Programmable input, can be configured to on of the following:

Note 1:

Programmable input, can be configured to on of the following:

SImmediate warning close on fault − If the input is activated at any time the unit will alarm and energize the common warning and common alarm output.

SImmediate warning open on fault − If the input is deactivated at any time the unit will alarm and energize the common warning and common alarm output.

SImmediate shutdown close on fault − If the input is activated at any time the generator will be shutdown and energize the common warning and common shutdown output. The generator can not be started.

SImmediate shutdown open on fault − If the input is deactivated at any time the generator will be shutdown and energize the common warning and common shutdown output. The generator can not be started.

SDelayed warning close on fault − If the input is activated and the safety time has elapsed the unit will alarm and energize the common warning and common alarm output.

SDelayed warning open on fault − If the input is deactivated and the safety time has elapsed the unit will alarm and energize the common warning and common alarm output.

SDelayed shutdown close on fault − If the input is activated and the safety time has elapsed the generator will be shutdown and energize the common warning and common shutdown output.

SDelayed shutdown open on fault − If the input is deactivated and the safety time has elapsed the generator will be shutdown and energize the common warning and common shutdown output.

Table 4-1Programmable Functions and Values Continued

Auxiliary Output 1

F

f

f

F

f

f

f

f

Not Used

 

 

 

 

 

 

f

f

F

Pre−heat

 

 

 

 

 

 

f

F

f

Load Transfer

 

 

 

 

 

 

f

F

F

Common Warning

 

 

 

 

 

 

F

f

f

Common Shutdown

 

 

 

 

 

 

F

f

F

System in Auto

 

 

 

 

 

 

F

F

f

Common Alarm

 

 

 

 

 

 

F

F

F

Energize to Stop

See Note 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Auxiliary Output 2

F

f

f

F

F

f

f

f

Not Used

 

 

 

 

 

 

f

f

F

Pre−heat

 

 

 

 

 

 

f

F

f

Load Transfer

 

 

 

 

 

 

f

F

F

Common Warning

 

 

 

 

 

 

F

f

f

Common Shutdown

 

 

 

 

 

 

F

f

F

System in Auto

 

 

 

 

 

 

F

F

f

Common Alarm

 

 

 

 

 

 

F

F

F

Energize to Stop

See Note 2

 

 

 

 

 

 

 

 

 

Note 2:

Outputs are solid state, rated at 1.2 Amps and switch to battery negative when active.

Programmable output can be configured to one of the following:

SPre−heat. − The output is energized for the period of pre−heat time prior to cranking, and between the cranking attempts.

SLoad Transfer. − The output is active after the safety timer has elapsed.

SCommon warning. − The output is active if there are any warning alarm active.

SCommon shutdown − The output is active if there are any shutdown alarms active.

SSystem in auto. − The output is active when the system is in automatic mode.

SCommon Alarm. − The output is active if there is any alarm condition.

SEnergize to stop. − The output is energized when the engine is required to stop (normal or fault conditions), and will remain energized for the period of the Energize To Stop. Timer, to ensure the engine has come to a complete stop.