Connect User Input Contacts and Relay Outputs to the User Connection Plate
Overview
Make contact closure connections (NO or NC) at the user connection plate to monitor dry contacts. You can make up to four input contacts and four relay output connections.
The figure at the right shows the location of the user connection plate on the roof of the PDU enclosure.
Make the connections from inside the enclosure, or remove the user connection plate and make the connections.
Remove the plate using a Phillips or standard screw driver to loosen the two captive screws. Use the knockout in the plate to route cables to and from the user connections on the plate. If you remove the plate, make sure that you do not disturb the existing connections.
See the Operation Manual for
information on how to configure the input contacts and relay outputs.