When the minimum heat load is not provided to the MCS-200/100, unstable control of the temperatures and flow rates of the MCS-200/100 can occur.
For more information, contact your HP representative.
The following charts offer a guideline for determining the approximate amount of heat that can be removed from MCS-200/100 based on 20°C (68°F) and 25°C (77°F) server intake air temperatures (in degrees, Celsius), flow rates as liters per minute (lpm), or in US gallons per minute (gpm), delivered to the unit.
The term “water” in the following charts refers to the coolant described in “Acceptable water quality specifications (on page 78).”
MCS-100 coolant flow requirements with 20°C (68°F) server intake air
Facility planning for implementation 74