Start-Up Procedure: Apply power to the system

8. Secure the power module:

a. Tighten the screws on each side of the power module.

b. Turn the locking latch clockwise until the arrow on the knob faces the power module.

px0019a

Note: The power module will not start unless the locking latch is engaged.

9.Set the UPS DC Disconnect circuit breaker to ON, and then set the UPS System Enable switch to ON.

px0013a

10.If applicable, set the XR Battery Enclosure DC Disconnect circuit breaker to ON.

When the System Enable switch is in the ON position, the UPS is running on battery. The Startup screen appears on the display interface of the Symmetra PX UPS.

Then, the top-level status screen appears on the display interface. This may take up to 40 seconds.

PowerView RM

Rev: 000 English

Please wait...

Fuel %

Load %

In 000V out000V 60Hz Runtime: 1hr 2m

InfraStruXure System - Installation and Start-Up

31

Page 35
Image 35