HP Modular Cooling System manual HP Water Hook-Up Kit

Page 47

Flow rate and pressure capacity of chilled water plant input to the design of the facility feed line and dedicated water loop pipe diameters

Material compatibility within piping system to minimize the potential for electrochemical corrosion, and must be corrosion-resistant

Minimization of elbows and other restrictions that increase flow resistance

Insulation of piping to minimize risk of condensation and reduce incidental heating of supplied chilled water

Availability of a floor drain or reclamation system to capture system condensation

Structural securing of piping to support weight of distribution network filled with water

Water quality management, including particulate filtration, treatment, and flushing provisions, with isolation valves for service requirements

Availability and access to a data center leak detection system to monitor the infrastructure system for leaks

Air vents installed at the highest point in the pipe system

Each MCS-200/100 has an air vent, but additional vents in the supply piping system must be considered.

HP Water Hook-Up Kit

HP recommends using the MCS-200/100 Water Hook-up Option Kit BW971A, available on the HP website (http://www.hp.com), to connect the MCS-200/100 to a facility chilled water system. Each kit includes the hoses and accessories required for connecting the facility supply and return lines to the main inlet and outlet connections of an MCS-200/100 unit and must be installed prior to the delivery of an MCS-200/100.

MCS-200/100 Water Hook-Up Option Kit contents

Item

1

2

3

Description (quantity)

Main hose assembly* (2)

90-degree elbow assembly (2)

Teflon gasket (2)

Facility planning for implementation 47

Image 47
Contents Part Number June Edition HP Modular Cooling System 200/100 Site Preparation GuidePage Contents Before you contact HP HP contact information Appendix B Conversion factors and formulasOverview OverviewMCS-100 unit dual-rack configuration MCS-200 unit single-rack configuration Product overview Air flow for MCS-100 single-rack configuration Air flow for MCS-100 dual-rack configuration Air flow for MCS-200 single-rack configuration Key components MCS-100 components Description MCS-200 components Unit top view MCS-100 expansion rack physical specifications Physical specificationsElectrical specifications Parameter Value Comments Space and positioning considerations Facility planning for implementationFacility planning overview Maneuvering space requirements Delivery space requirementsMCS-200/100 Reference MCS-200/100 expansion rack Reference Operational space requirementsFacility planning for implementation System positioning Cable openings Facility planning for implementation Facility planning for implementation Top view Bottom view Cabinet leveling feetFacility planning for implementation MCS-100 dual-rack configuration IT rack side view MCS-100 single-rack configuration Facility planning for implementation MCS-200 single-rack configuration MCS-200 dual-rack configuration IT rack side view MCS-200 single-rack configuration Floor loading considerations Facility planning for implementation Page Rating WeightElectrical considerations Term DescriptionSystem grounding MCS-200 Raised floor grounding Description Electrical planning around water-handling components Connecting to facility A/C powerVoltage fluctuations and outages Facility planning for implementation Coolant source planning Plumbing considerations HP Water Hook-Up Kit M6 screw Above the floor for MCS-200 only Facility planning for implementation Piping approaches Hose openings Bottom view Top view MCS-200 hose openings Bottom view Top view MCS-100 floor tile cutouts Raised floor cutouts for the MCS unitRear view Facility planning for implementation Facility planning for implementation Facility planning for implementation Facility planning for implementation Facility planning for implementation Facility planning for implementation Facility planning for implementation Facility planning for implementation Facility planning for implementation Facility planning for implementation Facility planning for implementation Chilled water system components Fittings Astm B16.22 Wrought copper Strainer Description SpecificationsWatts TP or equivalent Typical plumbing installation guidelinesGeneral thermal requirements Coolant requirementsDetermining heat load capacities Cooling loop sizingPage Facility planning for implementation Facility planning for implementation Facility planning for implementation Facility planning for implementation Additional water precautions Acceptable water quality specificationsPlumbing materials to avoid Before installing and running active componentsEnvironmental considerations Control systemFacility planning for implementation Delivery survey form Appendix a Forms and checklistsDimension Measurement Area/condition Yes Comment/date Pre-installation checklistsSite preparation checklist Safety considerations Appendix a Forms and checklists Conversion factors and formulas Appendix B Conversion factors and formulasRegulatory information Safety and regulatory complianceWarranty information Regulatory requirements for Exit signs Regulatory information HP contact information Support and other resourcesBefore you contact HP Acronyms and abbreviations Water steam pressure Uninterruptible power systemDocumentation feedback Index Site preparation checklist