(5)Turn on Main Power Switch on both panels. Main Power Lamp on each panel will light.
(6)Turn on manual pilot valves. Both pilots should light.
(7)Turn on Manual Main Gas Valves.
(8)Turn on Main Gas Valve Switch on both panels to light burners. Main Gas Valve Lamp on each panel will light.
Proceed To Paragraph 15- Minimum Input Adjustments (for diaphragm
SEQUENCE OF OPERATION EEP – See Fig. 54
b.NORMAL OPERATION – 5015B thru 5026B
(1)When the operating control calls for heat, terminal #6 of both panels and both RA890F relays are energized.
(2)A component self check circuit on each RA890F relay is activated which checks the electronic network of the relay.
(3)Terminals #3 and #4 on both panels and
RA890F relays are energized. Terminal #3 opens pilot line solenoid valve supplying gas to the Q179C pilot. Terminal #4 energizes the ignition transformer creating electric spark ignition at the Q179C pilot.
(4)Flame rod circuit between each Q179C pilot and terminal “F” on its respective RA890F proves presence of flame electronically at its Q179C pilot.
(5)Terminal #4 to ignition transformer is de- energized after flame is proven at its Q179C.
(6)Terminal #5 on each RA890F is energized supplying power to its respective main gas valves. “Main Gas Valve” panel lamps will light providing “Main Gas Valve” switches are “ON” (circuits closed).
(7)Main gas valves open and main burners are ignited by the pilot flames.
(8)When the operating control is satisfied, terminals #6 and all other terminals on both RA890F relays and panels are
“Main Gas Valve” lamps go “OFF”, the main gas valves and pilot valve for each gas train are closed and main burners and pilot burner flames are extinguished.
(9)“Main Power” lamp remains lighted.
c.SAFETY SHUTDOWN
(1)SAFETY SWITCH CIRCUIT
Make sure all manual resets are activated where applicable.
(2) PILOT FAILURE | |||
| (a) | Pilot failure can only occur during the | |
|
| operating cycle of the boiler. Any pilot | |
|
| failure on either of the Q179C Electronic | |
|
| Pilot, after ignition of pilot flame, will close | |
|
| the pilot valve and the main gas valves | |
|
| controlled by that particular RA890F relay | |
|
| in 0.8 second. The burners controlled by the | |
|
| other RA890F will continue to burn. | |
| (b) | For 15 seconds, after failure of a Q179C | |
|
| pilot, the relay through terminals #3 and | |
|
| #4 will try to | |
|
| pilot flame can be sensed by the flame rod | |
|
| circuit in 15 seconds, terminals #3 and #4 | |
|
| are | |
|
| on safety. “Pilot Failure Alarm Lamp” will | |
|
| be activated. | |
| (c) | Pilot failure is caused by the following: | |
|
| (1) | Complete loss of gas supply. |
|
| (2) | Poor ignition spark caused by low |
|
|
| voltage, poor ground connection, faulty |
|
|
| wiring, and possibly a defective ignition |
|
|
| transformer. |
|
| (3) | Low gas pressure will prevent flame rod |
|
|
| circuit from sensing pilot flame properly. |
|
| (4) | Unusually strong secondary air drafts |
|
|
| can blow the pilot flame away from the |
|
|
| rod momentarily causing nuisance shut- |
|
|
| down. |
|
| (5) A pilot line solenoid valve will not open | |
|
|
| because of faulty wiring, low voltage, or |
|
|
| possibly the valve is defective. |
|
| (6) A defective RA890 may be the cause | |
|
|
| but items (1) thru (5) should be followed |
|
|
| first. See also RA890 relay literature |
|
|
| furnished with the panel system. |
|
| (7) | By referring to the Sequence of |
|
|
| Operations, step by step operation |
|
|
| of the system can be controlled and |
|
|
| the cause of pilot failure can be readily |
|
|
| found. After the cause of pilot failure |
|
|
| has been corrected, resume normal |
|
|
| operation by following the Lighting |
|
|
| Instructions on the panel. |
d. SHUTDOWN INSTRUCTIONS | |||
(1) | Turn off all switches on both panels. | ||
(2) | Close manual |
68
If limit control, low water
13. THERMOCOUPLE CONTROL SYSTEM (Canada |
Only) |
The 5006B thru 5013B boilers are equipped with |
a Thermocouple Control System that utilizes a |