Trane Vertical Bypass/Non Bypass Panel Internal Main Panel Fuses, Forklift, Shipping Weights

Page 17
3.1.3 Internal Main Panel Fuses

Installation

3.1.3 Internal Main Panel Fuses

Use only the specified fuse or an equivalent replacement for the internal main fuses. See the specifications label inside the cover of the unit for acceptable replacement main fuses. A sample of this can be seen in Table 3.6.

Fuse

 

Description

Manufacturer

Part Number/Size

F13A & C

 

Primary Transformer

Bussmann

FNQ-R-0.50

F15A, B, & C

 

Main Fuses

Bussmann

LPJ-30-SP

 

 

 

 

 

F16A, B, & C

 

Drive Fuses

Bussmann

JJS-35

 

 

 

 

 

F900, F901,F902

 

SMPS - Power Supply

Bussmann

FWH-020A6F, 500V

 

 

 

 

 

Table 3.6 Sample Fuse Rating Label

 

 

 

3.2Mechanical Installation 3.2.1 Lifting

3.2Mechanical Installation 3.2.1 LiftingHeavy Objects!WARNING

Heavy Objects!

Do not use cables (chains or slings) except as shown. Each of the cables (chains or slings) used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length.

Adjust as necessary for even unit lift. Other lifting arrangements may cause equipment or property-only damage. Failure to properly lift unit could result in death or serious injury. See details below.

3.2.3 Forklift

Only a competent lift operator with additional support personnel should attempt moving the unit.

Carefully position forklift and ensure stability prior to lift.

3.2.4 Shipping Weights

Weights listed in Table 3.7 are approximate for base units. Options can add or reduce weight of unit. Weights listed are in lbs.

3.2.3 Forklift3.2.4 Shipping WeightsWARNING

Check the weight of unit to determine the safety of the lifting method. Ensure that the lifting device is suitable for the task. If necessary, plan for a hoist, crane or forklift with appropriate rating to move the units.

Follow recommendations below. failure to do so could result in death or serious injury.

Frame

Non Bypass Panel

Bypass Panel

 

 

 

P2

36

84

 

 

 

P3

66

106

 

 

 

P4

106

167

 

 

 

P5

155

248

Table 3.7 Approximate Shipping Weights

3.2.2 Hoist or Overhead Lift

Use a solid steel spreader bar for lifting. Slide the spreader bar through the two (2) lifting holes on the panel. Lifting rings are 0.59in (15mm) in diameter (see Figure 3.1). If VFD mounting screws interfere with the spreader bar, lifting hooks can be used instead of the lifting bar.

Connect the spreader bar to a hoist or other lifting device.

Carefully lift the unit and secure it to the wall. Refer to 8 Appendix for dimensional drawings to determine fasteners size and location.

BAS-SVX49A-EN

3-3

Image 17
Contents TR200 Vertical Bypass/Non Bypass Panel Operators GuideBAS-SVX49A-EN AugustSafety Guidelines SafetyEQUIPMENT HAZARD UNINTENDED START2 Pre-installation Contents3 Installation 1 Introduction6 Electronically Controlled Bypass ECB Operation 4 Start Up5 Electromechanical Bypass EMB2 Operation 8 Appendix 7 Start Up TroubleshootingBAS-SVX49A-EN Contents1.1.1 Purpose of the Manual 1 Introduction1.1.2 Overview 1.1.3 Typical Bypass Operation1.3.1 Common Run/Stop with Bypass 1.3 Bypass Options1.3.2 Automatic Bypass 1.3.3 Run Permissive in Bypass1.5 Switch Mode Power Supply 1.4 Bypass Platform Configurations1.5.1 Control Transformer 1.6 Disconnects 1.6.1 Main DisconnectIntroduction 1.6.2 Mode Selector SwitchTable 1.3 Tier Definitions and Features 1.6.3 Panel ConfigurationsIntroduction Non bypass1.6.4 Panel Voltage and Frame Ratings 1.7Power Component Functions 1.7.1 Power FusingMain fusing Drive fusing2.1.2 Pre-installationCheck 2 Pre-installation2.1.3 Installation Site Check 2.1.1 Receiving Inspection2.2.1 Airborne Liquids 2.2Harsh Environments2.2.2 Airborne Solids 2.2.3 Corrosive Chemicals3.1.1 Tools Required 3 Installation3.1.2 Drive Fuses Installation230 V AC Installation460 V AC 600 V AC3.2.4 Shipping Weights 3.2Mechanical Installation 3.2.1 Lifting3.1.3 Internal Main Panel Fuses 3.2.3 ForkliftInstallation 3.3 CoolingFigure 3.2 Side Cooling Clearance Figure 3.1 Proper Lifting MethodProper Field Wiring and Grounding Required 3.4 Electrical InstallationHazardous Voltage INDUCED VOLTAGEBAS-SVX49A-EN InstallationFigure 3.4 Power Connections Table 3.8 Reference Designator Definitions InstallationFigure 3.5 P2 Bypass Mechanical Layout Diagram BAS-SVX49A-EN InstallationBAS-SVX49A-EN InstallationFigure 3.7 P3 Bypass Mechanical Layout Diagram BAS-SVX49A-EN Installation3-10 Figure 3.9 P4 Bypass Mechanical Layout Diagram InstallationBAS-SVX49A-EN 3-11BAS-SVX49A-EN Installation3-12 Figure 3.11 P5 Bypass Mechanical Layout Diagram InstallationBAS-SVX49A-EN 3-13BAS-SVX49A-EN Installation3-14 Installation 3.4.2 Wire and Cable AccessHazardous Voltage IMPORTANT NOTEFigure 3.15 P2 Panel Figure 3.16 P3 Panel Installation3-16 BAS-SVX49A-ENFigure 3.17 P4 Panel InstallationBAS-SVX49A-EN 3-17Figure 3.18 P5 Panel Installation3-18 BAS-SVX49A-ENInstallation 3.4.3 Wire SizeInstallation 3.4.4 Wire Type Rating3.4.5 Terminal Tightening Torques Non Bypass InstallationBypass HP KWGround Wire Installation230 V AC Non BypassGround Wire Installation460 VAC OutputGround Wire Installation600 VAC Non Bypass3.4.6 Input Line Connection 3.4.7 Motor WiringInstallation Hazardous Voltage3.4.8 Grounding Earthing 3.4.9 Control WiringInstallation Field WiringProgramming 3.4.10Serial Communication Bus ConnectionInstallation Installation 3.4.11 Drive Control TerminalsStart Up 4 Start UpHAZARDOUS VOLTAGE 4.1.1 Inspection Prior to Start Up 4.1.2 Start Up ProcedureHAZARDOUS VOLTAGE Start UpStart Up MOTOR STARTBAS-SVX49A-EN Start UpElectromechanical Bypass EMB2 Operation 5 Electromechanical Bypass EMB2 OperationBAS-SVX49A-EN Electromechanical Bypass E5.1.3 EMB2 Common Run/Stop 5.1.2 EMB2 Auto BypassAuto Bypass Function Setup Common Run/Stop Setup5.1.5 EMB2 Overload 5.1.4 EMB2 Run PermissiveMOTOR DAMAGE Run Permissive Function Setup5.1.8 EMB2 Fault Reporting 5.1.6 EMB2 Safety Interlock5.1.7 EMB2 Fire Mode Safety Interlock Function SetupFault Reporting Function Setup 5.1.9 EMB2 SwitchesMode selector switch Electromechanical Bypass E6.1.1 Overview 6 Electronically Controlled Bypass ECB Operation6.1Electronically Controlled Bypass ECB Operation Electronically Controlled B 6.1.2 ECB Control Card1 2 3 4 Electronically Controlled Bypass ECB Opera- tion Figure 6.2 ECB Control Card Terminal ConnectionsBAS-SVX49A-EN Input Conn Electronically Controlled BTerm Function6.1.3 ECB Drive or Bypass Selection 130BX238.10 Electronically Controlled BBAS-SVX49A-EN 6.1.4 ECB Programming 6.1.6 ECB Mode of Operation 6.1.5 ECB Hand/OFF/AutoElectronically Controlled B General InformationPar. No Mode of Operation SelectSelection Function6.1.8 ECB Auto Bypass 6.1.7 Bypass Status Word Bit ExamplesAuto Bypass Function Setup Electronically Controlled B6.1.10 ECB Overload 6.1.9 ECB Run PermissiveRun Permissive Function Setup Disable Run Permissive6.1.12 ECB Common Run/Stop 6.1.11 ECB Safety InterlockSafety Interlock Function Setup Overload Function Setup6.1.13 ECB Advanced Fire Mode 6.1.14 ECB Fault ReportingFire Mode Function Setup Fault Reporting Function SetupBAS-SVX49A-EN Electronically Controlled B6-14 7.1.1 Option Panel Alarm and Warnings 7 Start Up TroubleshootingStart Up Troubleshooting CodeSymptom Start Up TroubleshootingSolution Table 7.3 Fault TableSolution SymptomPossible cause TestSymptom Start Up TroubleshootingSolution Possible cause8.1.1 Dimensions 8 AppendixP2 BYPASS P3 BYPASSFigure 8.1 P2 Bypass 8.1.2 Mechanical DiagramsAppendix BAS-SVX49A-EN AppendixFigure 8.2 P2 Non-bypass Figure 8.3 P3 P4 P5 Bypass AppendixBAS-SVX49A-EN BAS-SVX49A-EN AppendixFigure 8.4 P3 P4 P5 Non-bypass Figure 8.5 EMB2 with Control Relay, Part 8.1.3 Typical Wiring DiagramsAppendix BAS-SVX49A-EN AppendixFigure 8.6 EMB2 with Control Relay, Part BAS-SVX49A-EN AppendixFigure 8.7 EMB2, Part Figure 8.8 EMB2, Part AppendixBAS-SVX49A-EN Figure 8.9 ECB, Part Appendix8-10 BAS-SVX49A-ENFigure 8.10 ECB, Part AppendixBAS-SVX49A-EN 8-11Figure 8.11 ECB with Control Relays, Part Appendix8-12 BAS-SVX49A-ENFigure 8.12 ECB with Control Relays, Part AppendixBAS-SVX49A-EN 8-13Figure 8.13 Non-bypass Appendix8-14 BAS-SVX49A-ENPage 177R0253 MG14D122 *MG14D122