FireplaceXtrordinair 36CF installation manual Hearth Requirements Recessed Hearth

Page 32

32

Installation (for qualified installers only)

Hearth Requirements – Recessed Hearth

A hearth is not required if the fireplace is raised 6” above the flooring surface. NOTE: Make sure to accommodate the flooring surface - this distance must be measured from the top of carpeting or other flooring material.

WARNING:

We recommend a hearth to protect the flooring surface from discoloration or other negative impact from the heater, especially if it is near the minimum raised height.

Min. 6”

Side View

Minimum 6” to top of flooring surface (carpet, etc.)

Carpet

Fireplace

 

 

1”

Cement Board

 

 

Plywood (OSB, etc.)

NOTE: When building a raised fireplace, consider the facing

 

 

 

material below the fireplace. If using tile, you may wish to

Framing

 

make the platform a suitable height for un-cut tile. For

Sub-Floor

 

example, if using 12” tile, make the platform 11” tall (10-1/2”

 

section of framing + 1/2” plywood).

 

 

Figure 21

© Travis Industries

4090102

100-01212_000

Image 32
Contents CF ST/Pier Gas Fireplace 2Introduction Overview Listing DetailsTable of Contents Safety Precautions Safety WarningsSafety Precautions Features and Specifications Installation OptionsSpecifications DimensionsAdditional Items Required Recommended Installation ProcedurePacking List Massachusetts Requirements Preparing the Fireplace Stand-offs Raised Fireplaces Fireplace Placement RequirementsClearances Minimum Framing 36 CF ST See Through BackFraming Dimensions 36 CF Pier FrontAttaching Stand-Offs to Framing Required Electrical Connection Battery Pack / Learn Switch Installation Do not route the wires over the top FireplaceBattery Installation Steps for Installing the Battery Box and Learn SwitchInstallation Warning Remote Synchronization Remote Synchronization Synchronizing the RemoteGas Inlet Pressure Gas Line RequirementsGas Line Connection Vent Installation Vent RequirementsApproved Vent Altitude ConsiderationsVent Clearances Vent LocationApproved Vent Configurations Exhaust Restrictor AdjustmentApproved Vent Configuration Rear Vent, Horz. Term 45 Elbow 0feet Max 5feetFeet max 0feet 5feet 10feet 15feet 20max Max 0feet 5feet 10feet 15feet 20max Feet Max Feet max 0feet 5feet 10feet 15feet 20max Installation for qualified installers only 0feet 5feet Feet max 10feet 15feet 40feet max Feet 5feet 10feet 15feet 20max Max 40feet max Feet 5feet 10feet 15feet Termination Requirements Hearth Requirements Flush HearthHearth Requirements Recessed Hearth Facing Requirements Non-Combustible Facing Mantel Requirements See ThroughFinalizing the Installation for qualified installers only Steps for Finalizing the InstallationFinalizing the Installation for qualified installers only Air Shutter AdjustmentGlass Frame Removal and Installation Glass Frame Glass TrimRock Wool Placement Log Set InstallationEmber Placement Log Installation Top 2 logs last 2 logs Picture from opposite side Picture from end Pier only LP Conversion Instructions Finalizing the Installation for qualified installers only Orifice Table Rate Screws Power Heat Duct Installation Andiron Installation48Index