Mitsubishi Electronics FR-F700 instruction manual Leakage currents, Noise reduction examples

Page 60

Noise

When performing low-noise operation at higher carrier frequency, electromagnetic noise tends to increase. Therefore, refer to the following measure example and consider taking the measures. Depending on the installation condition, the inverter may be affected by noise in a non-low noise (initial) status.

￿The noise level can be reduced by decreasing the carrier frequency (Pr. 72).

￿As measures against AM radio broadcasting noise and sensor malfunction, turning on the built-in noise reduction filter produces an effect. (For the switching method, refer to the instruction manual.)

￿As measures against induction noise from the power cable of the inverter, an effect is produced by putting a distance of 30cm (at least 10cm) or more and using a twisted pair shielded cable as a signal cable. Do not earth (ground) shield but connect it to signal common

cable.

Noise reduction examples

Install filter (FR-BLF,

Enclosure Decrease carrier frequency FR-BSF01) on inverter output side.

Inverter

 

 

FR-

 

 

power

EMC

Inverter

IM

Motor

BLF

supply

filter

 

 

 

 

 

 

Use 4-core cable for motor

Separate inverter and

 

power cable and use one cable

power line by more than

 

as earth (ground) cable.

30cm (at least 10cm)

 

 

from sensor circuit.

 

Use a twisted pair shielded cable

Control

Power

Sensor

 

power

supply for

 

sensor

 

supply

 

 

 

Do not earth (ground)

 

Do not earth (ground) shield but

enclosure directly.

 

connect it to signal common cable.

Do not earth (ground) control cable.

Leakage currents

Capacitances exist between the inverter I/O cables, other cables and earth and in the motor, through which a leakage current flows. Since its value depends on the capacitances, carrier frequency, etc., low acoustic noise operation at the increased carrier frequency of the inverter will increase the leakage current. Therefore, take the following measures. Select the earth leakage breaker according to its rated sensitivity current, independently of the carrier frequency setting.

To-earth (ground) leakage currents

Type

Influence and Measures

Leakage currents may flow not only into the inverter's own line but also into the other lines through the earth (ground) cable, etc.These leakage currents may operate earth (ground) leakage circuit breakers and earth leakage relays unnecessarily.

Influence

￿ Countermeasures

If the carrier frequency setting is high, decrease the Pr. 72

and

 

PWM frequency selection setting.

measures

 

 

Note that motor noise increases. Select Pr. 240 Soft-PWM

 

 

 

 

operation selection to make the sound inoffensive.

By using earth leakage circuit breakers designed for harmonic and surge suppression in the inverter's own line and other line, operation can be performed with the carrier frequency kept high (with low noise).

 

 

Inverter

Power

NV1

Motor

 

supply

 

C

Undesirable

Leakage

 

breaker

C

current path

 

NV2

Motor

 

 

 

Leakage

C

 

 

 

breaker

 

Line leakage current

Type

Influence and Measures

This leakage current flows via a static capacitance between the inverter output cables.

The external thermal relay may be operated unnecessarily by the harmonics of the leakage current.When the wiring length is long (50m or more) for the 400V class small- capacity model (7.5kW or less), the external thermal relay is

Influence

likely to operate unnecessarily because the ratio of the

leakage current to the rated motor current increases.

and

￿ Countermeasures

measures

⋅ Use Pr. 9 Electronic thermal O/L relay.

If the carrier frequency setting is high, decrease the Pr. 72 PWM frequency selection setting.

Note that motor noise increases. Select Pr. 240 Soft-PWM operation selection to make the sound inoffensive.

To ensure that the motor is protected against line-to-line leakage currents, it is recommended to use a temperature sensor to directly detect motor temperature.

 

MCCB

MC

 

Thermal relay

Motor

 

 

 

 

 

Undesirable

Power

 

Inverter

 

IM

supply

 

 

current path

 

 

 

 

 

 

 

line-to-line static

 

 

 

 

 

 

 

 

capacitances

 

 

 

 

Line-to-line leakage currents path

61

Image 60
Contents FR-F700 Energy savings for buildings and factories as a whole Outline Dimension Drawings Warranty InquiryConnection with Peripheral Devices Inverter FR-F700Why Can the Inverter Save Energy? Damper control discharge sideAmount Inverter controlStandard Specifications RatingType FR-F720-K Type FR-F740-KCommon specifications Can be selectedOperating status Open collectorOutline Dimension Drawings Inverter TypeFR-F720-0.75K 110 FR-F720-1.5K 125 FR-F740-0.75K to 2K are not provided With a cooling fanWiring cover FR-F740-15K, 18.5KFR-F720-30K is Not provided with aInverter Type Mass FR-F740-75K 140 120295 185 FR-HEL-H75K FR-F740-90K 150 130 310 190 FR-HEL-H90KDC reactor supplied FR-F740-110KFR-HEL-H110KMass kg MassRemove the eye nut after installation of the product MassRemove the eye nut after installation of the product FR-F740-400KFR-HEL-H400KFR-F740-450KFR-HEL-H450K Parameter ListPanel cutting dimension drawing Outline drawingPanel FR-DU07 M3 screw CableTerminal Connection Diagram Option connectorMain circuit Control circuitTerminal Specification Explanation TypeTerminal Name Description Relay output 1 alarm Preset detected frequency. *1Relay OutputExplanation of the Operation Panel FR-DU07 Operation mode switchover SettingBasic operation Name Setting Range Increments Initial Value Parameter ListRemarks Function24 to Jump100 101102 103135 139143 144178 179180 181261 262263 264867 872882 883Explanations of Parameters Maximum/minimumFrequency Jog operation Starting frequencySpeed and remote setting Stall prevention operationInput compensation of multi Pr , 23, 48, 49, 66, 148, 149, 154, 156Setting Pr , 70 Selection of regeneration unitSpeed display and speed Pr , 54, 158, 170, 171, 268, 563, 564, 867 Pr Remote setting function Connection diagramPr.59 Setting Description Pr , 58, 162 to 165, 299Retry function at alarm Pr Energy saving control selectionOccurrence Use the constant torque motorCarrier frequency and SoftPWM selection Analog input selectionPr , 240 Pr , 242, 243, 252, 253Pr. Reset selection, disconnected PU 75 detection Pr Output function of alarm codePr. Noise elimination at the analog 74 input Pr Prevention of parameter rewritePr Pr Operation mode selection Pr. Simple magnetic flux vector 80, 90 controlOff LED IndicationAdjustable 5 points V/F Communication initial settingPr to Pr to 124, 331 to 337, 341 to 343Pr Pr Pr , C2902 to C7905 Pr to 134, 575 to 577 PID controlAnalog input bias/gain calibration Analog input display unit changing PrSecond function signal RT Pr. Parameter unit display language 145 selectionSelection of action conditions Pr Pr toPr. Operation selection of the 161 operation panel Terminal assignmentPr to 196 output terminal Function assignmentPr. Selection of motor stopping 250 method and start signal Input/output phase failurePr Increase cooling fan life Pr to 247 Slip compensation261 to 266 power failure Power failure stop mode Pr.261 =Pr Parameter for manufacturer setting. Do not set Operation at instantaneousTo determine Maintenance time of parts Pr to 497 REM signalPr to 557 monitor signal Remote output functionPr. Regeneration avoidance Free parameterPr to 899 Energy saving monitor 882 to 886 functionPr PU contrast adjustment Pr. C0900, C1901 Adjustment of terminal FM AM calibrationParameter clear, parameter copy Pr , CL, ALLC, Er.CL, PcpyError message *2 Minor fault *4 Major failures *5 Protective FunctionsFunction Name Description Indication Regenerative overvoltage shutSupply short circuit RS-485 terminals power Was shorted Options Instructions MotorOption and Peripheral Devices OptionsController/Speed SeriesOthers ManualSpecifications, Structure, etc Stand-alone optionName type Name type Specifications, Structure, etc FR-BU-HK FR-BR-HKConnection example Outline dimension drawings External connection diagramCable Resistor unit Resistance Mass Type ValueHigh power factor Converter Outline dimension Unit mm FR-HC- HKCircuit configuration and connection Application of the sine wave filterApplication condition Capacitor for sine wave filterPeripheral devices list Standard Breaker EMC FilterOn mA Precautions for Operation/Selection Precautions for Peripheral Device Selection Noise Leakage currentsNoise reduction examples Input Target Measures Power Three 7kW Reference materials PhaseInput Target Measures Power Capacity Connect the AC reactor or DC reactorApplication to Motor 60Hz torque reference50Hz torque reference Suppressing the surge voltage on the inverter sideFR-F500 L FR-F700 Warranty FA Center in North America FA Center in TaiwanFA Center in Asean FA Center in Korea