Electronically Controlled Bypass (ECB) Opera- tion
•Auto bypass mode: When in drive mode, auto bypass is a timed interval that allows a fault condition in the drive to activate running the motor in bypass without operator intervention.
Mode of Operation Select
•Mode of operation is programmed through parameter group
Par. No. | Selection | Function |
Bypass Mode | Selects source of motor power. | |
|
| (0) Drive (drive mode) (1) Bypass (bypass |
|
| mode) |
|
|
|
Bypass Start Time Delay | Sets a delay time for starting in bypass that | |
|
| allows for external actions to take place prior |
|
| to line starting the motor. |
|
|
|
|
| |
|
|
|
Bypass Trip Time Delay | Setting a value other than 0 sec. enables | |
|
| auto bypass. Bypass trip delay sets the delay |
|
| time before switching to bypass mode when |
|
| the drive has a fault. |
|
|
|
|
| |
|
|
|
Test Mode Activation | Setting enabled puts bypass in test mode. | |
|
| See the manual for warnings and cautions. |
|
|
|
|
| (0) disabled (default value) (1) enabled |
|
|
|
Bypass Status Word | ||
|
| status in hex. See the next table for details. |
|
|
|
|
| 0, |
|
|
|
Bypass Running Hours | Read only display which shows bypass | |
|
| running hours. |
|
|
|
Table 6.4 Bypass Parameter Functions
Bit | Description |
|
|
0 | Test Mode The Test Mode bit will be true when the ECB is in Test Mode. |
|
|
1 | Drive Mode The Drive Mode bit will be true when the ECB is in Drive Mode. |
|
|
2 | Automatic Bypass Mode The Automatic Bypass Mode bit will be true when the ECB is in Automatic Bypass Mode. |
3 | Bypass Mode The Bypass Mode bit will be true when the ECB is in Bypass Mode. |
4 | Reserved This bit is reserved for future use. |
5 | Motor Running from Bypass/Drive The Motor Running from Bypass/Drive Bit will be true when the motor is running from |
| either the drive or the bypass. |
6 | Overload Trip The Overload Trip Bit will be true when the ECB detects an overload trip. |
|
|
7 | M2 Contactor Fault The Contactor Fault Bit will be true when an M2 Contactor Fault is detected. |
|
|
8 | M3 Contactor Fault The Contactor Fault Bit will be true when an M3 Contactor Fault is detected. |
|
|
9 | External Interlock The External Interlock Bit will be true when an External Interlock fault is detected. |
|
|
10 | Manual Bypass Override The Manual Bypass Override Bit will be true when the Manual Bypass Override input is true. |
|
|
Table 6.5 Parameter