•Above the unit
An HP Water Hook Up Kit must be installed prior to activating an MCS-200/100. The kit contains approximately 350 cm (138 inches) of flexible hose with terminated fittings on each end. The length that is available outside the MCS-200/100 depends on the preferred type of connection.
Available hose lengths outside the MCS-200/100 by connection type
Connection type | Approximate length supply | Approximate length return hose |
| hose | |
| | |
Bottom | 280 cm (110 inches) | 300 cm (118 inches) |
Rear | 280 cm (110 inches) | 300 cm (118 inches) |
Top | 200 cm (79 inches) | 180 cm (71 inches) |
The following figure shows the location of the condensate and overflow in the rear of the cooling unit. The MCS-200/100 includes both tubes for the hookup. Each tube is approximately 3 m (9 ft) in length. The overflow hose has an inner diameter of 9 mm (0.35 inch) and the condensation hose has an outer diameter
Facility planning for implementation 50