Specifications: 40 kW InfraStruXure PDU

 

 

 

 

 

Electrical

PD40F6FK1-M PD40G6FK1-M

PD40L6FK1-M

 

 

 

 

 

 

 

Power Cable Lengths

various

 

 

 

 

Recommended Wire Sizing

 

 

 

 

 

L1, L2, L3, N

3/0 AWG

4 AWG

4AWG

 

G

6 AWG

8 AWG

8 AWG

 

GEC

4 AWG

4 AWG

4 AWG

 

Power Cable—top

Accommodates 28, 3-phase power cables (42 knockouts)

 

Power Cable—bottom

Accommodates 28, 3-phase power cables (48 knockouts)

 

 

 

 

 

 

 

Panel Boards

 

 

 

 

 

 

 

 

 

 

 

Panel Style

3-phase

 

 

 

 

Number of Panels per PDU

2 maximum

 

 

 

 

Positions per Panel

42

 

 

 

 

3-Phase Breakers per Panel

14 maximum

 

 

 

 

1-Phase Breakers per Panel

42 maximum

 

 

 

 

Panel Rating

240 V/225 A (per phase)

 

 

 

Breaker Pitch

3/4 in

 

 

 

 

Accessibility

Through front of the unit

 

 

 

 

 

 

 

 

 

Relay Outputs

 

 

 

 

 

 

 

 

 

 

 

Nominal Switching Capacity

1 A at 30 Vdc

 

 

 

 

Maximum Switching Power

30 W

 

 

 

 

Maximum Switching Voltage

60 Vdc

 

 

 

 

Maximum Switching Current

2 ADC

 

 

 

 

Maximum Carrying Current

2 ADC

 

 

 

 

Surge Ratings

2 kV per Bellcore TA-NWT-001089

 

 

 

 

1.5 kV per FCC part 68

 

 

 

 

 

 

 

 

 

Physical

PD40F6FK1-M

PD40G6FK1-M

PD40L6FK1-M

 

 

 

 

 

 

 

Dimensions (H×W×D)

 

 

 

 

 

PDU

81×24×36 in. (2057 × 610 × 914 mm)

 

 

 

Shipping

86 × 36 × 48 in (2184 × 914 × 1219 mm)

 

Weight

 

 

 

 

 

PDU

1580lb (718.18kg)

 

 

 

 

Shipping

1680lb (763.6kg)

 

 

 

 

Heat Output With Transformer

4645BTU

4617BTU

3425BTU

 

Transformer (if installed)

 

 

 

 

 

Type

Isolation

Step-down

Step-down

 

 

 

 

 

 

42

InfraStruXure System - Installation and Start-Up

Page 46
Image 46
APC 208, 480, 600 manual PD40F6FK1-M PD40G6FK1-M PD40L6FK1-M