Level the PDU, UPS, NetShelter, and XR Battery Enclosures

Leveling feet are attached under the enclosure at each corner. The leveling feet can help provide a stable base if the selected floor space is uneven, but they are not intended to compensate for a badly sloped surface. To level the enclosure:

1.Use a 14-mm end of the open-ended wrench (provided) to extend the leveling foot until it makes firm contact with the floor.

2.Repeat step 1 for each of the remaining leveling feet.

3.Use a level to determine which feet need further adjustment to level the enclosure. Adjust as necessary.