•Fan controller—Operates the fans, according to the cabinet air temperature
•Air bleeder valve—Enables air to manually bleed out of the system when coolant is initially filled
•Water controller—Senses condensation, leaks, water temperatures, flow rate, and the status of the water valve, and sends this data to the management module
•AC input/network connection—Provides primary and secondary AC input connections, if available, and a network management interface
•AC transfer switch—Provides dual-AC power with a fail-over feature for redundancy
•Fans—Provide circulation of cooled air through the computer equipment rack
•Water group—Includes the water valve, flow meter, check valve, and temperature sensors A condensation pump with overflow and condensation lines connects to the water group. Each MCS-200/100 has one water group.
MCS-100 components
The MCS-100 is an air and water heat exchanger that removes high levels of excess heat generated by equipment installed in HP racks. The installed equipment pulls cold air in through the front of the closed MCS-100 and uses that air for internal cooling. After the air is warmed, the MCS-100 expels the air through the rear vents.
Overview 13