Trane Vertical Bypass/Non Bypass Panel ECB Run Permissive, ECB Overload, Motor Damage, Operation

Page 63
6.1.9 ECB Run Permissive

Electronically Controlled Bypass (ECB) Opera- tion

Figure 6.4 Drive Display with Bypass Start Time Delay Active

6.1.9 ECB Run Permissive

General Information

With run permissive active, the drive sends a run request and waits for a remote response before notifying the motor to start. The response indicates the system is safe to operate. Run permissive operates from the keypad hand/off/auto select in drive or bypass mode. Run permissive is enabled by programming in the drive parameters.

Prior to Enabling Run Permissive

Complete the start-up procedure to verify motor rotation direction in bypass is correct and that the system is ready in all respects for continuous full speed operation in bypass.

Verify that the drive is programmed for the run permissive function. See the drive support materials for programming the run permissive function.

Operation

A start command can be initiated from local hand start, serial communications, or a remote auto start signal through digital drive input terminals.

In response to the start command, an output request is sent from the programmable drive relay to the external equipment (to activate a valve or damper, for example).

When a return run signal on the digital input is received, the motor is started in either drive or bypass, depending upon which mode is active.

130BX244.10

 

programming and wiring to the drive control

 

Run Permissive Function Setup

 

See the drive manual or support materials for

 

 

terminals.

 

Wire the output run request to the drive output

 

 

terminals selected, and program the terminals for

 

 

run request.

 

Wire the input run command to the drive input

 

 

terminals selected, and program the terminals for

 

 

run permissive.

Disable Run Permissive

Disable run permissive through the drive parameters and terminal programming.

6.1.10 ECB Overload

General Information

An overload device provides overcurrent protection for the motor when running in bypass. The thermally activated overload monitors motor current and trips to remove power to the motor if a sustained overcurrent condition exists. A Class 20 overload is standard with a variable setting for motor current. Test and reset buttons are also provided. In drive mode, the drive provides current sensing and trip protection. Fuses provide quick action for high over current conditions.

Prior to Enabling Overload

Verify that the overload current dial setting matches the motor FLA rating on the motor nameplate.

If the motor FLA is greater or less than the range of the current dial, reconfirm that the motor HP and voltage are within the option panel (and drive) rating. If greater than the FLA rating, replace the panel with one of a proper rating.

CAUTION

MOTOR DAMAGE!

Repeated attempts to reset overload can cause motor damage. Correct the overload condition and let the overload and motor return to normal operating temperature before resetting. See motor manufacturer’s recommendations for time between start attempts. Failure to correct the overload condition and let the motor return to normal operating temperature could cause motor damage.

BAS-SVX49A-EN

6-11

Image 63
Contents August Operators GuideTR200 Vertical Bypass/Non Bypass Panel BAS-SVX49A-ENUNINTENDED START SafetySafety Guidelines EQUIPMENT HAZARD1 Introduction Contents2 Pre-installation 3 Installation4 Start Up 5 Electromechanical Bypass EMB2 Operation6 Electronically Controlled Bypass ECB Operation 8 Appendix 7 Start Up TroubleshootingBAS-SVX49A-EN Contents1.1.3 Typical Bypass Operation 1 Introduction1.1.1 Purpose of the Manual 1.1.2 Overview1.3.3 Run Permissive in Bypass 1.3 Bypass Options1.3.1 Common Run/Stop with Bypass 1.3.2 Automatic Bypass1.6 Disconnects 1.6.1 Main Disconnect 1.4 Bypass Platform Configurations1.5 Switch Mode Power Supply 1.5.1 Control TransformerIntroduction 1.6.2 Mode Selector SwitchNon bypass 1.6.3 Panel ConfigurationsTable 1.3 Tier Definitions and Features IntroductionDrive fusing 1.7Power Component Functions 1.7.1 Power Fusing1.6.4 Panel Voltage and Frame Ratings Main fusing2.1.1 Receiving Inspection 2 Pre-installation2.1.2 Pre-installationCheck 2.1.3 Installation Site Check2.2.3 Corrosive Chemicals 2.2Harsh Environments2.2.1 Airborne Liquids 2.2.2 Airborne SolidsInstallation 3 Installation3.1.1 Tools Required 3.1.2 Drive Fuses600 V AC Installation230 V AC 460 V AC3.2.3 Forklift 3.2Mechanical Installation 3.2.1 Lifting3.2.4 Shipping Weights 3.1.3 Internal Main Panel FusesFigure 3.1 Proper Lifting Method 3.3 CoolingInstallation Figure 3.2 Side Cooling ClearanceINDUCED VOLTAGE 3.4 Electrical InstallationProper Field Wiring and Grounding Required Hazardous VoltageInstallation Figure 3.4 Power ConnectionsBAS-SVX49A-EN Installation Figure 3.5 P2 Bypass Mechanical Layout DiagramTable 3.8 Reference Designator Definitions BAS-SVX49A-EN InstallationInstallation Figure 3.7 P3 Bypass Mechanical Layout DiagramBAS-SVX49A-EN Installation 3-10BAS-SVX49A-EN 3-11 InstallationFigure 3.9 P4 Bypass Mechanical Layout Diagram BAS-SVX49A-ENInstallation 3-12BAS-SVX49A-EN 3-13 InstallationFigure 3.11 P5 Bypass Mechanical Layout Diagram BAS-SVX49A-ENInstallation 3-14BAS-SVX49A-EN IMPORTANT NOTE 3.4.2 Wire and Cable AccessInstallation Hazardous VoltageBAS-SVX49A-EN InstallationFigure 3.15 P2 Panel Figure 3.16 P3 Panel 3-163-17 InstallationFigure 3.17 P4 Panel BAS-SVX49A-ENBAS-SVX49A-EN InstallationFigure 3.18 P5 Panel 3-18Installation 3.4.3 Wire Size3.4.4 Wire Type Rating 3.4.5 Terminal Tightening TorquesInstallation HP KW InstallationNon Bypass BypassNon Bypass InstallationGround Wire 230 V ACOutput InstallationGround Wire 460 VACNon Bypass InstallationGround Wire 600 VACHazardous Voltage 3.4.7 Motor Wiring3.4.6 Input Line Connection InstallationField Wiring 3.4.9 Control Wiring3.4.8 Grounding Earthing Installation3.4.10Serial Communication Bus Connection InstallationProgramming Installation 3.4.11 Drive Control Terminals4 Start Up HAZARDOUS VOLTAGEStart Up Start Up 4.1.2 Start Up Procedure4.1.1 Inspection Prior to Start Up HAZARDOUS VOLTAGEStart Up MOTOR STARTBAS-SVX49A-EN Start UpElectromechanical Bypass EMB2 Operation 5 Electromechanical Bypass EMB2 OperationBAS-SVX49A-EN Electromechanical Bypass ECommon Run/Stop Setup 5.1.2 EMB2 Auto Bypass5.1.3 EMB2 Common Run/Stop Auto Bypass Function SetupRun Permissive Function Setup 5.1.4 EMB2 Run Permissive5.1.5 EMB2 Overload MOTOR DAMAGESafety Interlock Function Setup 5.1.6 EMB2 Safety Interlock5.1.8 EMB2 Fault Reporting 5.1.7 EMB2 Fire ModeElectromechanical Bypass E 5.1.9 EMB2 SwitchesFault Reporting Function Setup Mode selector switch6 Electronically Controlled Bypass ECB Operation 6.1Electronically Controlled Bypass ECB Operation6.1.1 Overview 6.1.2 ECB Control Card 1 2 3 4Electronically Controlled B Figure 6.2 ECB Control Card Terminal Connections BAS-SVX49A-ENElectronically Controlled Bypass ECB Opera- tion Function Electronically Controlled BInput Conn Term6.1.3 ECB Drive or Bypass Selection Electronically Controlled B BAS-SVX49A-EN130BX238.10 6.1.4 ECB Programming General Information 6.1.5 ECB Hand/OFF/Auto6.1.6 ECB Mode of Operation Electronically Controlled BFunction Mode of Operation SelectPar. No SelectionElectronically Controlled B 6.1.7 Bypass Status Word Bit Examples6.1.8 ECB Auto Bypass Auto Bypass Function SetupDisable Run Permissive 6.1.9 ECB Run Permissive6.1.10 ECB Overload Run Permissive Function SetupOverload Function Setup 6.1.11 ECB Safety Interlock6.1.12 ECB Common Run/Stop Safety Interlock Function SetupFault Reporting Function Setup 6.1.14 ECB Fault Reporting6.1.13 ECB Advanced Fire Mode Fire Mode Function SetupElectronically Controlled B 6-14BAS-SVX49A-EN Code 7 Start Up Troubleshooting7.1.1 Option Panel Alarm and Warnings Start Up TroubleshootingTable 7.3 Fault Table Start Up TroubleshootingSymptom SolutionTest SymptomSolution Possible causePossible cause Start Up TroubleshootingSymptom SolutionP3 BYPASS 8 Appendix8.1.1 Dimensions P2 BYPASS8.1.2 Mechanical Diagrams AppendixFigure 8.1 P2 Bypass Appendix Figure 8.2 P2 Non-bypassBAS-SVX49A-EN Appendix BAS-SVX49A-ENFigure 8.3 P3 P4 P5 Bypass Appendix Figure 8.4 P3 P4 P5 Non-bypassBAS-SVX49A-EN 8.1.3 Typical Wiring Diagrams AppendixFigure 8.5 EMB2 with Control Relay, Part Appendix Figure 8.6 EMB2 with Control Relay, PartBAS-SVX49A-EN Appendix Figure 8.7 EMB2, PartBAS-SVX49A-EN Appendix BAS-SVX49A-ENFigure 8.8 EMB2, Part BAS-SVX49A-EN AppendixFigure 8.9 ECB, Part 8-108-11 AppendixFigure 8.10 ECB, Part BAS-SVX49A-ENBAS-SVX49A-EN AppendixFigure 8.11 ECB with Control Relays, Part 8-128-13 AppendixFigure 8.12 ECB with Control Relays, Part BAS-SVX49A-ENBAS-SVX49A-EN AppendixFigure 8.13 Non-bypass 8-14Page 177R0253 MG14D122 *MG14D122
Related manuals
Manual 56 pages 40.28 Kb