Instruction manual SGE 33
is
C13 Concentric wall flue terminal specifications
C33 concentric roof flue terminal specifications
3.9.4 Parallel connections
The table states the maximum pipe lengths for parallel systems. The maximum
pipe length depends on the chosen diameter.
Warning
Install flue component pipe runs with a run-off of 5mm per metre.
Chimney flue requirements for parallel systems
Subject Description
Wall flue terminal set:
1x Wall flue terminal (incl. wall flange
& clamping ring)
1x Pipe 500 mm
1x Bend 90°
Art. No. 0302 504 1
Construction Concentric
Manufacturer Muelink & Grol
Type M2000 MDV SEC
Pipe material Construction Concentric
Chimney flue Thick-walled aluminium with lip ring seal
Air supply Thin-walled galvanised sheet steel
Pipe diameters Chimney flue Ø 100 mm
Air supply Ø 150 mm
(1) No other wall flue terminal is permitted. Use this item number to order the wall conduit set from supplier,
manufacturer or wholesaler.
Subject Description
Roof flue terminal set:
1x Wall flue terminal (incl. clamping
ring)
1x Pipe 1000 mm
1x Mounting flange
Art. No. 0304 423 1
Construction Concentric
Manufacturer Muelink & Grol
Type M2000 DDV HR-C
Pipe material Construction Concentric
Chimney flue Thick-walled aluminium with lip ring seal
Air supply Thin-walled galvanised sheet steel
Pipe diameters Chimney flue Ø 100 mm
Air supply Ø 150 mm
(1) No other roof flue terminal is permitted. Use this item number to order the roof conduit set from
supplier,manufacturer or wholesaler.
Appliance Diameter1Maximum
total length
Lequivalent
90° bend
Lequivalent
bend 45°
SGE 40
SGE 60 100 mm 25 m 4.6 m 1.2 m
SGE 40
SGE 60 130 mm 100 m 2.4 m 1.4 m
1) Parallel systems with diameter of 130 mm or 150 mm. If the maximum total
length for a diameter of 130 mm is insufficient, 150 mm diameter must be
used. Any diameter enlargement must be carried out on both air supply and
chimney flue.