Connect DC Power Wiring, if Applicable

Electrical Hazard: Only Field Service Engineers or qualified personnel trained by APC may connect the XR Battery Enclosure to the Symmetra PX UPS or to another XR Battery Enclosure.

Warning: The supplied power and ground wires are for internal side-panel wiring only. These wires are not for use in external conduits.

Electrical Hazard: Before you begin connecting the DC power wiring, ensure that there are no battery units installed in the XR Battery Enclosures. Do not install battery units until instructed to do so.

Cascade XR Battery Enclosures

If you have multiple XR Battery Enclosures as part of your InfraStruXure system, you can cascade XR Battery Enclosures to a Symmetra PX UPS. Starting with the XR Battery Enclosure furthest away from the UPS:

1.Route DC output cables and the ground cable (coiled on the floor of the enclosure) from one XR Battery Enclosure to the next XR Battery Enclosure through the adjacent holes in the side panels of the enclosures.

2.Connect the DC output cables from one XR Battery Enclosure to the DC Input Circuit Breaker of the next XR Battery Enclosure [(+) to (+), (CT) to (CT), (–) to (–)].

3.Connect the ground wire from one XR Battery Enclosure to the grounding stud on the next XR Battery Enclosure.

To

XR Battery

Enclosure

XR (GND)

XR (–)

XR (CT)

XR (+)

pxb0007a

To

UPS

XR Battery Enclosure

XR Battery Enclosure

20

InfraStruXure System - Installation and Start-Up

Page 24
Image 24
APC 480, 208, 600 manual Connect DC Power Wiring, if Applicable, Cascade XR Battery Enclosures