VENTILATION
OPERATION
WARNING
Follow the minimum fresh, outside air ventilation requirements. If proper fresh, outside air ventilation is not provided, carbon monoxide poisoning can occur. Provide proper fresh, outside air ventilation before running heater.
Provide a fresh air opening of at least 2800 square cm (3 square feet) for each 29.3 kW (100,000 BTU/Hr) rating. Provide extra fresh air if more heaters are being used.
Example: A 44 kW (150,000 BTU/Hr) heater requires one of the following:
•a 4.88 m (16 foot) wide
•a 2.75 m (9 foot) wide
•two, 76.20 cm (30 inch) wide windows raised 28 cm (11 inches)
WARNING
Review and understand the warnings in the Safety Information Section. They are needed to safely operate this heater. Follow all local codes when using this heater.
To Start Heater
1.Follow all ventilation and safety information.
2.Fill fuel tank with kerosene or No. 1 fuel oil.
3.Attach fuel cap.
4.Plug power cord of heater into standard 230 volt/50 hertz, grounded (earthed) outlet. Use an extension cord if needed. Use only a
Extension Cord Wire Size Requirements
Up to 30.5 meters (100 feet) long, use 1.0 mm2 (16 AWG) conductor
30.6 to 61 meters (101 to 200 feet) long, use 1.5 mm2 (14 AWG) conductor
Heater will start when power cord is plugged into outlet. If not, push in flame- out control reset button (see Figure 4).
Control
Reset Button
(Fan Guard
Removed)
Figure 4 - Flame-Out Control Reset Button
Continued
7