Installation

Indoor Location Continued

4.Keep all fuel and its associated piping away from all components of the engine exhaust system.

5.The exhaust system should be inspected on a regular basis to assure there are no toxic exhaust gas leaks. In some areas this inspection may be provided by your local public service.

6.A carbon monoxide tester may be installed to detect the presence of the deadly gas during times when you are in the building with the engine running (during testing or maintenance).

Installation

The generator is completely assembled, tested and adjusted at the factory before it is shipped to

 

you. The procedures presented in this manual are suggestions and it is the responsibility of the

 

Owner/Operator to arrange for these procedures to be performed by licensed contractors

 

according to all applicable codes including local codes for your Municipality/City/County and

 

State. Installation generally includes the following:

1. Secure Generator to concrete pad.

2. Connect Fuel Supply.

3. Electrical Connections − power wiring (optional transfer switch) and control wiring.

4. Battery (not included).

5. Ground Connection.

After installation, the post installation checks must be performed prior to starting the engine. After these checks have been performed and the system operation is verified to be good, refer to Section 6 Maintenance for periodic checks that must be performed at scheduled intervals to ensure continued operation with minimal problems.

Secure the Generator

Refer to Table 3-1for the dimensions and weight of each generator. Mounting bolts in the base frame secure the generator to the shipping pallet. Remove these bolts, lift the generator and remove the shipping pallet.

Secure the generator to the concrete pad using anchor hardware (not provided). See Figure 3-1. Anchor bolts must be long enough to extend through the generator mounting frame.

Table 3-1 Physical Dimensions

 

 

 

 

 

 

 

Generator

Height

Width

Length

 

Weight

Model

Open

 

Enclosed

 

 

 

 

AE8−E/O

36.75

29.00

44.5

255 lbs.

 

463 lbs.

AE10−E/O

36.75

29.00

44.5

316 lbs.

 

509 lbs.

AE11−E

30.50

30.375

46

 

 

468 lbs.

AE25−E−NG

34.00

31.5.0

72

 

 

1450 lbs.

AE25−E−LP

34.00

31.5.0

72

 

 

1450 lbs.

3-4 Receiving & Installation

MN2415

Page 16