is

 

 

 

 

 

Code + Description

Cause

Solution

Remark

 

 

 

 

 

 

 

F10 (lock out error)

Pressure switch not

1.

Check the running speed of the fan (12.5 "Display the selected

If the error cannot be resolved or is persistent, contact your

 

Restriction on the

closing

 

appliance")

installation engineer

 

 

2.

Check that the hoses on the pressure switch and the air supply

To replace the necessary parts, you must contact your installation

 

number of ignition

 

 

hose between fan and burner are correctly fitted. Refit them if

engineer

 

attempts based on

 

 

 

 

 

 

necessary

 

 

pressure switch state

 

 

 

 

changes.

 

3.

Check for cracks in the hoses on the pressure switch and in the

 

 

 

 

 

air supply hose between fan and burner. If necessary, replace

 

 

 

 

 

the hoses.

 

 

 

 

4.

Check that the flue gas outlet is compliant (3.9 "Air supply and

 

 

 

 

 

flue").

 

 

 

 

5.

Check for blockage in the flue gas discharge. Remove any

 

 

 

 

 

blockage that may be present

 

 

 

 

6.

Check for blockage in the condensation water discharge.

 

 

 

 

 

Remove any blockage that may be present.

 

 

 

 

7.

Measure the pressure differential across the pressure switch.

 

 

 

 

 

See the table in Preparation for

 

 

 

 

 

maintenance (15.2 "Preparation for maintenance"). If there is

 

 

 

 

 

insufficient pressure differential, clean the heat exchanger. If the

 

 

 

 

 

pressure differential is acceptable, check that the pressure

 

 

 

 

 

switch is closing, using a multimeter.

 

 

 

 

 

 

 

F11 (blocking error)

Defective gas valves

See F07.

 

 

Flame detection with

 

 

 

 

 

closed gas valve.

 

 

 

 

 

 

 

 

 

 

 

F17 (blocking error)

No power supply at

1.

Check that there is power to the solar heating system controller

See the SGE electrical diagram (17 "Appendices")

 

Communication error

solar controller

2.

The measured voltage must be 230VAC (-15%, +10%)

If the error persists, consult your installation engineer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No cable or damaged

1.

Check the wiring (communication cable) between the main

See the SGE electrical diagram (17 "Appendices")

 

 

cable

 

controller and the solar heating system controller

For replacement of the cable, contact your installation engineer

 

 

 

2.

If cable missing, connect the cable

 

 

 

 

3.

If cable damaged, replace the cable

 

 

 

 

 

 

 

 

Instruction manual SGE

87

Page 87
Image 87