General Wiring Considerations
1.Control wires and Power wires cannot be located in the same conduit (NEC Article 725).
2.When routing the interface wiring, do not route it up against anything that could cut or chafe the wiring. do not route the wire up against any hot or potentially hot object.
3.Make sure that all the electrical components (generator set, transfer switch, battery charger, etc.) share a common hardwired ground.
4.Check with your local building inspector to determine what you must do to comply with the local regulations for grounding of this type of permanent installation.
AE8 Electrical Connections Applies only to AE8 Enclosed and Open Series Generators
Single Phase Power Connections
The generator has a 240V single phase AC output. These connections are made at the power terminal box shown in Figure
Figure 3-3 Single Phase Output Power Connections
AE8 with Enclosure or Open
Generator | 1 | L1 | Customer | |
N | N | |||
AC Output Connections | ||||
Output | ||||
4 | L2 | (to Transfer Switch) | ||
| ||||
|
|
| BW0120D |
L1 to N
L2 to N
L1 to L2
120VAC
120VAC
240VAC
Remote Start and Battery Charger Connections
Figure
Figure 3-4 Remote Start & Battery Connections
| AE8 |
|
| AE8 |
|
|
|
|
with Enclosure | Customer Provided Optional Equipment | Open |
| Customer Provided Optional Equipment | ||||
| 16AWG |
| 16AWG | |||||
|
|
|
|
|
|
| ||
R1 | Twisted Pair Wire | Remote Start Switch |
| Twisted Pair Wire | Remote Start Switch | |||
|
|
|
|
| ||||
R2 |
|
| (Close to Start) |
|
|
| (Close to Start) | |
|
|
|
|
|
|
|
| |
Batt+ |
| Out+ | Battery |
|
|
| Out+ | Battery |
Batt− |
| Out− |
|
|
| Out− | ||
D1 |
|
| Charger |
|
| + | − | Charger |
|
|
|
|
|
| |||
D2 |
|
|
|
|
|
| ||
|
| To 120VAC | BW0183D |
| Battery | To 120VAC | ||
|
|
|
| |||||
|
|
| (Shore Power) |
|
|
|
| (Shore Power) |
BW0120D
Note: Connect DK1 and DK2 of the battery charger go to the D1 and D2 terminals of the terminal block if a Master Control Systems Inc. Battery charger is installed. DK1 and DK2 are not polarity sensitive.
MN2415 | Receiving & Installation |