Selection of rated sensitivity current of earth (ground) leakage breaker

When using the earth leakage circuit breaker with the inverter circuit, select its rated sensitivity current as follows, independently of the PWM carrier frequency:

Breaker designed for harmonic and surge suppression

Rated sensitivity currentI ∆n ≥ 10 × (Ig1 + Ign + Igi + Ig2 + Igm)

Standard breaker

Rated sensitivity currentI ∆n ≥ 10 × {Ig1 + Ign + Igi + 3 × (Ig2 + Igm)}

Ig1, Ig2

: Leakage currents in wire path during commercial power supply

 

operation

Ign

: Leakage current of inverter input side noise filter

Igm

: Leakage current of motor during commercial power supply operation

Igi

: Inverter unit leakage current

(Note)1. Install the earth leakage breaker (ELB) on the input side of the inverter.

2.In the connection earthed-neutral system, the sensitivity current is purified against an earth (ground) fault in the inverter output side. Earthing (Grounding) must conform to the requirements of national and local safety regulations and electrical codes. (JIS, NEC section 250, IEC 536 class 1 and other applicable standards)

￿Selection example (in the case of the left figure)

 

Breaker Designed for

 

Standard Breaker

 

Harmonic and Surge

 

 

Suppression

 

 

 

Leakage current

1

 

 

5m

Ig1 (mA)

 

 

× 66 ×

 

 

= 0.11

3

 

 

1000m

 

Features

 

 

 

 

 

 

 

Peripheral Devices

Why energy

savings?

 

 

 

 

Standard

Specifications

 

 

 

 

Example of leakage current per 1km during the commercial power supply operation when the CV cable is routed in metal conduit

(Three-phase three-wire delta connection 400V60Hz)

(mA)

100

 

 

 

 

 

 

 

 

 

 

currents

120

 

 

 

 

 

 

 

 

 

 

8 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

leakage

4 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 0

 

 

 

 

 

 

 

 

 

 

2 3.5

 

 

 

8

 

142238

 

 

80150

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.5

3060100

Power supply size (mm2)

Leakage current example of Three-phase induction motor during the commercial power supply operation

(Totally-enclosed fan-cooled type motor 400V60Hz)

(mA)

2. 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

currents

 

 

 

 

 

 

 

 

 

 

 

 

0. 3

 

 

 

 

 

 

 

 

 

 

 

 

 

0. 7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

leakage

0. 5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0. 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

5

3.

7

7.

5

 

15223755

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0. 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2. 2

5.5 1118. 53045

 

Motor capacity (kW)

Leakage current

 

 

 

0 (without noise filter)

 

Ign (mA)

 

 

 

 

 

 

 

 

 

 

 

 

 

Leakage current Igi

 

 

 

1 (Without EMC filter)

 

Refer to the following table for the leakage current of the

(mA)

 

 

 

 

inverter

 

 

 

 

 

 

 

Leakage current

 

1

 

× 66 ×

 

60m

 

= 1.32

Ig2(mA)

3

 

 

1000m

 

 

 

 

Motor leakage

 

 

 

 

0.36

 

 

 

current Igm (mA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total leakage

 

 

2.79

 

 

 

 

6.15

current (mA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated sensitivity

 

 

 

 

 

 

 

 

 

current (mA)(≥ Ig ×

 

 

30

 

 

 

 

100

10)

 

 

 

 

 

 

 

 

 

Outline

Dimension

Drawings

 

 

 

 

 

 

 

 

 

 

 

 

Terminal Connection

Diagram

Terminal Specification

Explanation

 

 

 

 

 

 

 

Operation

Panel

 

 

 

 

 

 

 

For " " connection, the amount of leakage current is 1/3

example

5.5mm2 5m

5.5mm2 60m

 

ELB

Noise

 

 

 

filter

 

3φ

 

Inverter

IM

 

400V

 

 

 

2.2kW

Ig1

Ign

Ig2

Igm

 

Igi

 

 

￿Inverter leakage current (with and without EMC filter)

Input power conditions

(200V class : 220V/60Hz, 400V class : 440V/60Hz, power supply unbalance within 3%)

 

Voltage

EMC Filter

 

(V)

ON (mA)

OFF (mA)

Phase

200

22(1) *

1

grounding

 

 

 

 

400

30

1

Earthed-neutral

 

 

 

system

 

 

 

 

400

1

1

*For the 200V class 0.75K and 1.5K, the EMC filter is always valid. The leakage current is 1mA.

Parameter

List

 

 

 

 

Explanations of Parameters

 

 

Protective

Functions

 

 

 

 

Options

 

 

 

 

Instructions

 

 

 

 

Motor

 

 

 

 

Compatibility

 

 

Warranty

 

 

 

 

Inquiry

 

 

58

Image 57
Contents FR-F700 Energy savings for buildings and factories as a whole Warranty Inquiry Outline Dimension DrawingsInverter FR-F700 Connection with Peripheral DevicesDamper control discharge side Why Can the Inverter Save Energy?Amount Inverter controlRating Standard SpecificationsType FR-F720-K Type FR-F740-KCan be selected Common specificationsOperating status Open collectorInverter Type Outline Dimension DrawingsFR-F720-0.75K 110 FR-F720-1.5K 125 FR-F740-0.75K to 2K are not provided With a cooling fanFR-F740-15K, 18.5K Wiring coverFR-F720-30K is Not provided with aFR-F740-75K 140 120 Inverter Type Mass295 185 FR-HEL-H75K FR-F740-90K 150 130 310 190 FR-HEL-H90KFR-F740-110KFR-HEL-H110K DC reactor suppliedMass kg MassMass Remove the eye nut after installation of the productFR-F740-400KFR-HEL-H400K Remove the eye nut after installation of the productFR-F740-450KFR-HEL-H450K Parameter ListOutline drawing Panel cutting dimension drawingPanel FR-DU07 M3 screw CableOption connector Terminal Connection DiagramMain circuit Control circuitTerminal Specification Explanation TypeTerminal Name Description Preset detected frequency. *1 Relay output 1 alarmRelay OutputExplanation of the Operation Panel FR-DU07 Operation mode switchover SettingBasic operation Parameter List Name Setting Range Increments Initial ValueRemarks FunctionJump 24 to101 100102 103139 135143 144179 178180 181262 261263 264872 867882 883Explanations of Parameters Maximum/minimumFrequency Starting frequency Jog operationStall prevention operation Speed and remote settingInput compensation of multi Pr , 23, 48, 49, 66, 148, 149, 154, 156Setting Pr , 70 Selection of regeneration unitSpeed display and speed Pr , 54, 158, 170, 171, 268, 563, 564, 867 Connection diagram Pr Remote setting functionPr.59 Setting Description Pr , 58, 162 to 165, 299Pr Energy saving control selection Retry function at alarmOccurrence Use the constant torque motorAnalog input selection Carrier frequency and SoftPWM selectionPr , 240 Pr , 242, 243, 252, 253Pr Output function of alarm code Pr. Reset selection, disconnected PU 75 detectionPr. Noise elimination at the analog 74 input Pr Prevention of parameter rewritePr. Simple magnetic flux vector 80, 90 control Pr Pr Operation mode selectionOff LED IndicationCommunication initial setting Adjustable 5 points V/FPr to Pr to 124, 331 to 337, 341 to 343Pr to 134, 575 to 577 PID control Pr Pr Pr , C2902 to C7905Analog input bias/gain calibration Analog input display unit changing PrPr. Parameter unit display language 145 selection Second function signal RTSelection of action conditions Pr Pr toTerminal assignment Pr. Operation selection of the 161 operation panelPr to 196 output terminal Function assignmentInput/output phase failure Pr. Selection of motor stopping 250 method and start signalPr Increase cooling fan life Pr to 247 Slip compensationPower failure stop mode Pr.261 = 261 to 266 power failurePr Parameter for manufacturer setting. Do not set Operation at instantaneousPr to 497 REM signal To determine Maintenance time of partsPr to 557 monitor signal Remote output functionFree parameter Pr. Regeneration avoidancePr to 899 Energy saving monitor 882 to 886 functionPr. C0900, C1901 Adjustment of terminal FM AM calibration Pr PU contrast adjustmentParameter clear, parameter copy Pr , CL, ALLC, Er.CL, PcpyProtective Functions Error message *2 Minor fault *4 Major failures *5Function Name Description Indication Regenerative overvoltage shutOptions Instructions Motor Supply short circuit RS-485 terminals power Was shortedOptions Option and Peripheral DevicesSeries Controller/SpeedOthers ManualSpecifications, Structure, etc Stand-alone optionName type Name type Specifications, Structure, etc FR-BU-HK FR-BR-HKConnection example External connection diagram Outline dimension drawingsCable Resistor unit Resistance Mass Type ValueConverter Outline dimension Unit mm FR-HC- HK High power factorApplication of the sine wave filter Circuit configuration and connectionApplication condition Capacitor for sine wave filterPeripheral devices list Standard Breaker EMC FilterOn mA Precautions for Operation/Selection Precautions for Peripheral Device Selection Noise Leakage currentsNoise reduction examples Three 7kW Reference materials Phase Input Target Measures PowerInput Target Measures Power Capacity Connect the AC reactor or DC reactor60Hz torque reference Application to Motor50Hz torque reference Suppressing the surge voltage on the inverter sideFR-F500 L FR-F700 Warranty FA Center in Taiwan FA Center in North AmericaFA Center in Asean FA Center in Korea