Specifications

40 kW InfraStruXure PDU

Electrical

PD40F6FK1-M

PD40G6FK1-M

PD40L6FK1-M

 

 

 

 

Input

 

 

 

 

 

 

 

Nominal Voltage Requirements

208/120 V

480/277 V

600/346 V

Nominal Current

125 A

54 A

43 A

Frequency

57–63 Hz

57–63 Hz

57–63 Hz

Voltage Configuration

 

 

 

Transformer

3W + G + GEC

 

 

Without Transformer

4W + G

 

 

Upstream Circuit Breaker ††

175 AT

80 AT

60 AT

Main Input Conductor Size

3/0 AWG

#3 AWG

#4 AWG

UPS Breaker Size

175 AT

175 AT

175 AT

Maximum Continuous Current

155 A

67 A

54 A

Grounding

PE node (from AC or floor grid)

 

 

 

 

 

Output

 

 

 

 

 

 

 

Voltage AC

3-phase 4-wire PE

 

 

Nominal Voltage

208:120 V WYE

 

 

UPS Breaker Size

150 AT

150 AT

150 AT

Max. Distribution Breaker Size

150 AT

150 AT

150 AT

Number of Distribution Panels

2 × 225A, 42- position

 

Full Load Rating

40 kW

40 kW

40 kW

Max. Contin Current + 125% overload

139 A

139 A

139 A

Nominal Current

111 A

111 A

111 A

Internal Static Switch Fuses

175 A

 

 

Over-current Protection

 

 

 

PDU Current

Determined by UPS

 

 

Grounding

Separately derived neutral/ground bond

 

 

 

 

 

Wiring

 

 

 

 

 

 

 

UPS to PDU

3W + G (1/0 AWG)

 

 

PDU to Distribution Panels

4W + G (1/0 AWG)

 

 

Distribution Panels to Racks/Power Strips

4W + G (12 AWG)

 

 

Power Cable Connections

L21-20 connector system

 

 

 

 

 

InfraStruXure System - Installation and Start-Up

41