Installation Procedures: Connect DC Power Wiring, if Applicable
Connect power cables from the XR Battery Enclosure to the Symmetra PX UPS
1.Route the XR Battery Enclosure DC output cables to the Symmetra PX UPS through the hole in the adjacent side panels.
2.Connect the XR Battery Enclosure DC output cables to the Symmetra PX UPS DC input terminal [(+) to (+), (CT) to (CT),
Tighten the lugs on the terminals only to the torque specified: the power terminal lug diameter is 8 mm with a torque value of 53 lb/in (6Nm).
3.Connect the XR Battery Enclosure ground cable to the Symmetra PX UPS ground stud through the hole in the adjacent side panels.
XR (GND) |
|
XR (CT) | pxb0006a |
XR |
|
XR (+) |
|
XR Battery Enclosure | Symmetra PX UPS |
InfraStruXure System - Installation and | 21 |