6. Install at least one battery module (four battery units) in the Symmetra PX UPS. Install battery modules, starting in the lowest available shelf. Position the battery unit between the grooves, and slide it completely into the enclosure.
Heavy: Use two people to lift and install battery units.
Electrical Hazard: The DC bus in the Symmetra PX UPS is energized when battery modules are installed, even when the DC Disconnect circuit breaker is open.
7. Install at least one power module in the Symmetra PX UPS. Install power modules starting from the lowest available shelf. Push each module completely into the enclosure.
px0012a
Heavy: Use two people to lift and install power modules.
30 | InfraStruXure System - Installation and |