Start-Up Procedure: Apply power to the system
Verify UPS battery operation
1.Read the messages displayed on the Symmetra PX UPS display interface. Note any alarms and verify that they are appropriate for
2.Command the UPS to apply power to the load:
a.Press the ESC key to open the
b.Select Control, and press the ENTER key.
c.Select Turn Load On from the Control menu, and press the ENTER key.
d.On the next screen: select Yes, UPS Load ON, and press the ENTER key.
The interface will display the following screen:
The interface will display the following fault message:
e. Select Start Now, and press the ENTER key.
The interface will display the following screen:
The LOAD ON LED illuminates and the interface displays the following screen:
Fuel %
Load %
In 208V out000V 60Hz Runtime: 1hr 2m
Control Logging
Status Display
Setup Diags
Accessories Help
Control Menu
UPS Into Bypass
Do Self Test
Simulate Power Fail
Graceful Reboot
Graceful Turn Off
Start Runtime Cal
Turn Load On
Confirmation Screen
Confirm
Yes, UPS Load ON
No, Abort
UPS has been
commanded to turn load power on...
Low/No AC input
Start up on Batt?
Start Now
Abort
UPS has been
commanded to turn load power on...
UPS load is on
Press any key...
After you have verified that the UPS operates correctly in battery operation, shut down the UPS:
32 | InfraStruXure System - Installation and |