Trane Vertical Bypass/Non Bypass Panel Mode of Operation Select, Par. No, Selection, Function

Page 61
Mode of Operation Select

Electronically Controlled Bypass (ECB) Opera- tion

Auto bypass mode: When in drive mode, auto bypass is a timed interval that allows a fault condition in the drive to activate running the motor in bypass without operator intervention.

Mode of Operation Select

Mode of operation is programmed through parameter group 31-** . See Table 6.4.

Par. No.

Selection

Function

31-00

Bypass Mode

Selects source of motor power.

 

 

(0) Drive (drive mode) (1) Bypass (bypass

 

 

mode)

 

 

 

31-01

Bypass Start Time Delay

Sets a delay time for starting in bypass that

 

 

allows for external actions to take place prior

 

 

to line starting the motor.

 

 

 

 

 

0-60 sec. (default value is 5 sec.)

 

 

 

31-02

Bypass Trip Time Delay

Setting a value other than 0 sec. enables

 

 

auto bypass. Bypass trip delay sets the delay

 

 

time before switching to bypass mode when

 

 

the drive has a fault.

 

 

 

 

 

0-300 sec. (default is 0 sec. = OFF)

 

 

 

31-03

Test Mode Activation

Setting enabled puts bypass in test mode.

 

 

See the manual for warnings and cautions.

 

 

 

 

 

(0) disabled (default value) (1) enabled

 

 

 

31-10

Bypass Status Word

Read-only display, which shows the bypass

 

 

status in hex. See the next table for details.

 

 

 

 

 

0, 216-1 (default value is 0)

 

 

 

31-11

Bypass Running Hours

Read only display which shows bypass

 

 

running hours.

 

 

 

Table 6.4 Bypass Parameter Functions

Bit

Description

 

 

0

Test Mode The Test Mode bit will be true when the ECB is in Test Mode.

 

 

1

Drive Mode The Drive Mode bit will be true when the ECB is in Drive Mode.

 

 

2

Automatic Bypass Mode The Automatic Bypass Mode bit will be true when the ECB is in Automatic Bypass Mode.

3

Bypass Mode The Bypass Mode bit will be true when the ECB is in Bypass Mode.

4

Reserved This bit is reserved for future use.

5

Motor Running from Bypass/Drive The Motor Running from Bypass/Drive Bit will be true when the motor is running from

 

either the drive or the bypass.

6

Overload Trip The Overload Trip Bit will be true when the ECB detects an overload trip.

 

 

7

M2 Contactor Fault The Contactor Fault Bit will be true when an M2 Contactor Fault is detected.

 

 

8

M3 Contactor Fault The Contactor Fault Bit will be true when an M3 Contactor Fault is detected.

 

 

9

External Interlock The External Interlock Bit will be true when an External Interlock fault is detected.

 

 

10

Manual Bypass Override The Manual Bypass Override Bit will be true when the Manual Bypass Override input is true.

 

 

Table 6.5 Parameter 31-10 Bypass Status Word Bit Definitions

BAS-SVX49A-EN

6-9

Image 61
Contents TR200 Vertical Bypass/Non Bypass Panel Operators GuideBAS-SVX49A-EN AugustSafety Guidelines SafetyEQUIPMENT HAZARD UNINTENDED START2 Pre-installation Contents3 Installation 1 Introduction5 Electromechanical Bypass EMB2 Operation 4 Start Up6 Electronically Controlled Bypass ECB Operation 8 Appendix 7 Start Up TroubleshootingBAS-SVX49A-EN Contents1.1.1 Purpose of the Manual 1 Introduction1.1.2 Overview 1.1.3 Typical Bypass Operation1.3.1 Common Run/Stop with Bypass 1.3 Bypass Options1.3.2 Automatic Bypass 1.3.3 Run Permissive in Bypass1.5 Switch Mode Power Supply 1.4 Bypass Platform Configurations1.5.1 Control Transformer 1.6 Disconnects 1.6.1 Main DisconnectIntroduction 1.6.2 Mode Selector SwitchTable 1.3 Tier Definitions and Features 1.6.3 Panel ConfigurationsIntroduction Non bypass1.6.4 Panel Voltage and Frame Ratings 1.7Power Component Functions 1.7.1 Power FusingMain fusing Drive fusing2.1.2 Pre-installationCheck 2 Pre-installation2.1.3 Installation Site Check 2.1.1 Receiving Inspection2.2.1 Airborne Liquids 2.2Harsh Environments2.2.2 Airborne Solids 2.2.3 Corrosive Chemicals3.1.1 Tools Required 3 Installation3.1.2 Drive Fuses Installation230 V AC Installation460 V AC 600 V AC3.2.4 Shipping Weights 3.2Mechanical Installation 3.2.1 Lifting3.1.3 Internal Main Panel Fuses 3.2.3 ForkliftInstallation 3.3 CoolingFigure 3.2 Side Cooling Clearance Figure 3.1 Proper Lifting MethodProper Field Wiring and Grounding Required 3.4 Electrical InstallationHazardous Voltage INDUCED VOLTAGEFigure 3.4 Power Connections InstallationBAS-SVX49A-EN Figure 3.5 P2 Bypass Mechanical Layout Diagram InstallationTable 3.8 Reference Designator Definitions BAS-SVX49A-EN InstallationFigure 3.7 P3 Bypass Mechanical Layout Diagram InstallationBAS-SVX49A-EN 3-10 InstallationBAS-SVX49A-EN Figure 3.9 P4 Bypass Mechanical Layout Diagram InstallationBAS-SVX49A-EN 3-113-12 InstallationBAS-SVX49A-EN Figure 3.11 P5 Bypass Mechanical Layout Diagram InstallationBAS-SVX49A-EN 3-133-14 InstallationBAS-SVX49A-EN Installation 3.4.2 Wire and Cable AccessHazardous Voltage IMPORTANT NOTEFigure 3.15 P2 Panel Figure 3.16 P3 Panel Installation3-16 BAS-SVX49A-ENFigure 3.17 P4 Panel InstallationBAS-SVX49A-EN 3-17Figure 3.18 P5 Panel Installation3-18 BAS-SVX49A-ENInstallation 3.4.3 Wire Size3.4.5 Terminal Tightening Torques 3.4.4 Wire Type RatingInstallation Non Bypass InstallationBypass HP KWGround Wire Installation230 V AC Non BypassGround Wire Installation460 VAC OutputGround Wire Installation600 VAC Non Bypass3.4.6 Input Line Connection 3.4.7 Motor WiringInstallation Hazardous Voltage3.4.8 Grounding Earthing 3.4.9 Control WiringInstallation Field WiringInstallation 3.4.10Serial Communication Bus ConnectionProgramming Installation 3.4.11 Drive Control TerminalsHAZARDOUS VOLTAGE 4 Start UpStart Up 4.1.1 Inspection Prior to Start Up 4.1.2 Start Up ProcedureHAZARDOUS VOLTAGE Start UpStart Up MOTOR STARTBAS-SVX49A-EN Start UpElectromechanical Bypass EMB2 Operation 5 Electromechanical Bypass EMB2 OperationBAS-SVX49A-EN Electromechanical Bypass E5.1.3 EMB2 Common Run/Stop 5.1.2 EMB2 Auto BypassAuto Bypass Function Setup Common Run/Stop Setup5.1.5 EMB2 Overload 5.1.4 EMB2 Run PermissiveMOTOR DAMAGE Run Permissive Function Setup5.1.8 EMB2 Fault Reporting 5.1.6 EMB2 Safety Interlock5.1.7 EMB2 Fire Mode Safety Interlock Function SetupFault Reporting Function Setup 5.1.9 EMB2 SwitchesMode selector switch Electromechanical Bypass E6.1Electronically Controlled Bypass ECB Operation 6 Electronically Controlled Bypass ECB Operation6.1.1 Overview 1 2 3 4 6.1.2 ECB Control CardElectronically Controlled B BAS-SVX49A-EN Figure 6.2 ECB Control Card Terminal ConnectionsElectronically Controlled Bypass ECB Opera- tion Input Conn Electronically Controlled BTerm Function6.1.3 ECB Drive or Bypass Selection BAS-SVX49A-EN Electronically Controlled B130BX238.10 6.1.4 ECB Programming 6.1.6 ECB Mode of Operation 6.1.5 ECB Hand/OFF/AutoElectronically Controlled B General InformationPar. No Mode of Operation SelectSelection Function6.1.8 ECB Auto Bypass 6.1.7 Bypass Status Word Bit ExamplesAuto Bypass Function Setup Electronically Controlled B6.1.10 ECB Overload 6.1.9 ECB Run PermissiveRun Permissive Function Setup Disable Run Permissive6.1.12 ECB Common Run/Stop 6.1.11 ECB Safety InterlockSafety Interlock Function Setup Overload Function Setup6.1.13 ECB Advanced Fire Mode 6.1.14 ECB Fault ReportingFire Mode Function Setup Fault Reporting Function Setup6-14 Electronically Controlled BBAS-SVX49A-EN 7.1.1 Option Panel Alarm and Warnings 7 Start Up TroubleshootingStart Up Troubleshooting CodeSymptom Start Up TroubleshootingSolution Table 7.3 Fault TableSolution SymptomPossible cause TestSymptom Start Up TroubleshootingSolution Possible cause8.1.1 Dimensions 8 AppendixP2 BYPASS P3 BYPASSAppendix 8.1.2 Mechanical DiagramsFigure 8.1 P2 Bypass Figure 8.2 P2 Non-bypass AppendixBAS-SVX49A-EN BAS-SVX49A-EN AppendixFigure 8.3 P3 P4 P5 Bypass Figure 8.4 P3 P4 P5 Non-bypass AppendixBAS-SVX49A-EN Appendix 8.1.3 Typical Wiring DiagramsFigure 8.5 EMB2 with Control Relay, Part Figure 8.6 EMB2 with Control Relay, Part AppendixBAS-SVX49A-EN Figure 8.7 EMB2, Part AppendixBAS-SVX49A-EN BAS-SVX49A-EN AppendixFigure 8.8 EMB2, Part Figure 8.9 ECB, Part Appendix8-10 BAS-SVX49A-ENFigure 8.10 ECB, Part AppendixBAS-SVX49A-EN 8-11Figure 8.11 ECB with Control Relays, Part Appendix8-12 BAS-SVX49A-ENFigure 8.12 ECB with Control Relays, Part AppendixBAS-SVX49A-EN 8-13Figure 8.13 Non-bypass Appendix8-14 BAS-SVX49A-ENPage 177R0253 MG14D122 *MG14D122