Installation
460 VAC
|
|
| Panel (TR200) Non Bypass | Maximum Field | Field Ground | Minimum Temperature | |
HP (KW) | UL Motor Current | Wiring Size Class B | Wiring Size Class B | Wire Rating "°C" Copper | |||
& Bypass | |||||||
|
|
| or C | or C | Conductor | ||
|
|
|
| ||||
|
|
|
|
|
|
| |
15 | (11) | 21 |
| 10 AWG | 10 AWG | 60 | |
|
|
|
|
|
|
| |
20 | (15) | 27 | P2 | 8 AWG | 10 AWG | 60 | |
|
|
|
|
|
| ||
25 (18.5) | 34 |
| 6 AWG | 10 AWG | 60 | ||
|
|
|
|
|
|
| |
30 | (22) | 40 |
| 6 AWG | 10 AWG | 60 | |
|
|
|
|
|
|
| |
40 | (30) | 52 | P3 | 4 AWG | 10 AWG | 60 | |
|
|
|
|
|
|
| |
50 | (37) | 65 |
| 3 AWG | 8 AWG | 60 | |
|
|
|
|
|
|
| |
60 | (45) | 77 | P4 | 1 AWG | 8 AWG | 60 | |
|
|
|
|
|
| ||
75 | (55) | 96 | 1 AWG | 8 AWG | 60 | ||
| |||||||
100 | (75K) | 124 | P5 | 2/0 AWG | 6 AWG | 75 | |
125 (90) | 156 | 3/0 AWG | 6 AWG | 75 | |||
| |||||||
|
|
| 600 VAC |
|
| ||
|
|
| Panel (TR200) Non Bypass | Maximum Field | Field Ground | Minimum Temperature | |
HP (KW) | UL Motor Current | Wiring Size Class B | Wiring Size Class B | Wire Rating "Degree C" | |||
& Bypass | |||||||
|
|
| or C | or C | Copper Conductor | ||
|
|
|
| ||||
15 | (11) | 17 |
| 10 AWG | 10 AWG | 60 | |
|
|
|
|
|
|
| |
20 | (15) | 22 | P2 | 10 AWG | 10 AWG | 60 | |
|
|
|
|
|
| ||
25 (18.5) | 27 |
| 8 AWG | 10 AWG | 60 | ||
|
|
|
|
|
|
| |
30 | (22) | 32 |
| 8 AWG | 10 AWG | 60 | |
|
|
|
|
|
|
| |
40 | (30) | 41 | P3 | 6 AWG | 10 AWG | 60 | |
|
|
|
|
|
|
| |
50 | (37) | 52 |
| 4 AWG | 10 AWG | 60 | |
|
|
|
|
|
|
| |
60 | (45) | 62 | P4 | 3 AWG | 8 AWG | 60 | |
|
|
|
|
|
| ||
75 | (55) | 77 | 1 AWG | 8 AWG | 60 | ||
| |||||||
|
|
|
|
|
| ||
100 (75) | 99 | P5 | 1 AWG | 8 AWG | 60 | ||
|
|
|
|
|
| ||
125 (90) | 125 | 2/0 AWG | 6 AWG | 75 | |||
| |||||||
|
|
|
|
|
|
|
Table 3.10 Wire Size Chart 460 and 600 V
3.4.4 Wire Type Rating
•The wire style rating specifications are provided inTable 3.9 and Table 3.10
3.4.5 Terminal Tightening Torques
•
•
Tighten all connections to the torque specifications provided in Table 3.11 and Table 3.13
The torque specifications are also located on the tightening torque and wire rating label inside the panel cover. See Table 3.15 for a sample of the torque and wire rating data.