Trane TR200 Bypass Status Word Bit Examples, ECB Auto Bypass, Electronically Controlled B

Page 62
6.1.7 Bypass Status Word Bit Examples

Electronically Controlled B...

6.1.7 Bypass Status Word Bit Examples

1.Motor running and bypass in drive mode. Status word 22 hexadecimal converts to 00000100010 binary.

Bit

10

9

8

7

6

5

4

3

2

1

0

Binary

0

0

0

0

0

1

0

0

0

1

0

1.External interlock fault (open) and bypass in bypass mode. Status word 208 hexadecimal converts to 01000001000 binary.

Bit

10

9

8

7

6

5

4

3

2

1

0

 

 

 

 

 

 

 

 

 

 

 

 

Binary

0

1

0

0

0

0

0

1

0

0

0

6.1.8 ECB Auto Bypass

General Information

Auto bypass allows a fault condition in the drive to activate running the motor in bypass without operator intervention. Activation of the function is through setting timer start parameters in the drive programming. Fault trip and running in bypass are reported through the drive display, digital outputs, and serial communications. In addition, the independently powered ECB card is available to report bypass status when the drive is inoperable (control card operative) through its serial communications or digital outputs.

Prior to Enabling Auto Bypass

Complete the start-up procedure to verify motor rotation direction in bypass is correct and that the system is ready in all respects for continuous full speed operation in bypass.

Operation

With the auto bypass function enabled, a fault signal from the drive activates the auto bypass timer.

If the fault clears before the time delay is complete, the motor remains operating in drive mode. This allows temporary faults, such as a momentary under or over voltage, to clear without transferring the system to bypass.

If the timer completes its cycle before the fault clears, the panel trips into bypass mode and the motor runs at constant full speed from line input voltage.

In bypass, the motor will stop:

-if the drive receives a remote stop command

-local stop ([Off]) on the keypad is pressed

-a remote start command is removed

-a safety is open

-motor overload is tripped

Once auto bypass is activated, the only way to reset the unit back to drive mode is by operator intervention. Ensure that the fault has been cleared, then press [Drive Bypass] and select drive mode.

Auto Bypass Function Setup

Enable auto bypass by changing parameters in group 31 in the drive extended menu.

31-01, Bypass start time delay. Setting the timer at anything other than 0 time activates start delay in bypass. Leave at 30 sec. default or set as desired up to 60 sec.

31-02, Bypass trip time delay. Setting the timer at anything other than 0 time activates auto bypass. Leave at 5 sec. default or set as desired up to 60 sec.

Figure 6.3 Bypass Trip Time Delay

130BX243

6-10

BAS-SVX49A-EN

Image 62
Contents BAS-SVX49A-EN Operators GuideTR200 Vertical Bypass/Non Bypass Panel AugustEQUIPMENT HAZARD SafetySafety Guidelines UNINTENDED START3 Installation Contents2 Pre-installation 1 Introduction6 Electronically Controlled Bypass ECB Operation 4 Start Up5 Electromechanical Bypass EMB2 Operation 7 Start Up Troubleshooting 8 AppendixContents BAS-SVX49A-EN1.1.2 Overview 1 Introduction1.1.1 Purpose of the Manual 1.1.3 Typical Bypass Operation1.3.2 Automatic Bypass 1.3 Bypass Options1.3.1 Common Run/Stop with Bypass 1.3.3 Run Permissive in Bypass1.5.1 Control Transformer 1.4 Bypass Platform Configurations1.5 Switch Mode Power Supply 1.6 Disconnects 1.6.1 Main Disconnect1.6.2 Mode Selector Switch IntroductionIntroduction 1.6.3 Panel ConfigurationsTable 1.3 Tier Definitions and Features Non bypassMain fusing 1.7Power Component Functions 1.7.1 Power Fusing1.6.4 Panel Voltage and Frame Ratings Drive fusing2.1.3 Installation Site Check 2 Pre-installation2.1.2 Pre-installationCheck 2.1.1 Receiving Inspection2.2.2 Airborne Solids 2.2Harsh Environments2.2.1 Airborne Liquids 2.2.3 Corrosive Chemicals3.1.2 Drive Fuses 3 Installation3.1.1 Tools Required Installation460 V AC Installation230 V AC 600 V AC3.1.3 Internal Main Panel Fuses 3.2Mechanical Installation 3.2.1 Lifting3.2.4 Shipping Weights 3.2.3 ForkliftFigure 3.2 Side Cooling Clearance 3.3 CoolingInstallation Figure 3.1 Proper Lifting MethodHazardous Voltage 3.4 Electrical InstallationProper Field Wiring and Grounding Required INDUCED VOLTAGEBAS-SVX49A-EN InstallationFigure 3.4 Power Connections Table 3.8 Reference Designator Definitions InstallationFigure 3.5 P2 Bypass Mechanical Layout Diagram Installation BAS-SVX49A-ENBAS-SVX49A-EN InstallationFigure 3.7 P3 Bypass Mechanical Layout Diagram BAS-SVX49A-EN Installation3-10 BAS-SVX49A-EN InstallationFigure 3.9 P4 Bypass Mechanical Layout Diagram 3-11BAS-SVX49A-EN Installation3-12 BAS-SVX49A-EN InstallationFigure 3.11 P5 Bypass Mechanical Layout Diagram 3-13BAS-SVX49A-EN Installation3-14 Hazardous Voltage 3.4.2 Wire and Cable AccessInstallation IMPORTANT NOTE3-16 InstallationFigure 3.15 P2 Panel Figure 3.16 P3 Panel BAS-SVX49A-ENBAS-SVX49A-EN InstallationFigure 3.17 P4 Panel 3-173-18 InstallationFigure 3.18 P5 Panel BAS-SVX49A-EN3.4.3 Wire Size InstallationInstallation 3.4.4 Wire Type Rating3.4.5 Terminal Tightening Torques Bypass InstallationNon Bypass HP KW230 V AC InstallationGround Wire Non Bypass460 VAC InstallationGround Wire Output600 VAC InstallationGround Wire Non BypassInstallation 3.4.7 Motor Wiring3.4.6 Input Line Connection Hazardous VoltageInstallation 3.4.9 Control Wiring3.4.8 Grounding Earthing Field WiringProgramming 3.4.10Serial Communication Bus ConnectionInstallation 3.4.11 Drive Control Terminals InstallationStart Up 4 Start UpHAZARDOUS VOLTAGE HAZARDOUS VOLTAGE 4.1.2 Start Up Procedure4.1.1 Inspection Prior to Start Up Start UpMOTOR START Start UpStart Up BAS-SVX49A-EN5 Electromechanical Bypass EMB2 Operation Electromechanical Bypass EMB2 OperationElectromechanical Bypass E BAS-SVX49A-ENAuto Bypass Function Setup 5.1.2 EMB2 Auto Bypass5.1.3 EMB2 Common Run/Stop Common Run/Stop SetupMOTOR DAMAGE 5.1.4 EMB2 Run Permissive5.1.5 EMB2 Overload Run Permissive Function Setup5.1.7 EMB2 Fire Mode 5.1.6 EMB2 Safety Interlock5.1.8 EMB2 Fault Reporting Safety Interlock Function SetupMode selector switch 5.1.9 EMB2 SwitchesFault Reporting Function Setup Electromechanical Bypass E6.1.1 Overview 6 Electronically Controlled Bypass ECB Operation6.1Electronically Controlled Bypass ECB Operation Electronically Controlled B 6.1.2 ECB Control Card1 2 3 4 Electronically Controlled Bypass ECB Opera- tion Figure 6.2 ECB Control Card Terminal ConnectionsBAS-SVX49A-EN Term Electronically Controlled BInput Conn Function6.1.3 ECB Drive or Bypass Selection 130BX238.10 Electronically Controlled BBAS-SVX49A-EN 6.1.4 ECB Programming Electronically Controlled B 6.1.5 ECB Hand/OFF/Auto6.1.6 ECB Mode of Operation General InformationSelection Mode of Operation SelectPar. No FunctionAuto Bypass Function Setup 6.1.7 Bypass Status Word Bit Examples6.1.8 ECB Auto Bypass Electronically Controlled BRun Permissive Function Setup 6.1.9 ECB Run Permissive6.1.10 ECB Overload Disable Run PermissiveSafety Interlock Function Setup 6.1.11 ECB Safety Interlock6.1.12 ECB Common Run/Stop Overload Function SetupFire Mode Function Setup 6.1.14 ECB Fault Reporting6.1.13 ECB Advanced Fire Mode Fault Reporting Function SetupBAS-SVX49A-EN Electronically Controlled B6-14 Start Up Troubleshooting 7 Start Up Troubleshooting7.1.1 Option Panel Alarm and Warnings CodeSolution Start Up TroubleshootingSymptom Table 7.3 Fault TablePossible cause SymptomSolution TestSolution Start Up TroubleshootingSymptom Possible causeP2 BYPASS 8 Appendix8.1.1 Dimensions P3 BYPASSFigure 8.1 P2 Bypass 8.1.2 Mechanical DiagramsAppendix BAS-SVX49A-EN AppendixFigure 8.2 P2 Non-bypass Figure 8.3 P3 P4 P5 Bypass AppendixBAS-SVX49A-EN BAS-SVX49A-EN AppendixFigure 8.4 P3 P4 P5 Non-bypass Figure 8.5 EMB2 with Control Relay, Part 8.1.3 Typical Wiring DiagramsAppendix BAS-SVX49A-EN AppendixFigure 8.6 EMB2 with Control Relay, Part BAS-SVX49A-EN AppendixFigure 8.7 EMB2, Part Figure 8.8 EMB2, Part AppendixBAS-SVX49A-EN 8-10 AppendixFigure 8.9 ECB, Part BAS-SVX49A-ENBAS-SVX49A-EN AppendixFigure 8.10 ECB, Part 8-118-12 AppendixFigure 8.11 ECB with Control Relays, Part BAS-SVX49A-ENBAS-SVX49A-EN AppendixFigure 8.12 ECB with Control Relays, Part 8-138-14 AppendixFigure 8.13 Non-bypass BAS-SVX49A-ENPage MG14D122 *MG14D122 177R0253
Related manuals
Manual 56 pages 40.28 Kb