is

 

Explanation of type of appliance

 

 

 

Type of appliance

 

Description

 

 

 

B23

 

Air for combustion is drawn from the boiler room.

 

 

 

C13

 

Concentric and / or parallel wall flue terminal

 

 

 

C33

 

Concentric and / or parallel roof flue terminal

 

 

 

C43

 

Appliances on common air supply and flue gas discharge (concentric and / or

 

 

parallel) in multi-storey building.

 

 

 

C53

 

Air supply and flue terminal types mixed.

 

 

 

C63

 

Appliances supplied without flue components and / or terminal. These

 

 

appliances must be installed in compliance with local regulations.

 

 

 

 

 

Note

 

 

Make sure that the chimney discharges into an area where this is permitted

 

for this category of appliance.

 

 

 

3.9.3

Concentric connections

 

The table shows the requirements for concentric systems.

Warning

Install flue gas discharge pipe runs with a run-off of 5 mm per metre.

Chimney flue requirements for concentric systems (C13, C33)

Appliance

Diameter

Maximum length

Maximum

 

 

 

number of 90°

 

 

 

bends

SGE 40

 

 

 

 

 

 

 

SGE 60

100/150 mm

15 m

4

 

 

 

 

 

 

 

 

Caution

Both conditions stated in the table must be fulfilled.

Even if there are less bends than the stated maximum, the maximum pipe length may not be exceeded.

Even if the total pipe length is less than the stated maximum, the maximum number of bends may not be exceeded.

Instruction manual SGE

31

Page 31
Image 31
A.O. Smith SGE service manual Concentric connections