Indoor Location Continued
4.Keep all fuel and its associated piping away from all components of the engine exhaust system.
5.The exhaust system should be inspected on a regular basis to assure there are no toxic exhaust gas leaks. In some areas this inspection may be provided by your local public service.
6.A carbon monoxide tester may be installed to detect the presence of the deadly gas during times when you are in the building with the engine running (during testing or maintenance).
Installation | The generator is completely assembled, tested and adjusted at the factory before it is shipped to |
| you. The procedures presented in this manual are suggestions and it is the responsibility of the |
| Owner/Operator to arrange for these procedures to be performed by licensed contractors |
| according to all applicable codes including local codes for your Municipality/City/County and |
| State. Installation generally includes the following: |
1. Secure Generator to concrete pad.
2. Connect Fuel Supply.
3. Electrical Connections − power wiring (optional transfer switch) and control wiring.
4. Battery (not included).
5. Ground Connection.
After installation, the post installation checks must be performed prior to starting the engine. After these checks have been performed and the system operation is verified to be good, refer to Section 6 Maintenance for periodic checks that must be performed at scheduled intervals to ensure continued operation with minimal problems.
Secure the Generator
Refer to Table
Secure the generator to the concrete pad using anchor hardware (not provided). See Figure
Table 3-1 Physical Dimensions
|
|
|
|
|
|
|
Generator | Height | Width | Length |
| Weight | |
Model | Open |
| Enclosed | |||
|
|
|
| |||
AE8−E/O | 36.75 | 29.00 | 44.5 | 255 lbs. |
| 463 lbs. |
AE10−E/O | 36.75 | 29.00 | 44.5 | 316 lbs. |
| 509 lbs. |
AE11−E | 30.50 | 30.375 | 46 |
|
| 468 lbs. |
AE25−E−NG | 34.00 | 31.5.0 | 72 |
|
| 1450 lbs. |
AE25−E−LP | 34.00 | 31.5.0 | 72 |
|
| 1450 lbs. |