Code + Description | Cause | Solution | Remark |
| |
|
|
|
|
|
|
F04 (lock out error) | No gas | 1. | Open the main gas valve and/or the manual gas valve supplying | To repair the gas supply, contact your installation engineer |
|
Three unsuccessful |
|
| the water heater |
|
|
| 2. | Check the supply pressure to the gas control |
|
| |
ignition attempts. |
|
|
| ||
| 3. | If necessary, repair the gas supply |
|
| |
|
|
|
| ||
|
|
|
|
| |
| Air in the gas pipes | Bleed the air out of the gas pipe | See Checking the supply pressure and burner pressure for how to |
| |
|
|
|
| bleed air from the gas line, and measure the supply pressure and |
|
| No burner pressure | 1. | Check the burner pressure to the gas control |
| |
| burner pressure. |
| |||
|
| 2. | Check that the gas valve(s) open and shut correctly |
| |
|
| To replace the necessary parts, you must contact your installation |
| ||
|
| 3. | If necessary, replace the gas control. | engineer |
|
|
|
|
| ||
|
|
|
|
|
|
| Defect in the hot | 1. | Check that the hot surface igniter is correctly connected (JP2). | If the error persists, contact your installation engineer. |
|
| surface igniter circuit | 2. | Check the wiring of the hot surface igniter. | To replace the necessary parts, you must contact your installation |
|
|
| engineer |
| ||
|
| 3. | Measure the resistance across the hot surface igniter. This must |
| |
|
|
|
| ||
|
|
| lie between 2 and 5 ohms. |
|
|
|
| 4. | Check that the hot surface igniter lights up during ignition. |
|
|
|
| 5. | If necessary, replace the hot surface igniter. |
|
|
|
|
|
|
|
|
| Defect in the ionisation | 1. | Check that the flame probe is correctly connected (JP2) |
|
|
| circuit | 2. | Check the wiring of the flame probe |
|
|
|
|
|
| ||
|
| 3. | Measure the ionisation current. This must be at least 1.5 |
|
|
|
|
| microamps. |
|
|
|
| 4. | Replace the wiring if necessary. |
|
|
|
|
|
|
| |
| Supply voltage too low | Check the supply voltage, this must be 230 VAC |
|
| |
|
|
|
|
|
|
F05 (lock out error) | Incorrect roof or wall | 1. | Check that the correct roof or wall flue conduit (3.9 "Air supply | If the error cannot be resolved or is persistent, contact your |
|
| conduit. |
| and flue") has been fitted. | installation engineer |
|
Too many flame errors | Recirculating flue | 2. | If necessary, install the correct roof or wall conduit. |
|
|
have been signalled. | gases. |
|
| ||
3. | Check that the roof or wall conduit discharges into a permitted |
|
| ||
|
|
|
| ||
|
|
| area. |
|
|
|
|
|
|
|
|
Instruction manual SGE | 85 |