Weight
385 kg (849 lb)
455 kg (1003 lb)
458 kg (1010 lb)
385 kg (849 lb)
375 kg (827 lb)
457 kg (1007 lb)
457 kg (1007 lb)
375 kg (827 lb)
CAUTION: To reduce the risk of damage to the casters, make sure that the full weight of the rack rests on the leveling feet and feet pads, and not on the casters. The casters are designed only as an aid in moving the rack into position. They are not designed to support the weight of the rack, and the casters may become damaged if relied on to support the rack.
Common floor-loading terms
Term | Description |
|
|
Dead load | The weight rating for the load the floor can support expressed in kg/m² (lb/ft²) |
|
|
Uniform load | The load that the floor system can safely support; expressed in kg/m² (lb/ft² or kN/m²) |
Concentrated load* | The load that a floor panel can support on a 25 x 25 mm² (1 x 1 inches²) at the panels |
| weakest point (typically the center of the panel), without the surface of the panel |
| deflecting more than a predetermined amount |
|
|
Rolling load | The load a floor panel can support (without failure) when a wheel of specified diameter |
| and width is rolled across the panel |
Example: Tate All Steel 1250 raised floor specifications
Item | Rating |
|
|
Dead load | 34.2 kg/m² (7 lb/ft²) |
|
|
Uniform load | 1,552 kg/m² (400 lb/ft²) |
Concentrated load* | 567 kg (1,250 lb) |
Rolling load | 227 kg (500 lb) |
*With 2.54 mm (0.10 inch) of span maximum deflection
Electrical considerations
The electrical practices and suggestions in this guide are based on North American practices. For regions and areas outside North America, local electrical codes take precedence. An example would be the recommendation that the protective ground conductor should be green with yellow
WARNING: To avoid personal injury and damage to the equipment, be sure that an emergency power shut off switch is in place and is easily accessible.