Connect an Emergency Power Off Switch

Overview

To provide a mechanism for

emergency power off, attach a

remote switch (not included) to the EPO interface on the PDU

monitoring unit. The EPO interface () is connected to the

PDU Main Input switch () and to the UPS internal EPO switch

().

When the EPO is activated, the

main input breaker to the PDU transformer is opened, the UPS

DC Disconnect breaker is opened,

and the UPS System Enable switch is turned off. In this sequence, there is no power from the PDU transformer and there is no power from the UPS inverters and batteries.

Note: Contact closure is recommended.

Connecting the switch. The Emergency Power Off (EPO) switch connects to the PDU user connection plate. The figure on the right shows the location of the user connection plate on the roof of the PDU. Connect a switch using one of three following connections:

Contact closure

24Vac

• 24Vdc

Note: APC offers an optional InfraStruXure EPO System (EPW9). Contact your APC sales representative, or visit the APC Web site (www.apc.com) for more information.

22

InfraStruXure System - Installation and Start-Up

Page 26
Image 26
APC 600, 480, 208 manual Connect an Emergency Power Off Switch, Overview