13.3 Troubleshooting table for displayed errors Displayed errors
Code + Description | Cause | Solution |
| Remark | |
|
|
|
| ||
S01 (blocking error) | Sensor is not (correctly) | Connect the sensor lead to JP3 | See the SGE electrical diagram (17 "Appendices") | ||
Open circuit from | connected |
|
|
| |
Damaged cable or | Replace the sensor | To replace the necessary parts, you must contact your installation | |||
temperature sensor T2 | |||||
defective sensor |
|
| engineer | ||
at bottom of the tank |
|
|
|
| |
S02 (blocking error) | Sensor is not (correctly) | Connect the sensor lead to JP5 | See the SGE electrical diagram (17 "Appendices") | ||
Open circuit in sensor 1 | connected |
|
|
| |
|
|
|
| ||
Damaged cable or | Replace sensor T | 1 | To replace the necessary parts, you must contact your installation | ||
of temperature sensor | defective sensor |
| engineer | ||
T1 at the top of the |
|
| |||
|
|
|
| ||
tank(1). |
|
|
|
| |
S03 (blocking error) | Sensor is not (correctly) | Connect the sensor lead to JP5 | See the SGE electrical diagram (17 "Appendices") | ||
Open circuit in sensor 2 | connected |
|
|
| |
|
|
|
| ||
Damaged cable or | Replace sensor T | 1 | To replace the necessary parts, you must contact your installation | ||
of temperature sensor | defective sensor |
| engineer | ||
T1 at the top of the tank |
|
| |||
(1). |
|
|
|
| |
|
|
|
| ||
S04 (blocking error) | Dummy is not | Connect the dummy sensor (dummy sensor 1 and 2) leads to JP4. | See the SGE electrical diagram (17 "Appendices") | ||
Open circuit from | (correctly) connected |
|
|
| |
|
|
|
| ||
Defective dummy | Replace the dummy sensor | To replace the necessary parts, you must contact your installation | |||
dummy 1 | |||||
|
|
| engineer | ||
|
|
|
| ||
|
|
|
| ||
S05 (blocking error) | Dummy is not | Connect the dummy sensor (dummy sensor 1 and 2) leads to JP4. | See the SGE electrical diagram (17 "Appendices") | ||
Open circuit from | (correctly) connected |
|
|
| |
|
|
|
| ||
Defective dummy | Replace the dummy sensor | To replace the necessary parts, you must contact your installation | |||
dummy 2 | |||||
|
|
| engineer | ||
|
|
|
| ||
|
|
|
| ||
S07 (blocking error) | Sensor is not (correctly) | Connect the sensor lead to J14 (port 2 and 4) of the solar controller | See the SGE electrical diagram (17 "Appendices") | ||
Open circuit from | connected |
|
|
| |
temperature sensor S2 |
|
|
| ||
Damaged cable or | Replace the sensor | To replace the necessary parts, you must contact your installation | |||
at bottom of tank | defective sensor |
|
| engineer | |
|
|
| |||
|
|
|
|
|