| 12 |
| Service program |
|
|
APPLIANCE HISTORY BURNINGHOURS 000410 ^IGNITIONS 001000 ÈFLAME ERRORS 000021
IGNIT ERROR 000013
12.5 Display the selected appliance
Call up the menu for displaying the appliance selection as follows:
•: SELECT APPLIANCE
The appliance number can be found on the rating plate.
The appliance selection has been correctly preset in the factory.
SELECT APPLIANCE »5934
^8576 È 3379
6527
....
12.6 Switching the pump on or off
If a program-controlled pump is
installed (3.11.6 "Connecting a
•: PUMP RELAY
The standard setting for the pump relay is OFF.
PUMP RELAY »ON
OFF
If the mode WEEK PROGRAM or EXTRA PERIOD is active, then the setting for mode WEEK PROGRAM or EXTRA PERIOD has priority over the ON/OFF selection for the pump relay in the service menu.
Example
One of the week program periods is currently active. During this period, the pump relay setting is OFF. If the pump relay is set ON in the service menu, the pump will nonetheless remain OFF. The pump will only switch ON once the week program period has ended.
12.7 Setting the service interval
To aid servicing, the electronic controller includes a service interval which is used to set the frequency of maintenance interval (14.2 "Determining service interval") by the service and maintenance engineer, based on the number of burning hours.
is
The service interval is based on the number of burning hours. This can be set to 500, 1000 and 1500 hours. The standard setting for number of hours is 500. Once the preset number of hours is reached, a message (8.4 "Service condition"). to this effect will appear. Adjust the service interval via:
•: SERVICE INTERVAL
SERVICE INTERVAL
»500
^1000 BURNING HOURS È 1500
12.8 Setting legionella prevention
To prevent infection with legionella bacteria, the appliance heats the water to 65 °C once per week, for 1 hour. This period is adjustable. By default, this period is set to Monday from 02:00 to 03:00 hours.
12.8.1Switching legionella prevention on and off
To switch legionella prevention on or off, select:
•: ANTI LEGIONELLA
ANTI LEGIONELLA »YES
NO
•Select NO to switch legionella prevention off.
•Select YES to switch legionella prevention on. The following display appears:
ON MO 02:00 LEG OFF MO 03:00 Tset 65ÉC
»START CHANGE
•Select START to activate the period currently displayed.
The following display appears. This display indicates that legionella prevention is switched on.
a
LEG Ê Ê Ê Ê
02:45 Monday 60ÉC
MO 03:00 Tset 65ÉC
RUNNING
12.8.2Changing legionella prevention start time
If you wish to change the start time, select:
: ANTI LEGIONELLA YES CHANGE
The following display appears.
ON ÈMO 02:00 LEG
OFF MO 03:00
Tset 65 o C
START
74 | Instruction manual SGE |