3.Command the UPS to turn off power to the load:

a.Press the ESC key at the top-level status screen to open the top-level menu and have access to eight submenus.

b.Select Control, and press the ENTER key.

c.Select Turn Load Off from the Control menu, and press the ENTER key.

d.On the next screen: select Yes, UPS Load OFF, and press the ENTER key.

The LOAD ON LED turns off and the interface displays the following two screens:

4.Set the UPS System Enable switch to OFF, and then set the UPS DC Disconnect circuit breaker and to OFF.

5.If applicable, set the XR Battery Enclosure DC Disconnect circuit breaker to OFF.

Start-Up Procedure: Apply power to the system

Top-Level Menu

 

 

 

 

 

 

Control

Logging

 

 

Status

Display

 

 

Setup

Diags

 

 

Accessories

Help

 

 

 

 

Control Menu

UPS Into Bypass

Do Self Test

Simulate Power Fail

Graceful Reboot

Graceful Turn Off

Start Runtime Cal

Turn Load Off

Confirmation Screen

Confirm

Yes, UPS Load OFF

No, Abort

UPS has been

commanded to turn load power off...

UPS load is off

Press any key...

px0003a