Installation Procedures: Connect Utility Conductors to the PDU

For overhead wiring: Remove the user connection plate from the top of the PDU.

2.Cut an appropriately-sized hole in the gland plate for the conduit.

3.Re-attach the gland plate.

4.Install a lock-nut and bushing to the conduit.

5.Thread the conduit through the hole.

Install a circuit breaker

Warning: When you connect the InfraStruXure PDU to utility, you must install a circuit breaker to protect the PDU against over-current.

Determine the amperage of the circuit breaker that you need to install:

Input Voltage

Circuit Breaker Amperage

208V175A

480V80A

600V60A

InfraStruXure System - Installation and Start-Up