3

3.12.5

Installation

Connecting tank sensor

is

Note

This sensor is already mounted in the tank prior to delivery. The sensor is mounted between the inlet and outlet of the heat exchanger. However, you must still connect the lead to the solar heating system controller.

1.Connect the sensor lead with the blade connectors to the sensor.

2.Connect the other end to terminals 2 and 4 of J14.

3.Fit the cables in the strain relief.

4.Continue (3.12.6 "Connecting communication cable").

3.12.6Connecting communication cable

Note

>The communication cable must always be connected, otherwise neither the appliance nor the solar heating system controller will run.

1.Connect the double connector to J16.

2.Fit the cable in the strain relief.

3.Connect the other end of the communication cable to the terminal block of the appliance. See:

-connecting communication cable to appliance (3.11.9 "Connecting communication cable to solar heating system")

-electrical diagrams (17.3 "Electrical diagram for the appliance").

4.Connect the optional head pump (3.12.7 "Connecting extra head pump") or QT sensor (3.12.8 "Connecting Q/T sensor").

5.If you have no more connections to make:

-Fit the cap on the electrical terminal block.

-Fit the plastic covers onto the appliance.

3.12.7Connecting extra head pump

Note

This pump is essential if a greater head is required. When the system has such a high resistance (>110 kPa) that the pump in the pump station is insufficient, you can connect a second (ON/OFF) pump to the solar heating system controller.

1.Connect earth (), live and neutral to terminals 7 through 9.

2.Fit the cable in the strain relief.

3.If you need to connect an extra head pump continue (3.12.8 "Connecting Q/T sensor"), otherwise:

-Fit the cap on the terminal block.

-Fit the covers onto the appliance.

3.12.8Connecting Q/T sensor

Note

You can optionally add a Q/T sensor to the installation. This enables you to calculate the energy contribution of the system. For more information or to order the Q/T sensor, please contact your supplier.

1.Connect the 5V to J12-1.

2.Connect sensor S4 to J12-2.

40

Instruction manual SGE

Page 40
Image 40
A.O. Smith SGE service manual 12.5, Connecting tank sensor, Connecting communication cable, Connecting extra head pump