0

 

 

 

 

 

 

 

 

 

 

 

 

Resistor unit

0

FR-BU-H30K

Torque

------

------

260

180

160

130

100

80

70

------

 

 

4

FR-BU-H15K

Braking

280

200

120

100

80

70

------

------

------

------

 

 

0

 

(%)

 

 

 

 

 

 

 

 

 

 

 

 

V

FR-BU-H55K

------

------

------

------

300

250

180

150

120

100

 

Brake unit

￿ Brake unit and resistor unit combinations and used cables

 

 

 

 

 

 

(Note) 1. The temperature rise of the resistor unit is about a

 

 

Brake Unit Type

Resistor Unit Type

Cable (P/+-P/+, N/--

FR-BU-(H)￿￿K

 

 

maximum of 100°C. Therefore, use heat-resistant wires

 

 

 

 

N/-, P/+-P, PR-PR)

Resistor unit

 

2

FR-BU-15K

FR-BR-15K

3.5mm2

(such as glass wires).

 

 

FR-BR-(H)￿￿K

 

0

FR-BU-30K

FR-BR-30K

5.5mm2

 

 

0

 

 

 

V

FR-BU-55K

FR-BR-55K

14mm2

 

 

 

4

FR-BU-H15K

FR-BR-H15K

3.5mm2

 

 

 

0

FR-BU-H30K

FR-BR-H30K

3.5mm2

 

 

 

0

FR-BU-H55K

FR-BR-H55K

5.5mm2

 

 

 

V

 

Use the wires of the above recommended size or larger.

￿ Connection example

 

 

 

 

 

 

*3

 

 

 

 

 

 

 

 

 

ON

Inverter

 

 

 

 

 

 

 

 

 

 

FR-BU

FR-BR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

P/+

P/+

P/+

P

 

 

 

T *2

 

 

 

 

 

 

 

 

MC

 

 

 

 

 

 

 

 

 

 

N/-

N/-

PR

PR

 

 

 

 

 

 

 

 

 

 

 

MC

 

 

 

 

 

 

 

 

 

 

 

FR-BR

Within

 

Within

 

 

 

 

 

 

5m

 

5m

 

MCCB

MC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R/L1

U

Motor

P

TH1

Inverter

 

 

 

 

 

 

 

 

 

Three-phase AC

 

 

 

 

 

 

 

 

S/L2

V

IM

 

 

 

 

FR-BU

FR-BR

power supply

 

PR

 

 

 

 

 

 

 

 

Twist

 

 

Twist

 

 

T/L3

W

 

 

TH2

 

 

 

 

 

 

P/+

 

P/+ P/+

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter

 

FR-BU

N/-

 

N/- PR

PR

 

 

 

 

 

PR

HA

 

 

 

 

 

 

 

 

 

 

Within 10m

 

Within 10m

 

 

 

 

 

 

 

 

 

 

 

P/+

*1

P/+

HB

 

 

 

 

 

 

 

N/

N/

HC

 

 

 

 

 

 

 

 

*3. Minimize the cable length between the inverter and brake

 

 

 

 

*3

 

 

unit and the resistor unit and brake unit. Use a twisted

 

 

 

 

 

 

cable when the wiring length exceeds 5m. (If twisted

 

 

 

 

5m or less

 

 

 

 

 

 

 

 

wires are used, the distance should be within 10m.) Use

*1. Connect the inverter terminals (P/+, N/-) and brake unit (FR-BU (H)) terminals so that their

the wires of the above recommended size or larger.

terminal signals match with each other.

 

 

 

 

 

 

 

 

 

(Incorrect connection will damage the inverter.)

 

 

 

 

 

 

 

 

*2. When the power supply is 400V class, install a step-down transformer.

 

 

 

 

 

 

53

Image 52
Contents FR-F700 Energy savings for buildings and factories as a whole Outline Dimension Drawings Warranty InquiryConnection with Peripheral Devices Inverter FR-F700Why Can the Inverter Save Energy? Damper control discharge sideAmount Inverter controlStandard Specifications RatingType FR-F720-K Type FR-F740-KCommon specifications Can be selectedOperating status Open collectorOutline Dimension Drawings Inverter TypeFR-F720-0.75K 110 FR-F720-1.5K 125 FR-F740-0.75K to 2K are not provided With a cooling fanWiring cover FR-F740-15K, 18.5KFR-F720-30K is Not provided with aInverter Type Mass FR-F740-75K 140 120295 185 FR-HEL-H75K FR-F740-90K 150 130 310 190 FR-HEL-H90KDC reactor supplied FR-F740-110KFR-HEL-H110KMass kg MassRemove the eye nut after installation of the product MassRemove the eye nut after installation of the product FR-F740-400KFR-HEL-H400KFR-F740-450KFR-HEL-H450K Parameter ListPanel cutting dimension drawing Outline drawingPanel FR-DU07 M3 screw CableTerminal Connection Diagram Option connectorMain circuit Control circuitType Terminal Specification ExplanationTerminal Name Description Relay output 1 alarm Preset detected frequency. *1Relay OutputExplanation of the Operation Panel FR-DU07 Setting Operation mode switchoverBasic operation Name Setting Range Increments Initial Value Parameter ListRemarks Function24 to Jump100 101102 103135 139143 144178 179180 181261 262263 264867 872882 883Maximum/minimum Explanations of ParametersFrequency Jog operation Starting frequencySpeed and remote setting Stall prevention operationInput compensation of multi Pr , 23, 48, 49, 66, 148, 149, 154, 156Pr , 70 Selection of regeneration unit SettingSpeed display and speed Pr , 54, 158, 170, 171, 268, 563, 564, 867 Pr Remote setting function Connection diagramPr.59 Setting Description Pr , 58, 162 to 165, 299Retry function at alarm Pr Energy saving control selectionOccurrence Use the constant torque motorCarrier frequency and SoftPWM selection Analog input selectionPr , 240 Pr , 242, 243, 252, 253Pr. Reset selection, disconnected PU 75 detection Pr Output function of alarm codePr. Noise elimination at the analog 74 input Pr Prevention of parameter rewritePr Pr Operation mode selection Pr. Simple magnetic flux vector 80, 90 controlOff LED IndicationAdjustable 5 points V/F Communication initial settingPr to Pr to 124, 331 to 337, 341 to 343Pr Pr Pr , C2902 to C7905 Pr to 134, 575 to 577 PID controlAnalog input bias/gain calibration Analog input display unit changing PrSecond function signal RT Pr. Parameter unit display language 145 selectionSelection of action conditions Pr Pr toPr. Operation selection of the 161 operation panel Terminal assignmentPr to 196 output terminal Function assignmentPr. Selection of motor stopping 250 method and start signal Input/output phase failurePr Increase cooling fan life Pr to 247 Slip compensation261 to 266 power failure Power failure stop mode Pr.261 =Pr Parameter for manufacturer setting. Do not set Operation at instantaneousTo determine Maintenance time of parts Pr to 497 REM signalPr to 557 monitor signal Remote output functionPr. Regeneration avoidance Free parameterPr to 899 Energy saving monitor 882 to 886 functionPr PU contrast adjustment Pr. C0900, C1901 Adjustment of terminal FM AM calibrationParameter clear, parameter copy Pr , CL, ALLC, Er.CL, PcpyError message *2 Minor fault *4 Major failures *5 Protective FunctionsFunction Name Description Indication Regenerative overvoltage shutSupply short circuit RS-485 terminals power Was shorted Options Instructions MotorOption and Peripheral Devices OptionsController/Speed SeriesOthers ManualStand-alone option Specifications, Structure, etcName type Name type Specifications, Structure, etc FR-BR-HK FR-BU-HKConnection example Outline dimension drawings External connection diagramCable Resistor unit Resistance Mass Type ValueHigh power factor Converter Outline dimension Unit mm FR-HC- HKCircuit configuration and connection Application of the sine wave filterApplication condition Capacitor for sine wave filterPeripheral devices list EMC Filter Standard BreakerOn mA Precautions for Operation/Selection Precautions for Peripheral Device Selection Leakage currents NoiseNoise reduction examples Input Target Measures Power Three 7kW Reference materials PhaseInput Target Measures Power Capacity Connect the AC reactor or DC reactorApplication to Motor 60Hz torque reference50Hz torque reference Suppressing the surge voltage on the inverter sideFR-F500 L FR-F700 Warranty FA Center in North America FA Center in TaiwanFA Center in Asean FA Center in Korea