Burnham K50 manual Proceed to Paragraph 15- Minimum Input

Page 59

burners on the unaffected side would ignite on a “call for heat” and would continue to operate until the operating control was satisfied.

The EE Control System utilizes and RA890F Protectorelay and a Q179C Rectification Pilot, which in addition to a pilot burner and rectifying flame rod flame detector to prove pilot, includes an ignition electrode for spark ignition of the pilot. A Webster

612-6A7 Transformer supplies the high voltage spark potential. Once pilot flame is proven, ignition stops but pilot flame continues as long as there is a “call for heat” (intermittent electrically ignited pilot).

The RA890F Protectorelay Primary Control is a non-programming amplifying relay which when used with the Q179C Pilot provides solid state electronic Flame Safeguard Protection that will not allow the main gas valves to open on “call for heat” or that will shut down main burners within 0.8 second if pilot flame is not “proved”. Protectorelay will lock out on safety shutdown within 15 seconds if there is a pilot flame failure on start or, if during the “run” cycle, pilot flame is not re-established. Since #3 terminal in the Protectorelay is de-energized at end of safety switch timing, a solenoid valve in the pilot line will close and thus 100% shut-off is achieved.

a. OPERATING INSTRUCTIONS

(1)Make sure all Manual Main Shut-off Valves and all Pilot Valves have been off for at least five

minutes.

(2)Set Operating and Limit Controls to desired settings.

(3)Turn all Manual Main Shut-off Valves and Pilot Valves to Open Position.

(4)Turn on Main Electric Switch and Service Switch. Pilots will automatically light main burners.

Proceed to Paragraph 15- Minimum Input

Adjustments (for diaphragm “Lo-Hi-Lo” or motorized type gas valves)

SEQUENCE OF OPERATION EE – See Fig. 50

a.NORMAL OPERATION – 5015B thru 5026B

1.When the operating control calls for heat, terminal #6 of each RA890F Protectorelay is energized.

2.A component check circuit in each RA890F Protectorelay is activated which checks the electronic network of the relay.

3.Terminals #3 and #4 of each RA890F relay are energized. Terminal #3 opens the pilot line solenoid valve supplying gas to the Q179C pilot. Terminal #4 energizes ignition transformer creating electric spark ignition at the Q179C pilot.

4.Flame rod circuit between each Q179C pilot and terminal “F” on its respective RA890F proves

presence of flame electronically at its Q179C pilot.

5.Terminal #4 of each RA890F and the ignition transformer connected to it is de-energized.

6.Terminal #5 on each RA890F is energized supplying power to its respective main gas valves.

7.Main gas valves open and main burners are ignited by the pilot flames.

8.When the operating control is satisfied, terminals

6 and all other terminals on both RA890F relays are de-energized. The main gas valves and pilot valve for each gas train are closed and main burners and pilot burner flames are extinguished.

b. SAFETY SHUTDOWN

1.SAFETY SWITCH CIRCUIT

If limit control, low water cut-off or any other electrical safety switch opens, power to terminal 6 and all other terminals on both RA890 Relays is interrupted de-energizing the main gas valves and pilot valves and the main gas burners and pilot burners are immediately extinguished. Normal operation can be resumed when the cause of the safety switch malfunction is corrected. Make sure all manual resets are activated where applicable.

2.PILOT FAILURE

(a)Pilot failure can occur during the start and operating cycle of the boiler. Any pilot failure on either of the Q179C Electronic

Pilots, after ignition of pilot flame will close the pilot valve and the main gas valves controlled by that particular RA890F relay in 0.8 second. The burners controlled by the other RA890F will continue to burn.

(b)For 15 seconds after failure of a Q179C pilot, the relay through terminals #3 and #4 will attempt to re-establish pilot flame. If no pilot flame can be sensed by the flame rod circuit in 15 seconds, terminals #3 and #4 are de-energized, and the relay will lock out on safety.

(c)Pilot failure is caused by the following:

(1)Complete loss of gas supply.

(2)Poor ignition spark caused by low voltage, poor ground connection, faulty wiring, and possibly a defective ignition transformer.

(3)Low gas pressure will prevent flame rod circuit from sensing pilot flame properly.

(4)Unusually strong secondary air drafts can blow the pilot flame away from the flame rod momentarily causing nuisance shutdown.

(5)A pilot line solenoid valve will not open

because of faulty wiring, low voltage, or

possibly the valve is defective.

59

 

Image 59
Contents Series 5B Section I Equipment Check List Important Information Canadian Equipment Check List Canadian Equipment Check List Natural GAS Maximum 14 W.C. Minimum 5.5 W.C Dimensional DataProvide Combustion and Ventilation AIR Do not Install this Boiler on CarpetingSingle Manifold Base 5006B Thru 5014B Section Boilers BASE-BURNER-MANIFOLD AssemblysDual Manifold Bases 5015B Thru 5026B Section Boilers LEH Section on Base Assembly of Center SectionsArrangement of Sections and Canopys Purpose of Tappings and Their Locations Open Steam or Water Trim CartonConnect Supply and Return Piping to Heating System Installation of BUILT-IN HeaterTesting Boiler Assembly for Leaks Oxygen Corrosion Sealing of BASE, Installation Flue Covers and CanopiesAttachment of Flue Covers Page Page Page Page Sizes 5006B Thru 5019B Recommended Water Boiler PipingSupply Connection & I Return Connection Supply Connections & 2 Return ConnectionsInstallation of Jacket Support Brackets to Base END Panels Installation of Jacket Parts Common to ALL Boiler SizesPage Exploded View of Jacket 6 Thru 10 Section Boilers Securing of CANOPY/DRAFTHOOD CANOPY/DRAFTHOOD Mounting Diagram Exploded View of Jacket 11 Thru 19 SECT. Boilers Completion of Jacket Installation 11 Thru 26 Section Boilers Exploded View of Jacket 20 Thru 22 SECT. Boilers Exploded View of Jacket 26 SECT. Boilers Steam Trim and Controls Shutoff Valve Between Safety ValveMounting Elevations of M&M 150 and a 67M Float Lwco Water Trim and Controls Open GAS Train Cartons Recommended Piping to BUILT-IN Tankless HeatersOpen Gas Controls Cartons Pilot Piping EI Control System Robertshaw7000 A B Thru 5009B Installation of S8610M ModuleA B Thru 5026B NAT. GAS Canada 5006B Thru 5026B NAT. GAS Pilot Piping EI Control System V88APilot Piping EO Control System Installation of Pilot Safety SwitchInstallation of Pilot Safety Switch EO Control System EE Control System Installation of EO and EE Mounting Bracket and ControlsPilot Piping EE Control System Sect. and larger boilersPilot Piping EOP Control System Installation of Pilot Safety Switch EOP Control SystemPilot Piping EEP Control System EEP Control SystemPage Single Vent System Manifold Vent System VentingPage General Section IV OperationTable IV Water Content Control Variations CondensationBe sure power is off when checking high voltage connections A B Thru 5009B Canada 5006B Thru 5014B Schematic Wiring Diagram EI Control System V88 GAS TrainSequence of Operation A B Thru 5014BEI Control System Schematic wiring diagram 15 Thru 26 SECT. BoilersSequence of Operation Page Pilot Failure Safety Switch CircuitWiring diagram 6 Thru 14 SECT. Boilers Proceed to Paragraph 15- Minimum Input Wiring diagram 15 Thru 26 SECT. Boilers Operating and safety controls. Should any EE Control System Wiring diagram 15 Thru 26 SECT. Boilers Proceed to Paragraph 15- Minimum Input Wiring Diagram 6 Thru 14 SECT. Boilers EOP Control System Turn on Main Power Switch. Main Power Light will light Wiring Diagram 15 Thru 26 SECT. Boilers EOP Control System Safety Switch Circuit Wiring Diagram 6 Thru 14 SECT. Boilers EEP Control System Pilot Failure Safety Switch Circuit Wiring Diagram 15 Thru 26 SECT. Boilers EEP Control System Make sure all manual resets are activated where applicable Normal Operation Sequence Page Check GAS Input Rate to Boiler Screw Minimum Input AdjustmentsV8944B Combination Valve Motorized Modulating ActuatorTest Ignition System Safety SHUT-OFF Device AS Follows Combustion Chamber BURN-OFF Thermocouple Pilot SystemRemoval of Jacket Front Panel Section V ServiceAvoid Breathing Fiber Particulates and Dust Lubrication Cleaning of FluewaysPilot Locations Honeywell Q179D Pilot w/THERMOCOUPLE Main Burner Flame AdjustmentPilot Flame Honeywell Q3481B Pilot FlameHoneywell Q327A Pilot w/THERMOCOUPLE Pilot Flame Honeywell Q179C PilotDo not drain water below gauge glass Jackets Base PartsNumber in in Table Relates to Corresponding Number Series 5B Base Parts 5006B thru 5014BBase Parts 5015B 5016B 5017B 5018B 5019B 5020B 5021B 5022B 5024B 5026B Series 5B Base Parts 5015B thru 5026BBase Parts Boiler Size Quantity Part Size CanopyIntegral Canopy Drafthoods & Sections Series 5B Section Replacement Chart Series 5B Base / Pilot Assemblies Series 5B Jackets 60413075 5007B Lower Top Panel 2 x 37-3/16 60413085 5008B 2 x 20-7/8 Complete Jackets Jackets Boiler Size 5006B 5008B 5009B 5014B 5015B 5016B 5017B 5026B Boiler SizeV88A GAS Trains Canada Natural GAS only Fluid Power GAS Trains USA 5006B 5009B 5015B 5016B 5017B 100Diaphragm Valve LO-HI-LO GAS Train Canada Natural GAS only 101102 Fluid Power GAS Trains CanadaIgnition Module & Support Bracket EI Control System 103Description Manifold Module Support L62GB-3C Pilot Safety Switch104 A. 5010B-5026B NAT. GAS Canada 5006B-5026B NAT. GAS 105Transformer & Pilot Line Regulator EO Control System 106107 108 109 110 EOP & EEP Control Panel 111112 EI Control System Pilot AssemblyEI GAS 1136236007 NAT. GAS Not Available for LP 1146236003 NAT. GAS 115 Date Service Performed116 Limited Warranty