FireplaceXtrordinair 36CF installation manual Non-Combustible Facing

Page 34

34

Installation (for qualified installers only)

Non-Combustible Facing

Non-combustible facing on the front of the fireplace must extend a minimum 16-1/2” from the top of the glass frame (49-1/2” from the base of the fireplace). Above 16-1/2” combustible facing may be used (see “Mantel Requirements” on the following page for more details).

Non-combustible facing on the front of the fireplace must extend a minimum 2” to each side of the glass frame. Beyond 2” combustible facing may be used, but may not protrude more than 4” (see “Mantel Requirements” on the following page for more details).

The maximum depth for non-combustible facing is 6” (includes the fiber board)

Combustible Material

(drywall, etc.

Fiber Board (required)

16-1/2”” Min.

Non-Combustible Facing (tile, rock, marble, etc.)

Fireplace

Glass Frame

Figure 23

© Travis Industries

4090102

100-01212_000

Image 34
Contents CF ST/Pier Gas Fireplace 2Introduction Overview Listing DetailsTable of Contents Safety Precautions Safety WarningsSafety Precautions Specifications Features and SpecificationsInstallation Options DimensionsPacking List Recommended Installation ProcedureAdditional Items Required Massachusetts Requirements Preparing the Fireplace Stand-offs Clearances Fireplace Placement RequirementsRaised Fireplaces Minimum Framing 36 CF ST See Through BackFraming Dimensions 36 CF Pier FrontAttaching Stand-Offs to Framing Required Electrical Connection Battery Pack / Learn Switch Installation Do not route the wires over the top FireplaceInstallation Warning Remote Synchronization Steps for Installing the Battery Box and Learn SwitchBattery Installation Remote Synchronization Synchronizing the RemoteGas Line Connection Gas Line RequirementsGas Inlet Pressure Approved Vent Vent InstallationVent Requirements Altitude ConsiderationsVent Clearances Vent LocationApproved Vent Configurations Exhaust Restrictor AdjustmentApproved Vent Configuration Rear Vent, Horz. Term 45 Elbow 0feet Max 5feetFeet max 0feet 5feet 10feet 15feet 20max Max 0feet 5feet 10feet 15feet 20max Feet Max Feet max 0feet 5feet 10feet 15feet 20max Installation for qualified installers only 0feet 5feet Feet max 10feet 15feet 40feet max Feet 5feet 10feet 15feet 20max Max 40feet max Feet 5feet 10feet 15feet Termination Requirements Hearth Requirements Flush HearthHearth Requirements Recessed Hearth Facing Requirements Non-Combustible Facing Mantel Requirements See ThroughFinalizing the Installation for qualified installers only Steps for Finalizing the InstallationFinalizing the Installation for qualified installers only Air Shutter AdjustmentGlass Frame Removal and Installation Glass Frame Glass TrimEmber Placement Log Set InstallationRock Wool Placement Log Installation Top 2 logs last 2 logs Picture from opposite side Picture from end Pier only LP Conversion Instructions Finalizing the Installation for qualified installers only Orifice Table Rate Screws Power Heat Duct Installation Andiron Installation48Index