Trane Vertical Bypass/Non Bypass Panel Start Up Troubleshooting, Option Panel Alarm and Warnings

Page 67
Start Up Troubleshooting

Start Up Troubleshooting

7 Start Up Troubleshooting

7.1.1 Option Panel Alarm and Warnings

Code

Title
Definition

Number

 

 

 

 

 

220

Overload Trip

Motor overload has tripped. Indicates excess motor load. Check motor and driven load. To reset,

 

 

press [Off Reset]. Then, to restart the system, press [Auto on] or [Hand on].

 

 

 

221

Bypass Interlock

Bypass interlock has opened and caused the motor to stop. Correct the problem. Depending on

 

 

the setting of parameter 14-20, the system will either automatically reset this alarm or require the

 

 

[Off Reset] key to be pressed.

 

 

 

222

M2 Open Failed

ECB: The contactor that connects the drive to the motor failed to open. The motor can not be

 

 

operated.

 

 

 

223

M2 Close Failed

ECB: The contactor that connects the drive to the motor failed to close. The motor can not be

 

 

operated.

 

 

 

224

M3 Open Failed

ECB: The contactor that connects the motor to the power line has failed to open.

 

 

 

226

M3 Close Failed

ECB: The contactor that connects the motor to the power line has failed to close. The motor can

 

 

not be operated.

 

 

 

227

Bypass Com Error

Communication between the main control card and the bypass option has been lost. Motor control

 

 

lost. It will be possible to run the motor using Manual Bypass Override.

 

 

 

228

APU Low Voltage

The Option Panel Power Supply has failed, or there is a power problem.

 

 

 

229

Motor Disconn.

Terminal 3 on connector X57 of the ECB control card shows an open. This generally means that

 

 

neither motor has been selected in contactor motor select. Select a motor.

Table 7.1 Option Panel Alarms and Warnings (ECB only)

DisplayText

Definition

Bypass Run Starts in:

Indicates the number of sec. until the motor will be started in bypass. This time delay

 

can be adjusted using parameter 31-01.

Bypass Activates in:

Indicates the number of sec. left until the system automatically activates Bypass Mode.

 

Time delay can be adjusted using parameter 31-02.

Table 7.2 Option Panel Status Display (ECB only)

 

BAS-SVX49A-EN

7-1

Image 67
Contents August Operators GuideTR200 Vertical Bypass/Non Bypass Panel BAS-SVX49A-ENUNINTENDED START SafetySafety Guidelines EQUIPMENT HAZARD1 Introduction Contents2 Pre-installation 3 Installation5 Electromechanical Bypass EMB2 Operation 4 Start Up6 Electronically Controlled Bypass ECB Operation 8 Appendix 7 Start Up TroubleshootingBAS-SVX49A-EN Contents1.1.3 Typical Bypass Operation 1 Introduction1.1.1 Purpose of the Manual 1.1.2 Overview1.3.3 Run Permissive in Bypass 1.3 Bypass Options1.3.1 Common Run/Stop with Bypass 1.3.2 Automatic Bypass1.6 Disconnects 1.6.1 Main Disconnect 1.4 Bypass Platform Configurations1.5 Switch Mode Power Supply 1.5.1 Control TransformerIntroduction 1.6.2 Mode Selector SwitchNon bypass 1.6.3 Panel ConfigurationsTable 1.3 Tier Definitions and Features IntroductionDrive fusing 1.7Power Component Functions 1.7.1 Power Fusing1.6.4 Panel Voltage and Frame Ratings Main fusing2.1.1 Receiving Inspection 2 Pre-installation2.1.2 Pre-installationCheck 2.1.3 Installation Site Check2.2.3 Corrosive Chemicals 2.2Harsh Environments2.2.1 Airborne Liquids 2.2.2 Airborne SolidsInstallation 3 Installation3.1.1 Tools Required 3.1.2 Drive Fuses600 V AC Installation230 V AC 460 V AC3.2.3 Forklift 3.2Mechanical Installation 3.2.1 Lifting3.2.4 Shipping Weights 3.1.3 Internal Main Panel FusesFigure 3.1 Proper Lifting Method 3.3 CoolingInstallation Figure 3.2 Side Cooling ClearanceINDUCED VOLTAGE 3.4 Electrical InstallationProper Field Wiring and Grounding Required Hazardous VoltageFigure 3.4 Power Connections InstallationBAS-SVX49A-EN Figure 3.5 P2 Bypass Mechanical Layout Diagram InstallationTable 3.8 Reference Designator Definitions BAS-SVX49A-EN InstallationFigure 3.7 P3 Bypass Mechanical Layout Diagram InstallationBAS-SVX49A-EN 3-10 InstallationBAS-SVX49A-EN 3-11 InstallationFigure 3.9 P4 Bypass Mechanical Layout Diagram BAS-SVX49A-EN3-12 InstallationBAS-SVX49A-EN 3-13 InstallationFigure 3.11 P5 Bypass Mechanical Layout Diagram BAS-SVX49A-EN3-14 InstallationBAS-SVX49A-EN IMPORTANT NOTE 3.4.2 Wire and Cable AccessInstallation Hazardous VoltageBAS-SVX49A-EN InstallationFigure 3.15 P2 Panel Figure 3.16 P3 Panel 3-163-17 InstallationFigure 3.17 P4 Panel BAS-SVX49A-ENBAS-SVX49A-EN InstallationFigure 3.18 P5 Panel 3-18Installation 3.4.3 Wire Size3.4.5 Terminal Tightening Torques 3.4.4 Wire Type RatingInstallation HP KW InstallationNon Bypass BypassNon Bypass InstallationGround Wire 230 V ACOutput InstallationGround Wire 460 VACNon Bypass InstallationGround Wire 600 VACHazardous Voltage 3.4.7 Motor Wiring3.4.6 Input Line Connection InstallationField Wiring 3.4.9 Control Wiring3.4.8 Grounding Earthing InstallationInstallation 3.4.10Serial Communication Bus ConnectionProgramming Installation 3.4.11 Drive Control TerminalsHAZARDOUS VOLTAGE 4 Start UpStart Up Start Up 4.1.2 Start Up Procedure4.1.1 Inspection Prior to Start Up HAZARDOUS VOLTAGEStart Up MOTOR STARTBAS-SVX49A-EN Start UpElectromechanical Bypass EMB2 Operation 5 Electromechanical Bypass EMB2 OperationBAS-SVX49A-EN Electromechanical Bypass ECommon Run/Stop Setup 5.1.2 EMB2 Auto Bypass5.1.3 EMB2 Common Run/Stop Auto Bypass Function SetupRun Permissive Function Setup 5.1.4 EMB2 Run Permissive5.1.5 EMB2 Overload MOTOR DAMAGESafety Interlock Function Setup 5.1.6 EMB2 Safety Interlock5.1.8 EMB2 Fault Reporting 5.1.7 EMB2 Fire ModeElectromechanical Bypass E 5.1.9 EMB2 SwitchesFault Reporting Function Setup Mode selector switch6.1Electronically Controlled Bypass ECB Operation 6 Electronically Controlled Bypass ECB Operation6.1.1 Overview 1 2 3 4 6.1.2 ECB Control CardElectronically Controlled B BAS-SVX49A-EN Figure 6.2 ECB Control Card Terminal ConnectionsElectronically Controlled Bypass ECB Opera- tion Function Electronically Controlled BInput Conn Term6.1.3 ECB Drive or Bypass Selection BAS-SVX49A-EN Electronically Controlled B130BX238.10 6.1.4 ECB Programming General Information 6.1.5 ECB Hand/OFF/Auto6.1.6 ECB Mode of Operation Electronically Controlled BFunction Mode of Operation SelectPar. No SelectionElectronically Controlled B 6.1.7 Bypass Status Word Bit Examples6.1.8 ECB Auto Bypass Auto Bypass Function SetupDisable Run Permissive 6.1.9 ECB Run Permissive6.1.10 ECB Overload Run Permissive Function SetupOverload Function Setup 6.1.11 ECB Safety Interlock6.1.12 ECB Common Run/Stop Safety Interlock Function SetupFault Reporting Function Setup 6.1.14 ECB Fault Reporting6.1.13 ECB Advanced Fire Mode Fire Mode Function Setup6-14 Electronically Controlled BBAS-SVX49A-EN Code 7 Start Up Troubleshooting7.1.1 Option Panel Alarm and Warnings Start Up TroubleshootingTable 7.3 Fault Table Start Up TroubleshootingSymptom SolutionTest SymptomSolution Possible causePossible cause Start Up TroubleshootingSymptom SolutionP3 BYPASS 8 Appendix8.1.1 Dimensions P2 BYPASSAppendix 8.1.2 Mechanical DiagramsFigure 8.1 P2 Bypass Figure 8.2 P2 Non-bypass AppendixBAS-SVX49A-EN BAS-SVX49A-EN AppendixFigure 8.3 P3 P4 P5 Bypass Figure 8.4 P3 P4 P5 Non-bypass AppendixBAS-SVX49A-EN Appendix 8.1.3 Typical Wiring DiagramsFigure 8.5 EMB2 with Control Relay, Part Figure 8.6 EMB2 with Control Relay, Part AppendixBAS-SVX49A-EN Figure 8.7 EMB2, Part AppendixBAS-SVX49A-EN BAS-SVX49A-EN AppendixFigure 8.8 EMB2, Part BAS-SVX49A-EN AppendixFigure 8.9 ECB, Part 8-108-11 AppendixFigure 8.10 ECB, Part BAS-SVX49A-ENBAS-SVX49A-EN AppendixFigure 8.11 ECB with Control Relays, Part 8-128-13 AppendixFigure 8.12 ECB with Control Relays, Part BAS-SVX49A-ENBAS-SVX49A-EN AppendixFigure 8.13 Non-bypass 8-14Page 177R0253 MG14D122 *MG14D122
Related manuals
Manual 56 pages 40.28 Kb