| Specifications: 40 kW InfraStruXure PDU | |||
Physical |
| ||||
|
|
|
|
|
|
Configuration | Delta to WYE |
|
|
|
|
Maximum Power Rating | 60kVA |
|
|
|
|
Maximum Current Rating | 166A | 72A | 58A | ||
Construction | Cu windings, open core |
|
|
| |
Temperature Rating | 220° C (Class H) |
|
|
|
|
Maximum Temperature Rise | 150°C |
|
|
|
|
Efficiency |
|
|
|
| |
|
|
|
|
|
|
Environmental |
|
|
|
|
|
|
|
| |||
Operating Environment | Protected from water and conductive contaminates | ||||
Temperature |
|
|
|
|
|
Operating | 32 to 104° F (0 to 40° C) |
|
|
| |
Storage | 32 to 113° F (0 to 45° C) |
|
|
| |
Class | Class H (220° C) |
|
|
|
|
Humidity |
|
|
|
|
|
Operating | 0 to 95%, |
|
|
| |
Storage | 0 to 95%, |
|
|
| |
Elevation |
|
|
|
|
|
Storage | 3,000 ft (10 000 m) |
|
|
| |
Acoustic Noise Emission | Maximum 50dB(A) at 1 m |
|
|
| |
Heat Rejection at Full Load | 5194 BTU/hr. (1.5 kW) |
|
|
| |
|
|
|
|
|
|
Compliance |
|
|
|
|
|
|
|
|
|
|
|
Approvals | UL 60950, cUL |
|
|
|
|
|
|
|
|
|
|
†Transformerless units only. |
|
|
|
|
|
†† Provided by customer. |
|
|
|
|
|
‡The specifications are recommendations. Consult the NEC and local codes for requirements specific to your installation.
.
InfraStruXure System - Installation and | 43 |