Trane Vertical Bypass/Non Bypass Panel, TR200 specifications Pre-installation, Receiving Inspection

Page 13
Pre-installation

Pre-installation

2 Pre-installation

2.1.1 Receiving Inspection

Inspect the packaging and equipment closely when received. Any indication of careless handling by the carrier should be noted on the delivery receipt, especially if the equipment will not be immediately uncrated. Obtain the delivery person’s signed agreement to any noted damages for any future insurance claims. Ensure that the model number and power match the order and intended use for the drive.

IMPORTANT LOST OR DAMAGED GOODS INSPECT THIS SHIPMENT IMMEDIATELY UPON ARRIVAL If goods are received short or in damaged condition, insist on a notation of the loss or damage across the face of the freight bill. Otherwise no claim can be enforced against the transportation company. If concealed loss or damage is discovered, notify your carrier at once and request an inspection. This is absolutely necessary. Unless you do this the carrier will not entertain any claim for loss or damage. The agent will make an inspection and can grant a concealed damage notation. If you give the transportation company a clear receipt for equipment that has been damaged or lost in transit, you do so at your own risk and expense.

Trane is willing to assist you to collect claims for loss or damage, but willingness on our part does not make us responsible for collection of claims or replacement of material. The actual filing and processing of the claim is your responsibility.

Figure 2.1 Sample Panel Label

2.1.2 Pre-installation Check

1.Compare panel model number to what was ordered.

2.Ensure each of the following are rated for the same voltage:

Drive

Panel

Power line

Motor

3.Ensure that the panel output rating is equal to or greater than motor total full load current for full motor performance.

Motor power size and panel must match for proper overload protection.

If panel rating is less than motor; full motor output cannot be achieved.

4.Check motor wiring:

Any disconnect between drive and motor should be interlocked to drive safety interlock circuit to avoid unwanted drive trips.

Do not connect power factor correction capacitors between the drive and motor.

Two speed motors must be wired permanently for full speed.

Y-start, Δ-run motors must be wired permanently for run.

2.1.3 Installation Site Check

Because the option panel relies on the ambient air for cooling, it is important to observe the limitations on ambient air temperature. Derating concerns start above 104°F (40°C) and 3300 feet (1000m) elevation above sea level.

It is important with multiple panels to check wall strength. Make sure that the proper mounting screws or bolts are used.

Ensure that the wall or floor area for installation will support the weight of the unit.

If construction work continues after the equipment is mounted, it is important to keep the interior free from concrete dust and similar

BAS-SVX49A-EN

2-1

Image 13
Contents TR200 Vertical Bypass/Non Bypass Panel Operators GuideBAS-SVX49A-EN AugustSafety Guidelines SafetyEQUIPMENT HAZARD UNINTENDED START2 Pre-installation Contents3 Installation 1 Introduction5 Electromechanical Bypass EMB2 Operation 4 Start Up6 Electronically Controlled Bypass ECB Operation 8 Appendix 7 Start Up TroubleshootingBAS-SVX49A-EN Contents1.1.1 Purpose of the Manual 1 Introduction1.1.2 Overview 1.1.3 Typical Bypass Operation1.3.1 Common Run/Stop with Bypass 1.3 Bypass Options1.3.2 Automatic Bypass 1.3.3 Run Permissive in Bypass1.5 Switch Mode Power Supply 1.4 Bypass Platform Configurations1.5.1 Control Transformer 1.6 Disconnects 1.6.1 Main DisconnectIntroduction 1.6.2 Mode Selector SwitchTable 1.3 Tier Definitions and Features 1.6.3 Panel ConfigurationsIntroduction Non bypass1.6.4 Panel Voltage and Frame Ratings 1.7Power Component Functions 1.7.1 Power FusingMain fusing Drive fusing2.1.2 Pre-installationCheck 2 Pre-installation2.1.3 Installation Site Check 2.1.1 Receiving Inspection2.2.1 Airborne Liquids 2.2Harsh Environments2.2.2 Airborne Solids 2.2.3 Corrosive Chemicals3.1.1 Tools Required 3 Installation3.1.2 Drive Fuses Installation230 V AC Installation460 V AC 600 V AC3.2.4 Shipping Weights 3.2Mechanical Installation 3.2.1 Lifting3.1.3 Internal Main Panel Fuses 3.2.3 ForkliftInstallation 3.3 CoolingFigure 3.2 Side Cooling Clearance Figure 3.1 Proper Lifting MethodProper Field Wiring and Grounding Required 3.4 Electrical InstallationHazardous Voltage INDUCED VOLTAGEFigure 3.4 Power Connections InstallationBAS-SVX49A-EN Figure 3.5 P2 Bypass Mechanical Layout Diagram InstallationTable 3.8 Reference Designator Definitions BAS-SVX49A-EN InstallationFigure 3.7 P3 Bypass Mechanical Layout Diagram InstallationBAS-SVX49A-EN 3-10 InstallationBAS-SVX49A-EN Figure 3.9 P4 Bypass Mechanical Layout Diagram InstallationBAS-SVX49A-EN 3-113-12 InstallationBAS-SVX49A-EN Figure 3.11 P5 Bypass Mechanical Layout Diagram InstallationBAS-SVX49A-EN 3-133-14 InstallationBAS-SVX49A-EN Installation 3.4.2 Wire and Cable AccessHazardous Voltage IMPORTANT NOTEFigure 3.15 P2 Panel Figure 3.16 P3 Panel Installation3-16 BAS-SVX49A-ENFigure 3.17 P4 Panel InstallationBAS-SVX49A-EN 3-17Figure 3.18 P5 Panel Installation3-18 BAS-SVX49A-ENInstallation 3.4.3 Wire Size3.4.5 Terminal Tightening Torques 3.4.4 Wire Type RatingInstallation Non Bypass InstallationBypass HP KWGround Wire Installation230 V AC Non BypassGround Wire Installation460 VAC OutputGround Wire Installation600 VAC Non Bypass3.4.6 Input Line Connection 3.4.7 Motor WiringInstallation Hazardous Voltage3.4.8 Grounding Earthing 3.4.9 Control WiringInstallation Field WiringInstallation 3.4.10Serial Communication Bus ConnectionProgramming Installation 3.4.11 Drive Control TerminalsHAZARDOUS VOLTAGE 4 Start UpStart Up 4.1.1 Inspection Prior to Start Up 4.1.2 Start Up ProcedureHAZARDOUS VOLTAGE Start UpStart Up MOTOR STARTBAS-SVX49A-EN Start UpElectromechanical Bypass EMB2 Operation 5 Electromechanical Bypass EMB2 OperationBAS-SVX49A-EN Electromechanical Bypass E5.1.3 EMB2 Common Run/Stop 5.1.2 EMB2 Auto BypassAuto Bypass Function Setup Common Run/Stop Setup5.1.5 EMB2 Overload 5.1.4 EMB2 Run PermissiveMOTOR DAMAGE Run Permissive Function Setup5.1.8 EMB2 Fault Reporting 5.1.6 EMB2 Safety Interlock5.1.7 EMB2 Fire Mode Safety Interlock Function SetupFault Reporting Function Setup 5.1.9 EMB2 SwitchesMode selector switch Electromechanical Bypass E6.1Electronically Controlled Bypass ECB Operation 6 Electronically Controlled Bypass ECB Operation6.1.1 Overview 1 2 3 4 6.1.2 ECB Control CardElectronically Controlled B BAS-SVX49A-EN Figure 6.2 ECB Control Card Terminal ConnectionsElectronically Controlled Bypass ECB Opera- tion Input Conn Electronically Controlled BTerm Function6.1.3 ECB Drive or Bypass Selection BAS-SVX49A-EN Electronically Controlled B130BX238.10 6.1.4 ECB Programming 6.1.6 ECB Mode of Operation 6.1.5 ECB Hand/OFF/AutoElectronically Controlled B General InformationPar. No Mode of Operation SelectSelection Function6.1.8 ECB Auto Bypass 6.1.7 Bypass Status Word Bit ExamplesAuto Bypass Function Setup Electronically Controlled B6.1.10 ECB Overload 6.1.9 ECB Run PermissiveRun Permissive Function Setup Disable Run Permissive6.1.12 ECB Common Run/Stop 6.1.11 ECB Safety InterlockSafety Interlock Function Setup Overload Function Setup6.1.13 ECB Advanced Fire Mode 6.1.14 ECB Fault ReportingFire Mode Function Setup Fault Reporting Function Setup6-14 Electronically Controlled BBAS-SVX49A-EN 7.1.1 Option Panel Alarm and Warnings 7 Start Up TroubleshootingStart Up Troubleshooting CodeSymptom Start Up TroubleshootingSolution Table 7.3 Fault TableSolution SymptomPossible cause TestSymptom Start Up TroubleshootingSolution Possible cause8.1.1 Dimensions 8 AppendixP2 BYPASS P3 BYPASSAppendix 8.1.2 Mechanical DiagramsFigure 8.1 P2 Bypass Figure 8.2 P2 Non-bypass AppendixBAS-SVX49A-EN BAS-SVX49A-EN AppendixFigure 8.3 P3 P4 P5 Bypass Figure 8.4 P3 P4 P5 Non-bypass AppendixBAS-SVX49A-EN Appendix 8.1.3 Typical Wiring DiagramsFigure 8.5 EMB2 with Control Relay, Part Figure 8.6 EMB2 with Control Relay, Part AppendixBAS-SVX49A-EN Figure 8.7 EMB2, Part AppendixBAS-SVX49A-EN BAS-SVX49A-EN AppendixFigure 8.8 EMB2, Part Figure 8.9 ECB, Part Appendix8-10 BAS-SVX49A-ENFigure 8.10 ECB, Part AppendixBAS-SVX49A-EN 8-11Figure 8.11 ECB with Control Relays, Part Appendix8-12 BAS-SVX49A-ENFigure 8.12 ECB with Control Relays, Part AppendixBAS-SVX49A-EN 8-13Figure 8.13 Non-bypass Appendix8-14 BAS-SVX49A-ENPage 177R0253 MG14D122 *MG14D122